Permit Application Status

PRRES20171326


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20171326
Building Permit - Residential
Certificate of Occupancy
MAR INVESTMENTS INC
NEW SINGLE FAMILY
NEW SINGLE FAMILY UNFINISHED BASEMENT
04/27/2017
05/02/2017
10/24/2017
12/20/2017
Locations
Contacts
MAR INVESTMENTS INC, Address:PO BOX 847  
KEVIN HIGDON CONSTRUCTION, LLC, Address:P O BOX 847, Phone:(816) 524-9797  
PRAIRIE CENTER PLUMBING HEATING & A/C, Address:242 N MARION, Phone:(913) 829-6263  
LUCAS ELECTRIC , Address:517 MARGARET LN, Phone:(816) 807-4432  
PRAIRIE CENTER PLUMBING HEATING & A/C, Address:242 N MARION, Phone:(913) 829-6263  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 05/04/2017 05/02/2017
Jonathon Hilton
Residential Plan Review Approved 05/04/2017 05/02/2017
Jonathon Hilton
Plot Plan Review Approved 05/01/2017 05/02/2017
Nick Lightner
As-graded plot plan
Resolved
05/02/2017

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy. *Please add in a bubble " AS-GRADED PLOT PLAN IS REQUIRED PRIOR TO SODDING "
Misc
Resolved
05/02/2017

