Permit Application Status

PRRES20171691


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20171691
Building Permit - Residential
Certificate of Occupancy
D AND D AVIATION INC
NEW SINGLE FAMILY
NEW SINGLE FAMILY FINISHED BASEMENT COVERED DECK
05/25/2017
06/02/2017
11/21/2017
05/04/2018
Locations
Contacts
D AND D AVIATION INC, Address:5282 NE ASH GROVE CT  
D AND D BUILDING INC, Address:PO BOX 7014, Phone:(816) 491-2125  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
INTREPID ELECTRIC LLC, Address:620 S KISNER CIR, Phone:(816) 796-2781  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 06/05/2017 06/01/2017
Jonathon Hilton
Residential Plan Review Approved 06/05/2017 06/01/2017
Jonathon Hilton
08 Designate locations of smoke detectors and carbon monoxide detectors
Corrective Action Required
06/01/2017

Designate locations of smoke detectors and carbon monoxide detectors. (IRC Section R314 and R315)
11 Designate R-value(s) for floors, walls, ceilings, roof/ceilings.
Corrective Action Required
06/01/2017

Designate R-value(s) for floors, walls, ceilings, roof/ceilings. (LSCO 7-802)
12 Detail required separation between garage and living area including door
Corrective Action Required
06/01/2017

Detail required separation between garage and living area including door, door closer and gypsum board. (IRC R302.5) *** Indicate self closing device on garage door and note fire rated time.
20 Footings, column pads, piers and grade beams - reinforcement
Corrective Action Required
06/01/2017

Footings, column pads, piers and grade beams - reinforcement size and spacing.
32 Size, height, spacing of studs. (IRC Section R602)
Corrective Action Required
06/01/2017

Size, height, spacing of studs. (IRC Section R602)
Plot Plan Review Rejected 05/30/2017 05/25/2017
Jonathon Hilton
Basement opening elevations
Resolved
05/26/2017

Minimum Building Opening Elevation (MBOE) and location on structure must be provided on the plot plan. *Can you please add this to the plot plan just so it shows it on the plot plan. MBOE says 904.72
Residential Plan Review Rejected 05/30/2017 05/25/2017
Jonathon Hilton
08 Designate locations of smoke detectors and carbon monoxide detectors
Corrective Action Required
05/25/2017

Designate locations of smoke detectors and carbon monoxide detectors. (IRC Section R314 and R315)
11 Designate R-value(s) for floors, walls, ceilings, roof/ceilings.
Corrective Action Required
05/25/2017

Designate R-value(s) for floors, walls, ceilings, roof/ceilings. (LSCO 7-802)
12 Detail required separation between garage and living area including door
Corrective Action Required
05/25/2017

Detail required separation between garage and living area including door, door closer and gypsum board. (IRC R302.5) *** Indicate self closing device on garage door and note fire rated time.
20 Footings, column pads, piers and grade beams - reinforcement
Corrective Action Required
05/25/2017

Footings, column pads, piers and grade beams - reinforcement size and spacing.
32 Size, height, spacing of studs. (IRC Section R602)
Corrective Action Required
05/25/2017

