Permit Application Status

PRRES20171140


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20171140
Building Permit - Residential
Certificate of Occupancy
NICK ZVACEK CONSTRUCTION LLC
NEW SINGLE FAMILY
NEW HOUSE WITH COVERED DECK
04/13/2017
06/21/2017
09/22/2021
Locations
Contacts
NICK ZVACEK CONSTRUCTION LLC, Address:1009 INDUSTRIAL DR  
NICK ZVACEK CONSTRUCTION LLC, Address:1009 INDUSTRIAL DR, Phone:(816) 213-7204  
A & D HEATING AND COOLING INC, Address:2006 W MAIN ST, Phone:(816) 537-7952  
ADVANCED ELECTRICAL LLC, Address:PO BOX 1573, Phone:(816) 347-8187  
A BRIGHT PLUMBING LLC, Address:201 NE WOODBURY DR, Phone:(816) 867-4540  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 04/17/2017 06/21/2017
Nick Lightner
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,068.04 $1,068.04 Paid 06/21/2017
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 06/21/2017
8331507-Sewer Connection Fee $600.00 $600.00 Paid 06/21/2017
8331401-Water Tap Fee $3,310.00 $3,310.00 Paid 06/21/2017
8350015-Water Meter Fee $405.36 $405.36 Paid 06/21/2017
8331504-EFHB Middle Big Creek, Full $669.60 $669.60 Paid 06/21/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 10/3/2017 (9:30) 10/3/2017 at 9:30 AM 10/03/2017
Underslab Plumbing Inspection - Residential Passed 10/30/2017 10/30/2017 at 10:25 AM 10/30/2017
Sewer Service Inspection - R Passed 10/30/2017 10/30/2017 at 2:30 AM 10/30/2017
Water Service Inspection - R Partial 10/30/2017 at 2:40 AM 10/30/2017
Water Service Inspection - R Passed 10/31/2017 (9:00) 10/31/2017 at 9:05 AM 10/31/2017
Piers/Caissons Inspection - Residential Failed 12/5/2017 12/5/2017 at 8:25 AM 12/05/2017
Misc
Corrective Action Required
12/05/2017
Pier holes to extend 3' below grade to undisturbed soil.
Piers/Caissons Inspection - Residential Passed 12/6/2017 (9:00) 12/6/2017 at 1:00 AM 12/06/2017
Misc
Resolved
12/06/2017
Pier holes to extend 3' below grade to undisturbed soil.
All Rough Inspection - Residential Not Ready 12/21/2017 12/21/2017 at 11:05 AM 12/21/2017
Misc
Corrective Action Required
12/21/2017
PROVIDE THE SET OF PLANS FOR THIS ADDRESS THAT WERE REVIEWED BY THE CITY OF LEE'S SUMMIT.
All Rough Inspection - Residential Not Ready 12/27/2017 12/27/2017 at 9:00 AM 12/27/2017
Misc
Corrective Action Required
12/21/2017
PROVIDE THE SET OF PLANS FOR THIS ADDRESS THAT WERE REVIEWED BY THE CITY OF LEE'S SUMMIT. PLANS DO NOT HAVE THIS ADDRESS ON THEM. PROVIDE THE PLANS THAT WERE REVIEWED FOR THIS ADDRESS AND PERMIT.
All Rough Inspection - Residential Failed 12/29/2017 at 3:25 PM 12/29/2017
Misc
Corrective Action Required
12/27/2017
PROVIDE THE SET OF PLANS FOR THIS ADDRESS THAT WERE REVIEWED BY THE CITY OF LEE'S SUMMIT. PLANS DO NOT HAVE THIS ADDRESS ON THEM. PROVIDE THE PLANS THAT WERE REVIEWED FOR THIS ADDRESS AND PERMIT.
Gas Service Inspection - Residential Passed 12/27/2017 12/29/2017 12/29/2017
Electrical Service Inspection Passed 12/27/2017 12/29/2017 12/29/2017
All Rough Inspection - Residential Failed 12/29/2017 12/29/2017
Misc
Corrective Action Required
12/29/2017
1. Frame garage portals per detail 2. Fur out around return air in garage to accommodate required insulation. 3. Seal around plumbing penetration in return air over master closet. 4. 2 2x12 over living not designed for purlin support. Land on bearing wall by stairs. 5. Install stud support for hip rafter over master. 6. Vertical fireblock basement finish walls every 10 feet. 7. Nail siding at roof rakes.
All Rough Inspection - Residential Failed 1/10/2018 1/10/2018 at 10:05 AM 01/10/2018
Misc
Corrective Action Required
12/29/2017
1. Frame garage portals per detail 2. Fur out around return air in garage to accommodate required insulation. 4. 2 2x12 over living not designed for purlin support. Land on bearing wall by stairs. 5. Install stud support for hip rafter over master ALL THE WAY 6. Vertical fireblock basement finish walls every 10 feet. 7. Nail siding at roof rakes.