*East side of the house side yard set back. This doesn't meet the set back for this area. Can the house be moved? If not we will need in writing asking for a directors signature to sign off on what's been proposed.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,091.71 $1,091.71 Paid 05/02/2017
8331507-Sewer Connection Fee $570.00 $570.00 Paid 05/02/2017
8331401-Water Tap Fee $3,310.00 $3,310.00 Paid 05/02/2017
8350015-Water Meter Fee $405.36 $405.36 Paid 05/02/2017
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 05/02/2017
8331504-EFHB Middle Big Creek, Full $636.12 $636.12 Paid 05/02/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 5/12/2017 (1:30) 5/12/2017 05/12/2017
Underslab Plumbing Inspection - Residential Passed 6/5/2017 6/5/2017 06/05/2017
Erosion Control Inspection Residential Failed 06/05/2017
Sewer Service Inspection - R Passed 6/30/2017 (3:00) 6/30/2017 06/30/2017
Water Service Inspection - R Passed 7/5/2017 (8:45) 7/5/2017 07/05/2017
Gas Piping Inspection - Residential Not Ready 7/10/2017 7/10/2017 07/10/2017
Misc
Corrective Action Required
07/10/2017
lack of erosion control and gravel in the street. support wardflex at furnace firepalce not installed wardflex isn't bonded
Piers/Caissons Inspection - Residential Passed 7/25/2017 07/25/2017
Suspended Slab Inspection Passed 7/25/2017 07/25/2017
Erosion Control Inspection Residential Partial 07/25/2017
All Rough Inspection - Residential Not Ready 7/31/2017 07/31/2017
Misc
Corrective Action Required
07/31/2017
no plans on site-no inspection erorosion control down, gravel in the street. note::: fireplace flue not furred down, fireplace flue clearance, firestop dead space for hood to kitchen,firestop flue chase, support stairs stringers.
All Rough Inspection - Residential Failed 7/31/2017 07/31/2017
Misc
Corrective Action Required
07/31/2017
-missing lvl's basement, 1st floor, attic for roof support. revise plans or install per plans. check all roof support and location of lvls at re-inspection. - fur out fireplace flue, flue clearance to pvc and wood. - connect gas line at fireplace, protect wardflex at fireplace. -firestop kitchen hood dead space. - firestop garage wall fur down. -support bottom of stairs stringers to 2nd floor. -nail dbl josit 16" oc.c -snow blocking mstr bedroom bathroom. support ridge over 3rd car.
Electrical Service Inspection Passed 7/31/2017 07/31/2017
All Rough Inspection - Residential Failed 8/3/2017 08/03/2017
Misc
Corrective Action Required
07/31/2017
-missing lvl's basement, 1st floor, attic for roof support. revise plans or install per plans. check all roof support and location of lvls at re-inspection. - connect gas line at fireplace, protect wardflex at fireplace. *OK to insulate / rock, but don't cover structure that still needs to be inspected upon receipt of revised plans.
Gas Piping Inspection - Residential Failed 8/14/2017 8/14/2017 08/14/2017
Misc
Corrective Action Required
07/10/2017
not holding pressure wardflex isn't bonded
Gas Piping Inspection - Residential Failed 8/17/2017 8/17/2017 at 7:30 AM 08/17/2017
Misc
Corrective Action Required
08/14/2017
not holding pressure wardflex isn't bonded Denied - gravel from one end of Blackstone to the other . clean street and recall.
Erosion Control Inspection Residential Failed 8/17/2017 at 7:45 AM 08/17/2017
Misc
Corrective Action Required
08/17/2017
clean entire street. from Benziger to stoneybrook.
Gas Piping Inspection - Residential Failed 8/24/2017 at 10:20 AM 08/24/2017
Misc
Corrective Action Required
08/17/2017
Pressure OK. Conductor from UFA ground was disconnected, then used to bond the gas line. Reconnect UFA ground; bond gas line.
Gas Piping Inspection - Residential Passed 8/28/2017 at 3:15 PM 08/28/2017
Misc
Resolved
08/28/2017
Pressure OK. Conductor from UFA ground was disconnected, then used to bond the gas line. Reconnect UFA ground; bond gas line.
Gas Service Inspection - Residential Passed 8/29/2017 8/28/2017 at 3:20 PM 08/28/2017
Driveway Inspection Partial 9/27/2017 9/27/2017 at 11:00 AM 09/27/2017
Informational
09/27/2017
Tom Chandler 09/27/2017 11:15 AM Inspected forms and compacted aggregate only.
Driveway Inspection Passed 10/2/2017 at 2:20 PM 10/02/2017
Informational
10/02/2017
Tom Chandler 10/02/2017 2:23 PM Driveway has been completed and passed final inspection.
Plot Plan Inspection Passed 12/1/2017 at 4:00 AM 12/01/2017
All Rough Inspection - Residential Passed 12/01/2017
Misc
Resolved
12/01/2017
-missing lvl's basement, 1st floor, attic for roof support. revise plans or install per plans. check all roof support and location of lvls at re-inspection. PLANS RECIEVED AND APPROVED. IN PLAN PERMIT FILE. MIKE COPELAND 08/11/2017 2:15 PM - connect gas line at fireplace, protect wardflex at fireplace. *OK to insulate / rock, but don't cover structure that still needs to be inspected upon receipt of revised plans.
Occupancy Inspection - Codes Residential Failed 12/1/2017 12/1/2017 at 4:05 AM 12/01/2017
Misc
Corrective Action Required
12/01/2017
1. Obtain sprinkler permit. 2. Extend sump discharge away from foundation. 3. A ground-prong is broken off in the outlet in the garage. 4. Patch holes in garage wall. 5. Secure electric receptacle yokes - throughout. 6. Electric receptacle is not permitted above the bathtub - master bath.
Erosion Control Inspection Residential Passed 12/1/2017 at 3:55 AM 12/01/2017
Misc
Resolved
12/01/2017
clean entire street. from Benziger to stoneybrook.
Occupancy Inspection - Codes Residential Full C of O 12/20/2017 12/20/2017 at 11:00 AM 12/20/2017
Misc
Resolved
12/20/2017
1. Obtain sprinkler permit. 2. Extend sump discharge away from foundation. 3. A ground-prong is broken off in the outlet in the garage. 4. Patch holes in garage wall. 5. Secure electric receptacle yokes - throughout. 6. Electric receptacle is not permitted above the bathtub - master bath.
Documents & Images
Date Uploaded File Type Document Name
04/27/2017 Letter Codes Residential Plan Review
05/02/2017 Receipt Receipt for transaction: 2017-001687
05/02/2017 Letter Codes Building Permit
05/04/2017 Plot Plan DOC050417-021
05/12/2017 Letter Inspection Summary
05/24/2017 Engineer Report/Study DOC052417-007
06/05/2017 Letter Inspection Summary
06/30/2017 Letter Inspection Summary
07/10/2017 Letter Inspection Summary
07/25/2017 Letter Inspection Summary
07/31/2017 Letter Inspection Summary
08/03/2017 Letter Inspection Summary
08/14/2017 Letter Inspection Summary
08/17/2017 Letter Inspection Summary
08/28/2017 Letter Inspection Summary
09/27/2017 Letter DE-Daily Inspection Summary
10/02/2017 Letter DE-Daily Inspection Summary
12/01/2017 Letter Inspection Summary
12/20/2017 Letter Codes Final Certificate of Occupancy
12/22/2017 Letter Codes Final Certificate of Occupancy
03/09/2018 Plot Plan As Graded Plot Plan
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home