Size, height, spacing of studs. (IRC Section R602)
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,149.44 $1,149.44 Paid 06/02/2017
8331507-Sewer Connection Fee $570.00 $570.00 Paid 06/02/2017
Water Tap Fee $3,310.00 $3,310.00 Paid 06/02/2017
Water Meter Fee $405.36 $405.36 Paid 06/02/2017
Right of Way Permit Fee $75.00 $75.00 Paid 06/02/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 6/15/2017 (2:30) 6/15/2017 06/15/2017
Underslab Plumbing Inspection - Residential Passed 6/26/2017 6/26/2017 06/26/2017
Sewer Service Inspection - R Passed 6/26/2017 (9:15) 6/26/2017 06/26/2017
Water Service Inspection - R Passed 6/27/2017 (9:30) 6/27/2017 06/27/2017
Suspended Slab Inspection Failed 7/3/2017 (4:00) 7/3/2017 07/03/2017
Misc
Corrective Action Required
07/03/2017
-PROVIDE SUSPENDED GARAGE FLOOR STRUCTURAL PLAN ON SITE. REBAR LAYOUT SHALL BE PER PLAN -INSTALL I BEAM SUPPORT COLUMN AND BRACE FLOOR -INSTALL REBAR CHAIRS
Suspended Slab Inspection Failed 7/5/2017 (8:00) 7/5/2017 07/05/2017
Misc
Corrective Action Required
07/03/2017
-PROVIDE SUSPENDED GARAGE FLOOR STRUCTURAL PLAN ON SITE. **PLACE REBARS IN THE CORRUGATIONS AND TIE TO PERPENDICULAR REBARS **PLACE 10 FT REBAR OVER I BEAM @ 8" OC W/ 1"-1.5" OF TOP CONCRETE COVER
Suspended Slab Inspection Passed 7/6/2017 (8:00) 7/6/2017 07/05/2017
Misc
Resolved
07/05/2017
-PROVIDE SUSPENDED GARAGE FLOOR STRUCTURAL PLAN ON SITE. **PLACE REBARS IN THE CORRUGATIONS AND TIE TO PERPENDICULAR REBARS **PLACE 10 FT REBAR OVER I BEAM @ 8" OC W/ 1"-1.5" OF TOP CONCRETE COVER
Erosion Control Inspection Residential Failed 8/18/2017 08/18/2017
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
08/18/2017
DEFICIENT EROSION CONTROL INSTALLATION. INSTALL EROSION CONTROL ALONG THE BACK OF LOT. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Gas Service Inspection - Residential Failed 8/18/2017 8/18/2017 08/18/2017
Misc
Corrective Action Required
08/18/2017
**INSPECTION DENIED DUE TO EROSION CONTROL DEFICIENCY
Electrical Service Inspection Passed 8/25/2017 8/25/2017 08/25/2017
Erosion Control Inspection Residential Partial 8/25/2017 08/25/2017
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
08/18/2017
8/25/17-EROSION CONTROL IN COMPLIANCE
Gas Service Inspection - Residential Passed 8/25/2017 8/25/2017 08/25/2017
Misc
Resolved
08/25/2017
**INSPECTION DENIED DUE TO EROSION CONTROL DEFICIENCY
All Rough Inspection - Residential Failed 8/25/2017 8/25/2017 08/25/2017
Misc
Corrective Action Required
08/25/2017
FRAMING: -FRAME CS PF WALLS PER PLAN -BRACE INTERIOR WALLS PER PLAN -HAVE ENGINEER OK/ADDRESS THE OVERNOTCHED DOUBLE JOIST AT STAIR WALL THAT CARRIES LVL LOAD -AT FRONT BED&BATH, MOVE THE ROOF SUPPORT STRUTS TO WALL WITH DOUBLE JOIST BELOW -INSTALL EXTERIOR DOOR FRAMES PER LS SECURITY CODE -SOLIDBLOCK ALL LAPPED JOISTS ABOVE I BEAMS -PROVIDE FULL SOLIDBLOCKING SUPPORT UNDER I BEAM (I BEAM BETWEEN KITCHEN AND LIVING RM) POINT LOAD -FIREBLOCKING: FB THE TRIANGULAR SPACE AT FIREPLACE SHELF FROM ROOF; FB FLOOR AT TRAP; FB BASEMENT WALL PER CODE; FB DEAD SPACE FROM FURDOWN SPACE AT BASEMENT TUB MECHANICAL: -INSTALL B-VENT SHIELD FOR HEARTH FIREPLACE -FIX THE DENTED B-VENT -CONNECT DUCT TO BATHFAN AT FRONT BATH ELECTRICAL: -INSTALL A WALL RECEPTACLE IN HALLWAY OUTSIDE BASEMENT BEDS PLUMBING: -STRAP OVERBORED WALL TOP PLATE AT FRONT BATH **OK TO INSULATE
