Permit Application Status

PRRES20183999


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20183999
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - COVERED DECK
12/03/2018
12/06/2018
08/08/2019
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
KIMBEL MECHANICAL SYSTEMS, INC, Address:1936 N SHILOH DR, Phone:(479) 756-1099  
RYAN@SUMMITHOMESKC.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 12/05/2018 12/05/2018
Steve Conrick
Residential Plan Review Approved 12/05/2018 12/03/2018
Kim Brennan
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,236.45 $1,236.45 Paid 12/06/2018
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 12/06/2018
8331507-Sewer Connection Fee $600.00 $600.00 Paid 12/06/2018
8331401-Water Tap Fee $3,409.00 $3,409.00 Paid 12/06/2018
8350015-Water Meter Fee $408.37 $408.37 Paid 12/06/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 12/21/2018 12/21/2018 12/21/2018
Underslab Plumbing Inspection - Residential Failed 1/15/2019 1/15/2019 at 8:00 AM 01/15/2019
Misc
Corrective Action Required
01/15/2019
* NO VISIBLE ADDRESS * BACKFILL NOT COMPLETE NO ACCESS
Sewer Service Inspection - R Passed 1/22/2019 at 1:00 PM 01/22/2019
Water Service Inspection - R Passed 1/24/2019 1/24/2019 at 11:31 AM 01/24/2019
Underslab Plumbing Inspection - Residential Passed 1/28/2019 1/28/2019 at 10:25 AM 01/28/2019
Misc
Resolved
01/28/2019
* NO VISIBLE ADDRESS * BACKFILL NOT COMPLETE NO ACCESS
Gas Piping Inspection - Residential Passed 3/20/2019 at 10:00 AM 03/20/2019
Gas Service Inspection - Residential Passed 3/20/2019 at 10:11 AM 03/20/2019
Electrical Service Inspection Passed 3/20/2019 at 10:21 AM 03/20/2019
All Rough Inspection - Residential Failed 3/20/2019 3/20/2019 at 10:31 AM 03/20/2019
Misc
Corrective Action Required
03/20/2019
1. Refer wall in kitchen should be 2-2x10 header. fix or provide provide engineers report. 2. Fire block at fire place where back wall is open to 2nd fl stud space 3. Fire stop master tub drain 4. Fire stop dryer vent 5. Install ledger locks or equivalent lag bolts at deck ledger board connection.
All Rough Inspection - Residential Passed 3/26/2019 3/26/2019 at 10:00 AM 03/26/2019
Misc
Resolved
03/26/2019
1. Refer wall in kitchen should be 2-2x10 header. fix or provide provide engineers report. 2. Fire block at fire place where back wall is open to 2nd fl stud space 3. Fire stop master tub drain 4. Fire stop dryer vent 5. Install ledger locks or equivalent lag bolts at deck ledger board connection.
Driveway Inspection Partial 4/16/2019 4/16/2019 04/16/2019
Misc
Informational
04/16/2019
PRE POUR INSPECTION The forms are up and there appears to be sufficient compacted aggregate.
Driveway Inspection Passed 4/23/2019 04/24/2019
Misc
Informational
04/16/2019
PRE POUR INSPECTION The forms are up and there appears to be sufficient compacted aggregate.
Sidewalk Inspection Partial 5/30/2019 (P.M.) 5/30/2019 05/31/2019
Misc
Informational
05/31/2019
PRE POUR INSPECTION The crew formed the sidewalk up but left the ADA section out for a later install. They will call back in the ADA at a later date.
Sidewalk Inspection Partial 6/4/2019 06/06/2019
Misc
Informational
05/31/2019
PRE POUR INSPECTION The crew formed the sidewalk up but left the ADA section out for a later install. They will call back in the ADA at a later date.
Sidewalk Inspection Partial 6/6/2019 (P.M.) 6/6/2019 06/06/2019
Misc
Informational
06/06/2019
PRE POUR INSPECTION The crew formed the sidewalk up but left the ADA section out for a later install. They will call back in the ADA at a later date.
Misc
Informational
06/06/2019
PRE POUR INSPECTION Inspection for the curb replacement at the ADA ramp section. The crew removed the existing curb to make sufficient room for an ADA compliant ramp. The curb is formed and I verified that it meets the City of Lee’s Summit’s standard details.
