Permit Application Status

PRRES20173920


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20173920
Building Permit - Residential
Final Completion
MUENSTERMANN JANET
REPAIR REPLACE UPGRADE
HVAC
12/04/2017
12/04/2017
03/27/2018
Locations
Contacts
LEES SUMMIT HEATING/COOLING INC, Address:1050 SE CENTURY DR, Phone:(816) 525-7218  
MUENSTERMANN JANET, Address:50 SW 1501 RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 12/04/2017 12/04/2017
Development Center
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Repair/Replace/Upgrade $157.34 $157.34 Paid 12/04/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Mechanical Inspection - Residential Partial 12/7/2017 at 11:15 AM 12/07/2017
Misc
Corrective Action Required
12/07/2017
CONDENSATE DRAIN LINE FROM ATTIC UNIT: PRESENTLY SECURED AT ONE PLACE AT FURNACE. SECURE AT TWO ADDITIONAL LOCATIONS.
Rough Mechanical Inspection - Residential Passed 3/19/2018 03/19/2018
Misc
Resolved
03/19/2018
CONDENSATE DRAIN LINE FROM ATTIC UNIT: PRESENTLY SECURED AT ONE PLACE AT FURNACE. SECURE AT TWO ADDITIONAL LOCATIONS.
Final Mechanical Inspection Failed 12/7/2017 3/19/2018 at 10:25 AM 03/19/2018
Miscellaneous Correction
Corrective Action Required
03/19/2018
IRC R703.1 SEALING OF EXTERIOR WALL: SEAL WALL WHERE LINE SETS PENETRATE.
Miscellaneous Correction
Corrective Action Required
03/19/2018
NEC 350.30; IRC 3802.1: LIQUIDTIGHT FLEXIBLE NON-METALLIC ELECTRICAL WHIP MUST BE SECURED TO STRUCTURE WITHIN 12" OF ENTRY TO A/C DISCONNECT ENCLOSURE. ZIP-TYING TO LINESET DOES NOT SATISFY ELECTRICAL CODE REQUIREMENT.
Final Mechanical Inspection Not Ready 3/26/2018 3/26/2018 at 11:05 AM 03/26/2018
Miscellaneous Correction
Corrective Action Required
03/19/2018
IRC R703.1 SEALING OF EXTERIOR WALL: SEAL WALL WHERE LINE SETS PENETRATE.
Miscellaneous Correction
Corrective Action Required
03/19/2018
NEC 350.30; IRC 3802.1: LIQUIDTIGHT FLEXIBLE NON-METALLIC ELECTRICAL WHIP MUST BE SECURED TO STRUCTURE WITHIN 12" OF ENTRY TO A/C DISCONNECT ENCLOSURE. ZIP-TYING TO LINESET DOES NOT SATISFY ELECTRICAL CODE REQUIREMENT.
Final Mechanical Inspection Passed 3/27/2018 at 9:20 AM 03/27/2018
Miscellaneous Correction
Resolved
03/27/2018
IRC R703.1 SEALING OF EXTERIOR WALL: SEAL WALL WHERE LINE SETS PENETRATE.
Miscellaneous Correction
Resolved
03/27/2018
NEC 350.30; IRC 3802.1: LIQUIDTIGHT FLEXIBLE NON-METALLIC ELECTRICAL WHIP MUST BE SECURED TO STRUCTURE WITHIN 12" OF ENTRY TO A/C DISCONNECT ENCLOSURE. ZIP-TYING TO LINESET DOES NOT SATISFY ELECTRICAL CODE REQUIREMENT.
Documents & Images
Date Uploaded File Type Document Name
12/04/2017 Receipt Receipt for transaction: 2017-007512
12/04/2017 Letter Codes Building Permit
12/04/2017 Scope of Work DOC120417-006
12/04/2017 Letter Codes Building Permit
12/07/2017 Letter Inspection Summary
03/19/2018 Letter Inspection Summary
03/26/2018 Letter Inspection Summary
03/27/2018 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home