All Rough Inspection - Residential Failed 8/31/2017 8/31/2017 08/31/2017
Misc
Corrective Action Required
08/25/2017
FRAMING: -FRAME CS PF WALLS PER PLAN **HAVE ENGINEER ADDRESS THIS. PLAN CALLS FOR A/4 CSPF WALL DETAIL -BRACE INTERIOR WALLS PER PLAN -HAVE ENGINEER OK/ADDRESS THE OVERNOTCHED DOUBLE JOIST AT STAIR WALL THAT CARRIES LVL LOAD -INSTALL EXTERIOR DOOR FRAMES PER LS SECURITY CODE -FIREBLOCKING: FB THE TRIANGULAR SPACE AT FIREPLACE SHELF FROM ROOF; FB WALL SPACE FROM CEILING FURDOWN SPACE AT BASEMENT BATH MECHANICAL: -INSTALL B-VENT SHIELD FOR HEARTH FIREPLACE -FIX THE DENTED B-VENT PLUMBING: -STRAP OVERBORED WALL TOP PLATE AT FRONT BATH **STRAP REQUIRED WHEN TOP PLATES ARE BORED MORE THAN 50% **OK TO INSULATE
All Rough Inspection - Residential Failed 9/5/2017 9/5/2017 09/05/2017
Misc
Corrective Action Required
08/31/2017
FRAMING: -FRAME CS PF WALLS PER PLAN **HAVE ENGINEER ADDRESS THIS. PLAN CALLS FOR A/4 CSPF WALL DETAIL -BRACE INTERIOR WALLS PER PLAN -INSTALL EXTERIOR DOOR FRAMES PER LS SECURITY CODE -FIREBLOCKING: FB WALL SPACE FROM CEILING FURDOWN SPACE AT BASEMENT BATH MECHANICAL: -INSTALL B-VENT SHIELD FOR HEARTH FIREPLACE -FIX THE DENTED B-VENT PLUMBING: -STRAP OVERBORED WALL TOP PLATE AT FRONT BATH **STRAP REQUIRED WHEN TOP PLATES ARE BORED MORE THAN 50% **OK TO INSULATE
All Rough Inspection - Residential Failed 9/7/2017 9/7/2017 09/07/2017
Misc
Corrective Action Required
09/05/2017
FRAMING: -FRAME CS PF WALLS PER PLAN **HAVE ENGINEER ADDRESS THIS. PLAN CALLS FOR A/4 CSPF WALL DETAIL MECHANICAL: -INSTALL INSULATION SHIELD FOR THE HEARTH FIREPLACE VENT AS REQUIRED PER IRC G2426.4 (IGFC 502.4). MAKE SURE THE SHIELD PROVIDE MIN. 1" CLEARANCE AROUND THE VENT, SEPARATING THE BLOWN-IN INSULATION FROM THE VENT **OK TO INSULATE
Driveway Inspection Partial 11/21/2017 11/21/2017 at 10:30 AM 11/21/2017
Sidewalk Inspection Partial 11/21/2017 at 10:35 AM 11/21/2017
Erosion Control Inspection Residential Passed 12/07/2017
DCM2 ESC DEFICIENT INSTALLATION
Resolved
12/07/2017
8/25/17-EROSION CONTROL IN COMPLIANCE
Occupancy Inspection - Codes Residential Failed 12/7/2017 12/7/2017 at 3:15 PM 12/07/2017
Misc
Corrective Action Required
12/07/2017
-OBTAIN LAWN IRRIGATION PERMIT -DRIVEWAY&SIDEWALK NOT APPROVED ON RECORD -ALLROUGH NOT APPROVED -PIERS NOT INSPECTED&APPROVED -RAISE WATER METER W/ LID FLUSHED TO GRADE. MAINTAIN DISTANCE FROM METER TO LID IS 14"-18". -EXPOSE SEWER TRACER BOX -INSTALL SPLASHBLOCKS -SEAL EXTERIOR WALL: IRRIGATION WATER LINE PENETRATION, SEAL ABOVE GFCI RECEPTACLE NEAR AC -FIRESTOP PENETRATIONS BELOW GARAGE SINK -THE LUMINAIRE ABOVE MAKE-UP TABLE AND HALOGEN LIGHT INSIDE MASTERT CLOSET ARE NON-COMPLIANT -MASTER BED SMOKE ALARM AND BASEMENT BED SMOKE ALARM ARE NOT INTERCONNECTED WITH THE REST OF THE ALARM SYSTEM -INSTALL SECURITY COMPLIANT STRIKE PLATE FOR BASEMENT WALKOUT DOOR Sec. 7-1408.2. - Strike plates. Exterior door strike plates shall be a minimum of eighteen (18) gauge metal with four (4) offset screw holes. Strike plates shall be attached to wood with not less than three (3) inch wood screws, which shall have a minimum of one (1) inch penetration into the nearest stud. Note: For side lighted units, refer to Section 7-1408.5. (Ord. No. 6600, § 1, 3-13-2008; Ord. No. 6634, § 5, 6-5-2008) -LOCATE AND MAKE ACCESSIBLE THE SEWER CLEANOUT AND UFER GROUNDING CONNECTION