All Rough Inspection - Residential Failed 1/16/2018 1/16/2018 at 9:20 AM 01/16/2018
Misc
Corrective Action Required
01/10/2018
7. Nail siding at roof rakes. (REAR RAKE OVER MASTER BEDROOM STILL NOT NAILED)
Driveway Inspection Partial 2/16/2018 at 11:00 AM 02/16/2018
Informational
02/16/2018
Tom Chandler 02/16/2018 11:05 AM Inspected forms and compacted gravel only.
Driveway Inspection Passed 2/27/2018 at 10:55 AM 02/27/2018
Informational
02/27/2018
Tom Chandler 02/27/2018 10:54 AM Driveway has been completed and passed final inspection.
Plot Plan Inspection Passed 04/27/2018
Occupancy Inspection - Codes Residential Failed 10/16/2018 10/16/2018 at 1:35 PM 10/16/2018
Misc
Corrective Action Required
10/16/2018
• Guard rail is required at east side of front porch • HOUSE SMELLS LIKE GAS • Self closing hinges on garage entry door not operating properly • Outlet at south side of kitchen island not wired correctly • Oven is not fully installed , no pull over protection. • No back flow preventer at water main spigot in basement • Smokes in guest bed and rec room should be swapped. To be smoke only in bedroom, and combo in rec room • Missing joist hangers at double header to joist, and at double joist to ledger • No ledger locks or anchor bolts attaching ledger board to rim joist • Secure nm conduit at ac condenser it is hanging in the grass. • Siding is touching the dirt on on southeast side of house. Need to have 6” clearance from grade. • Sewer clean out is broken off on southeast side of house • Window screens • Only 1 security screw in rear entry door to deck. • Basement bath is missing light fixture • Attic access in closet on 2nd fl not of adequate size or in suitable location. attic access needs to be at least 22" x 30" and should be located in hallway or other location with ready access.
Occupancy Inspection - Codes Residential Temporary C of O 10/23/2018 10/23/2018 at 9:50 AM 12/06/2018
Misc
Resolved
10/23/2018
• Guard rail is required at east side of front porch • HOUSE SMELLS LIKE GAS • Self closing hinges on garage entry door not operating properly • Outlet at south side of kitchen island not wired correctly • Oven is not fully installed , no pull over protection. • No back flow preventer at water main spigot in basement • Smokes in guest bed and rec room should be swapped. To be smoke only in bedroom, and combo in rec room • Missing joist hangers at double header to joist, and at double joist to ledger • No ledger locks or anchor bolts attaching ledger board to rim joist • Secure nm conduit at ac condenser it is hanging in the grass. • Siding is touching the dirt on on southeast side of house. Need to have 6” clearance from grade. • Sewer clean out is broken off on southeast side of house • Window screens • Only 1 security screw in rear entry door to deck. • Basement bath is missing light fixture • Attic access in closet on 2nd fl not of adequate size or in suitable location. attic access needs to be at least 22" x 30" and should be located in hallway or other location with ready access.
Misc
Corrective Action Required
10/23/2018
* BRING WATER METER UP TO GRADE *
Occupancy Inspection - Codes Residential Full C of O 09/22/2021
Misc
Resolved
09/22/2021
* BRING WATER METER UP TO GRADE *
Documents & Images
Date Uploaded File Type Document Name
06/21/2017 Receipt Receipt for transaction: 2017-004120
06/21/2017 Letter Codes Building Permit
06/23/2017 Plot Plan DOC062317-003
09/12/2017 Email DOC091217-005
10/03/2017 Letter Inspection Summary
10/03/2017 Engineer Report/Study DOC100317-011
10/30/2017 Letter Inspection Summary
10/30/2017 Letter Inspection Summary
10/31/2017 Letter Inspection Summary
12/05/2017 Letter Inspection Summary
12/06/2017 Letter Inspection Summary
12/21/2017 Letter Inspection Summary
12/27/2017 Letter Inspection Summary
12/29/2017 Letter Inspection Summary
12/29/2017 Letter Inspection Summary
01/10/2018 Letter Inspection Summary
01/16/2018 Letter Inspection Summary
02/16/2018 Letter DE-Daily Inspection Summary
02/27/2018 Letter DE-Daily Inspection Summary
04/27/2018 Letter Inspection Summary
04/27/2018 Plot Plan DOC042718-04272018141700
10/16/2018 Letter Inspection Summary
10/23/2018 Letter Codes Temporary Certificate of Occupancy
12/06/2018 Letter Codes Temporary Certificate of Occupancy
09/22/2021 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.