Permit Application Status

PRRES20180333


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20180333
Building Permit - Residential
Certificate of Occupancy
CHOYCE LLC
NEW SINGLE FAMILY
NEW HOUSE FINISHED AND UNFINISHED BASEMENT COVERED AND UNCOVERED DECK
02/15/2018
03/07/2018
04/16/2019
Locations
Contacts
CHOYCE LLC, Address:PO BOX 847  
KC CUSTOM HOMES, Address:406 NW DONOVAN RD, Phone:(816) 564-5149  
MIKE BRYANT HEATING & COOLING , Address:1711 E 123RD , Phone:(913) 441-7807  
LUCAS ELECTRIC , Address:517 MARGARET LN, Phone:(816) 807-4432  
A BRIGHT PLUMBING LLC, Address:201 NE WOODBURY DR, Phone:(816) 867-4540  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 02/20/2018 02/21/2018
Brandon Kalwei
Plot Plan Review Approved 02/20/2018 02/16/2018
Troy Thompson
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $943.20 $943.20 Paid 03/07/2018
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 03/07/2018
8331504-EFHB Middle Big Creek, Full $602.64 $602.64 Paid 03/07/2018
8331507-Sewer Connection Fee $540.00 $540.00 Paid 03/07/2018
8331401-Water Tap Fee $3,343.00 $3,343.00 Paid 03/07/2018
8350015-Water Meter Fee $431.83 $431.83 Paid 03/07/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 3/7/2018 3/7/2018 at 4:40 PM 03/07/2018
Sewer Service Inspection - R Passed 3/29/2018 at 11:30 AM 03/29/2018
Water Service Inspection - R Passed 3/30/2018 03/30/2018
Underslab Plumbing Inspection - Residential Passed 4/5/2018 4/5/2018 at 9:00 AM 04/05/2018
Gas Service Inspection - Residential Passed 8/9/2018 8/9/2018 08/09/2018
Electrical Service Inspection Passed 8/9/2018 8/9/2018 08/09/2018
All Rough Inspection - Residential Failed 8/9/2018 8/9/2018 at 10:10 AM 08/09/2018
Misc
Corrective Action Required
08/09/2018
**NOT READY FOR INSPECTION. PROVIDE PLAN ON SITE. CORRECT THE BELOW LIST. NOT A COMPLETE LIST. FRAMING: -Fb main fl fireplace space and shelf wall space from roof -Block exterior door per security code; fill in gap behind hinges with solid wood -Front bed wall supporting the hip rafters is not a bearing wall, so is the bath/master closet wall -Anchor garage sill plate within 12” of breaks -Gap under some garage studs -Nail corner studs per code (16d@12” oc or equivalence) -Sheath floor opening at kitchen -Fb basement wall space vertically every max ten ft; Fb basement wall space from ceiling furdown and soffit space; Fb basement wall space from joist at west side of basement -Anchor basement sill plate at max 6 ft interval and within 12” of breaks -Install joist hangers along stair wall -Install hanger for double joist connection at stair -Complete framing around basement fireplace and fb as required; PLUMBING: -Vent master tub trap per code. The connection to the vent cannot be lower than the trap weir -Protect plumbing at wall bottom plate behind basement bath sinks; protect at wet bar ELECTRICAL: -Install a receptacle within 25 ft of AC -Complete electrical to outside lights and receptacle and electrical inside throughout -Secure home run wiring; protect wiring -Provide wall receptacle spacing per code at rear basement family rm -Secure basement fireplace receptacle box -Securely fasten NM cable at interval no more than 4.5 ft -Parallel wiring inside return air space above bottom stair landing MECHANICAL: -Complete dryer vent to outside -Complete main fl fireplace vent connection, install insulation vent shield , and provide min 1” clearance from combustible -Vent all bath fans -Provide min clearance above basement fireplace from combustible per manufacturer **DO NOT INSULATE
All Rough Inspection - Residential Failed 8/14/2018 8/14/2018 at 1:00 PM 08/14/2018
Misc
Corrective Action Required
08/09/2018