Driveway Inspection Passed 12/12/2017 at 3:00 PM 12/12/2017
Sidewalk Inspection Passed 12/12/2017 at 3:05 PM 12/12/2017
Occupancy Inspection - Codes Residential Temporary C of O 12/13/2017 12/13/2017 at 4:00 PM 12/13/2017
Misc
Corrective Action Required
12/07/2017
-RAISE WATER METER W/ LID FLUSHED TO GRADE. MAINTAIN DISTANCE FROM METER TO LID IS 14"-18". -PIERS NOT INSPECTED&APPROVED. HAVE ENGINEER INSPECT&OK THE PIERS -EXPOSE SEWER TRACER BOX **INSTALL THE TRACER BOX REQUIRED BY CITY DESIGN -THE HALOGEN LIGHT INSIDE THE MASTER CLOSET ARE LOCATED WITHIN THE "CLOSET STORAGE SPACE" AS DEFINED BY NEC 410.2. FIGURE 410.2. ANY LUMINAIRE LOCATED INSIDE THE CLOSET MUST BE LOCATED MINIMUM DISTANCE FROM THE "CLOSET STORAGE SPACE" PER NEC SECTION 410.16(C)
All Rough Inspection - Residential Passed 01/12/2018
Misc
Resolved
01/12/2018
FRAMING: -FRAME CS PF WALLS PER PLAN **HAVE ENGINEER ADDRESS THIS. PLAN CALLS FOR A/4 CSPF WALL DETAIL MECHANICAL: -INSTALL INSULATION SHIELD FOR THE HEARTH FIREPLACE VENT AS REQUIRED PER IRC G2426.4 (IGFC 502.4). MAKE SURE THE SHIELD PROVIDE MIN. 1" CLEARANCE AROUND THE VENT, SEPARATING THE BLOWN-IN INSULATION FROM THE VENT **OK TO INSULATE
Occupancy Inspection - Codes Residential Temporary C of O 5/2/2018 5/2/2018 at 1:56 PM 05/02/2018
Misc
Corrective Action Required
12/13/2017
-THE LED LIGHT INSIDE THE MASTER CLOSET ARE LOCATED WITHIN THE "CLOSET STORAGE SPACE" AS DEFINED BY NEC 410.2. FIGURE 410.2. ANY LUMINAIRE LOCATED INSIDE THE CLOSET MUST BE LOCATED MINIMUM DISTANCE FROM THE "CLOSET STORAGE SPACE" PER NEC SECTION 410.16(C) OR IS LISTED TO BE INSTALLED WITHIN A "STARAGE SPACE" AS DEFINED BY 410.2
Occupancy Inspection - Codes Residential Full C of O 5/7/2018 5/4/2018 at 2:46 PM 05/04/2018
Misc
Resolved
05/04/2018
-THE LED LIGHT INSIDE THE MASTER CLOSET ARE LOCATED WITHIN THE "CLOSET STORAGE SPACE" AS DEFINED BY NEC 410.2. FIGURE 410.2. ANY LUMINAIRE LOCATED INSIDE THE CLOSET MUST BE LOCATED MINIMUM DISTANCE FROM THE "CLOSET STORAGE SPACE" PER NEC SECTION 410.16(C) OR IS LISTED TO BE INSTALLED WITHIN A "STARAGE SPACE" AS DEFINED BY 410.2
Documents & Images
Date Uploaded File Type Document Name
05/25/2017 Letter Codes Residential Plan Review
06/02/2017 Receipt Receipt for transaction: 2017-003351
06/02/2017 Letter Codes Building Permit
06/05/2017 Plot Plan DOC060517
06/08/2017 Engineer Report/Study DOC060817-001
06/15/2017 Letter Inspection Summary
06/26/2017 Letter Inspection Summary
06/27/2017 Letter Inspection Summary
07/03/2017 Letter Inspection Summary
07/05/2017 Letter Inspection Summary
07/05/2017 Letter Inspection Summary
08/18/2017 Letter Inspection Summary
08/25/2017 Letter Inspection Summary
08/31/2017 Letter Inspection Summary
09/05/2017 Letter Inspection Summary
09/07/2017 Letter Inspection Summary
12/07/2017 Letter Inspection Summary
12/13/2017 Letter Codes Temporary Certificate of Occupancy
12/18/2017 inpsection report 20171691
12/18/2017 inspectin report 20172691
01/29/2018 Letter Codes 10 Day Letter
02/01/2018 Code Mod Request DOC020118-010
05/04/2018 Letter Field Certificate of Occupancy
05/07/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home