Sidewalk Inspection Partial 6/10/2019 6/11/2019 06/10/2019
Misc
Informational
06/06/2019
PRE POUR INSPECTION The crew formed the sidewalk up but left the ADA section out for a later install. They will call back in the ADA at a later date.
Misc
Informational
06/06/2019
PRE POUR INSPECTION Inspection for the curb replacement at the ADA ramp section. The crew removed the existing curb to make sufficient room for an ADA compliant ramp. The curb is formed and I verified that it meets the City of Lee’s Summit’s standard details.
Misc
Informational
06/10/2019
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate for the ADA ramp section of the sidewalk.
Occupancy Inspection - Codes Residential Temporary C of O 6/14/2019 6/14/2019 at 7:46 AM 06/14/2019
Misc
Corrective Action Required
06/14/2019
complete downspout at deck. final grading. sod splash blocks
Sidewalk Inspection Failed 7/2/2019 07/02/2019
Misc
Informational
06/10/2019
PRE POUR INSPECTION The crew formed the sidewalk up but left the ADA section out for a later install. They will call back in the ADA at a later date.
Misc
Informational
06/10/2019
PRE POUR INSPECTION Inspection for the curb replacement at the ADA ramp section. The crew removed the existing curb to make sufficient room for an ADA compliant ramp. The curb is formed and I verified that it meets the City of Lee’s Summit’s standard details.
Misc
Informational
06/10/2019
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate for the ADA ramp section of the sidewalk.
Misc
Corrective Action Required
07/02/2019
POST POUR INSPECTION. The ADA detectable warning panel section of the sidewalk has been damaged and needs replaced. Photos are attached.
Sidewalk Inspection Partial 7/8/2019 08/05/2019
Misc
Informational
07/02/2019
PRE POUR INSPECTION The crew formed the sidewalk up but left the ADA section out for a later install. They will call back in the ADA at a later date.
Misc
Informational
07/02/2019
PRE POUR INSPECTION Inspection for the curb replacement at the ADA ramp section. The crew removed the existing curb to make sufficient room for an ADA compliant ramp. The curb is formed and I verified that it meets the City of Lee’s Summit’s standard details.
Misc
Informational
07/02/2019
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate for the ADA ramp section of the sidewalk.
Misc
Corrective Action Required
07/02/2019
POST POUR INSPECTION. The ADA detectable warning panel section of the sidewalk has been damaged and needs replaced. Photos are attached.
Misc
Informational
08/05/2019
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate for the ADA replacement.
Sidewalk Inspection Passed 8/6/2019 08/08/2019
Occupancy Inspection - Codes Residential Full C of O 8/8/2019 8/8/2019 at 1:30 PM 08/08/2019
Misc
Resolved
08/08/2019
complete downspout at deck. final grading. sod splash blocks
Documents & Images
Date Uploaded File Type Document Name
12/06/2018 Receipt Receipt for transaction: 2018-007474
12/06/2018 Letter Codes Building Permit
12/12/2018 Plot Plan DOC121218-12122018090638
12/21/2018 Letter INSPECTION SUMMARY
01/15/2019 Letter INSPECTION SUMMARY
01/22/2019 Letter INSPECTION SUMMARY
01/24/2019 Letter INSPECTION SUMMARY
01/28/2019 Letter INSPECTION SUMMARY
03/20/2019 Letter INSPECTION SUMMARY
03/20/2019 Letter INSPECTION SUMMARY
03/20/2019 Letter INSPECTION SUMMARY
03/20/2019 Letter INSPECTION SUMMARY
03/26/2019 Letter INSPECTION SUMMARY
04/16/2019 Letter INSPECTION SUMMARY
04/24/2019 Letter INSPECTION SUMMARY
05/31/2019 Letter INSPECTION SUMMARY
06/06/2019 Letter INSPECTION SUMMARY
06/06/2019 Letter INSPECTION SUMMARY
06/10/2019 Letter INSPECTION SUMMARY
06/14/2019 Letter Codes Temporary Certificate of Occupancy
07/02/2019 ADA Panel Damaged
07/02/2019 Letter INSPECTION SUMMARY
08/05/2019 Letter INSPECTION SUMMARY
08/08/2019 Letter INSPECTION SUMMARY
08/08/2019 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home