**NOT READY FOR INSPECTION. PROVIDE PLAN ON SITE. CORRECT THE BELOW LIST. NOT A COMPLETE LIST. FRAMING: -Fb main fl fireplace space and shelf wall space from roof -Block exterior door per security code; fill in gap behind hinges with solid wood -Front bed wall supporting the hip rafters is not a bearing wall, so is the bath/master closet wall -Anchor garage sill plate within 12” of breaks -Gap under some garage studs -Nail corner studs per code (16d@12” oc or equivalence) -Sheath floor opening at kitchen -Fb basement wall space vertically every max ten ft; Fb basement wall space from ceiling furdown and soffit space; Fb basement wall space from joist at west side of basement -Anchor basement sill plate at max 6 ft interval and within 12” of breaks -Install joist hangers along stair wall -Install hanger for double joist connection at stair -Complete framing around basement fireplace and fb as required; PLUMBING: -Vent master tub trap per code. The connection to the vent cannot be lower than the trap weir -Protect plumbing at wall bottom plate behind basement bath sinks; protect at wet bar ELECTRICAL: -Install a receptacle within 25 ft of AC -Complete electrical to outside lights and receptacle and electrical inside throughout -Secure home run wiring; protect wiring -Provide wall receptacle spacing per code at rear basement family rm -Secure basement fireplace receptacle box -Securely fasten NM cable at interval no more than 4.5 ft -Parallel wiring inside return air space above bottom stair landing MECHANICAL: -Complete dryer vent to outside -Complete main fl fireplace vent connection, install insulation vent shield , and provide min 1” clearance from combustible -Vent all bath fans -Provide min clearance above basement fireplace from combustible per manufacturer **DO NOT INSULATE
Misc
Corrective Action Required
08/14/2018
* NO PLANS ON SITE*
All Rough Inspection - Residential Passed 8/20/2018 8/20/2018 at 1:20 PM 08/20/2018
Misc
Resolved
08/20/2018
**NOT READY FOR INSPECTION. PROVIDE PLAN ON SITE. CORRECT THE BELOW LIST. NOT A COMPLETE LIST. FRAMING: -Fb main fl fireplace space and shelf wall space from roof -Block exterior door per security code; fill in gap behind hinges with solid wood -Front bed wall supporting the hip rafters is not a bearing wall, so is the bath/master closet wall -Anchor garage sill plate within 12” of breaks -Gap under some garage studs -Nail corner studs per code (16d@12” oc or equivalence) -Sheath floor opening at kitchen -Fb basement wall space vertically every max ten ft; Fb basement wall space from ceiling furdown and soffit space; Fb basement wall space from joist at west side of basement -Anchor basement sill plate at max 6 ft interval and within 12” of breaks -Install joist hangers along stair wall -Install hanger for double joist connection at stair -Complete framing around basement fireplace and fb as required; PLUMBING: -Vent master tub trap per code. The connection to the vent cannot be lower than the trap weir -Protect plumbing at wall bottom plate behind basement bath sinks; protect at wet bar ELECTRICAL: -Install a receptacle within 25 ft of AC -Complete electrical to outside lights and receptacle and electrical inside throughout -Secure home run wiring; protect wiring -Provide wall receptacle spacing per code at rear basement family rm -Secure basement fireplace receptacle box -Securely fasten NM cable at interval no more than 4.5 ft -Parallel wiring inside return air space above bottom stair landing MECHANICAL: -Complete dryer vent to outside -Complete main fl fireplace vent connection, install insulation vent shield , and provide min 1” clearance from combustible -Vent all bath fans -Provide min clearance above basement fireplace from combustible per manufacturer **DO NOT INSULATE
Misc
Corrective Action Required
08/20/2018
ok to sheet rock
Driveway Inspection Partial 11/2/2018 11/2/2018 11/02/2018
Misc
Corrective Action Required
11/02/2018
Arrived to do inspection. Work still needed to be done. Returned after 2pm and had to make more adjustments. Inspection is complete. Aggregate was compacted and forms set to spec. Ready for pour.
Misc
Informational
11/08/2018
Joe Starlin 11/08/2018 7:02 AM The sidewalk has been inspected and is in spec.
Driveway Inspection Passed 11/5/2018 at 1:00 PM 11/07/2018
Misc
Corrective Action Required
11/02/2018
Arrived to do inspection. Work still needed to be done. Returned after 2pm and had to make more adjustments. Inspection is complete. Aggregate was compacted and forms set to spec. Ready for pour.
Corrective Action Required
11/07/2018
Joe Starlin 11/07/2018 3:57 PM Inspected the driveway 11/5/2018. The driveway is in spec.
Sidewalk Inspection Passed 11/5/2018 at 1:15 PM 11/08/2018
Misc
Informational
11/08/2018
The sidewalk has been inspected and after aggregate and form adjustments it is in spec. Ready for pour.
Misc
Informational
11/08/2018
Joe Starlin 11/08/2018 7:11 AM The sidewalk has been inspected and meets spec.
Sidewalk Inspection Passed 11/2/2018 11/2/2018 11/08/2018
Misc
Corrective Action Required
11/02/2018
The sidewalk has been inspected and after aggregate and form adjustments it is in spec. Ready for pour.
Misc
Informational
11/08/2018
Inspected sidewalk and it has met the spec.Joe Starlin 11/08/2018 7:39 AM
Occupancy Inspection - Codes Residential Failed 12/21/2018 at 7:00 AM 12/21/2018
Misc
Corrective Action Required
12/21/2018
- LOCKOUTS ON HARDWIRED APPLIANCES. - GFCI IN GARAGE NOT WORKING ALL OUTLETS NEED TO BE GFCI. -OUTLETS IN UNFINISHED BSMT NOT GFCI. - BAR SINK FAUCET INCOMPLETE. -LAUNDRY SINK NOT INSTALLED, CAP OR INSTALL. -HAMMER ARRESTORS ON LAUNDRY SUPPLY. - SUPPORT VENT PIPE FOR FURNACE. -SHEETROCK UNDER STAIRS. -INSTALL LAG BOLT PER MANUFACTURE, PROVIDE LISTING ON BOLTS USED. NEED TO BE CLOSER THAN 16"O.C. -NO DECK TO POST ATTACHMENT. CONNECT DECK POST TO DECK PER CODE FOR UPLIFT. - LAWN SPRINKLER PERMIT - SOD EROSION CONTROL, CLEAN STREET, WATER METER FLUSH WITH GRADE.
Occupancy Inspection - Codes Residential Temporary C of O 12/28/2018 12/28/2018
Misc
Partial Correction
01/03/2019
- SOD , WATER METER FLUSH WITH GRADE.
Misc
Corrective Action Required
01/03/2019
* SOD * BRING WATER METER TO GRADE
Occupancy Inspection - Codes Residential Temporary C of O 1/3/2019 1/3/2019 01/03/2019
Misc
Partial Correction
01/03/2019
- SOD , WATER METER FLUSH WITH GRADE.
Misc
Corrective Action Required
01/03/2019
*SOD * BRING WATER METER TO GRADE
Occupancy Inspection - Codes Residential Temporary C of O 2/21/2019 at 11:00 AM 02/21/2019
Misc
Resolved
04/16/2019
SOD SPLASH BLOCKSRAISE WATER METER TO GRADE
Plot Plan Inspection Passed 4/16/2019 at 10:45 AM 04/16/2019
Occupancy Inspection - Codes Residential Full C of O 4/16/2019 4/16/2019 at 11:11 AM 04/16/2019
Documents & Images
Date Uploaded File Type Document Name
02/15/2018 Letter Codes Residential Plan Review
03/07/2018 Receipt Receipt for transaction: 2018-000830
03/07/2018 Letter Codes Building Permit
03/07/2018 Letter Inspection Summary
03/09/2018 Plot Plan DOC030818-018
03/29/2018 Letter Inspection Summary
03/30/2018 Letter Inspection Summary
04/05/2018 Letter Inspection Summary
08/09/2018 Letter Inspection Summary
08/14/2018 Letter Inspection Summary
08/20/2018 Letter Inspection Summary
11/02/2018 Letter Inspection Summary
11/02/2018 Letter Inspection Summary
11/02/2018 Letter Inspection Summary
11/07/2018 Letter DE-Daily Inspection Summary
11/08/2018 Letter DE-Daily Inspection Summary
12/21/2018 Letter INSPECTION SUMMARY
12/28/2018 Letter Codes Temporary Certificate of Occupancy
01/03/2019 Letter Codes Temporary Certificate of Occupancy
02/21/2019 Letter Codes Temporary Certificate of Occupancy
04/16/2019 Letter INSPECTION SUMMARY
04/16/2019 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home