PRRES20162298
Building Permit - Residential
Certificate of Occupancy
RPWC HOLDINGS LLC
NEW SINGLE FAMILY
NEW HOUSE WITH COVERED DECK
09/09/2016
09/16/2016
08/22/2017
Locations
Contacts
RPWC HOLDINGS LLC, Address:3170 NE CARNEGIE DR STE 400, Phone:(816) 795-8100  
CAPITAL CONSTRUCTION SERVICES LLC, Address:2642 NE HAGAN RD, Phone:(816) 875-0018  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
SDI ELECTRIC, LLC, Address:3317 W 81ST ST, Phone:(913) 636-5021  
A BRIGHT PLUMBING LLC, Address:18107 E 18TH TER N, Phone:(816) 215-0730  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 09/13/2016 09/13/2016
James Fletchall
Plot Plan Review (P&D) Approved 09/13/2016 09/12/2016
Jennifer Thompson
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $832.49 $832.49 Paid 09/16/2016
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 09/16/2016
8331506-EFHB Maybrook, Full $553.93 $553.93 Paid 09/16/2016
8331507-Sewer Connection Fee $390.00 $390.00 Paid 09/16/2016
8331401-Water Tap Fee $3,310.00 $3,310.00 Paid 09/16/2016
8350015-Water Meter Fee $405.36 $405.36 Paid 09/16/2016
9110078-Valuation Fee New Single Family $59.28 $59.28 Paid 06/19/2017
$891.77
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 9/23/2016 (11:00) 9/23/2016 09/23/2016
Underslab Plumbing Inspection - Residential Passed 10/24/2016 10/24/2016 10/24/2016
Erosion Control Inspection Residential Failed 10/24/2016 10/24/2016
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
10/24/2016
REPAIR EROSION CONTROL AROUND LOT. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Sewer Service Inspection - R Passed 10/27/2016 (3:30) 10/27/2016 10/27/2016
Water Service Inspection - R Passed 10/28/2016 (3:00) 10/28/2016 10/28/2016
Piers/Caissons Inspection - Residential Passed 11/14/2016 (1:30) 11/14/2016 11/14/2016
Piers/Caissons Inspection - Residential Passed 11/15/2016 (1:00) 11/15/2016 11/15/2016
Electrical Service Inspection Passed 1/5/2017 01/05/2017
Gas Service Inspection - Residential Passed 1/5/2017 01/05/2017
All Rough Inspection - Residential Failed 1/5/2017 (8:00 to 5:00) 1/5/2017 01/05/2017
Misc
Corrective Action Required
01/05/2017
FRAMING: -PROVIDE PLAN ON SITE -NAIL GARAGE CORNER STUDS AND NAIL SHEATHING TO CORNER STUDS -ABOVE GARAGE: SUPPORT BOTTOM OF VALLEY; REDUCE SPAN OF VALLEY; INSTALL BLOCKING TO CATCH TOPS OF HIPS -FUR OUT WALL AT RETURN AIR IN GARAGE FOR THE REQUIRED R-13 INSULATION -AT REAR DOOR, BLOCK 3 STUD SPACES OUT AT STRIKE PLATE HEIGHT -THE FRONT BEDROOM BACK WALL IS NOT A BEARING WALL -FUR DOWN CEILING ABOVE MASTER BATH/CLOSET AREA FOR R-30 INSULATION -SHIM UNDER THE NOTCHED PART OF THE LVL HIP TO BEAR ONTO THE CEILING BEAM ABOVE MASTER BED PLUMBING: -PLUMBING NOT READY FOR INSPECTION. PROTECT THROUGHOUT AND INSTALL STRAP AT OVERBORED TOP PLATES. INSTALL STUD SHOE AT OVERBORED STUD IN LAUNDRY ***DO NOT INSULATE
All Rough Inspection - Residential Failed 1/10/2017 (8:00 to 5:00) 1/10/2017 01/10/2017
Misc
Corrective Action Required
01/05/2017
-PROTECT PLUMBING AT MASTER SHOWER WALL -INSTALL STRAP AT OVERBORED TOP PLATES OF KITCHEN WALL; NAIL ALL STRAP HOLES AT LAUNDRY ***OK TO INSULATE
All Rough Inspection - Residential Passed 1/13/2017 (8:00 to 5:00) 1/13/2017 01/13/2017
Misc
Resolved
01/13/2017
-PROTECT PLUMBING AT MASTER SHOWER WALL -INSTALL STRAP AT OVERBORED TOP PLATES OF KITCHEN WALL; NAIL ALL STRAP HOLES AT LAUNDRY ***OK TO INSULATE
Driveway Inspection Passed 2/22/2017 02/22/2017
Sidewalk Inspection Passed 4/18/2017 04/20/2017
Informational
04/20/2017
I was in the area doing another inspection and was asked to look at this sidewalk and ada ramp. They formed everything and had the rock compacted. I came back the next day to check and I passed it. The sanitary MH was in the path of the sidewalk and was too low, so I had them raise it and it was a little high , but after trying to adjust it I let them leave it a little high.Steve Robbins 04/20/2017 4:03 PM
Sidewalk Inspection Passed 2/27/2017 05/17/2017
All Rough Inspection - Residential Failed 6/27/2017 6/27/2017 06/27/2017
Misc
Corrective Action Required
06/27/2017
-FIREBLOCK BASEMENT WALL SPACE FROM JOIST SPACE AND CEILING FURDOWN SPACE; FB WALL VERTICALLY AT INTERVAL NO MORE THAN TEN FT -SECURE WIRINGS MIN. 1.25" ABOVE THE CEILING JOIST BOTTOM IN BEDROOM ***OK TO INSULATE
All Rough Inspection - Residential Passed 6/28/2017 6/28/2017 06/28/2017
Misc
Resolved
06/28/2017
-FIREBLOCK BASEMENT WALL SPACE FROM JOIST SPACE AND CEILING FURDOWN SPACE; FB WALL VERTICALLY AT INTERVAL NO MORE THAN TEN FT -SECURE WIRINGS MIN. 1.25" ABOVE THE CEILING JOIST BOTTOM IN BEDROOM ***OK TO INSULATE
Occupancy Inspection - Codes Residential Failed 8/18/2017 8/18/2017 08/18/2017
Misc
Corrective Action Required
08/18/2017
-FINAL GRADE, SOD, SPLASHBLOCKS -RAISE WATER METER TO FINAL GRADE LEVEL. -INSTALL SPARK RING FOR FLOOR RECEPTACLE -PROVIDE ACCESS TO HYDROTUYB MOTOR AND RECEPTACLE. ACCESS PANEL STUCK -INSTALL BREAKER LOCKS FOR OVEN AND COOKTOP -LOCATE AND MAKE ACCESSIBLE UFER GROUNDING CONNECTION -ONE UNLABELED BREAKER -INSTALL AFCI BREAKER FOR BASEMENT BED CIRCUIT
Occupancy Inspection - Codes Residential Temporary C of O 08/18/2017
Misc
Corrective Action Required
08/18/2017
-FINAL GRADE, SOD, SPLASHBLOCKS -RAISE WATER METER TO FINAL GRADE LEVEL.
Occupancy Inspection - Codes Residential Full C of O 8/22/2017 8/22/2017 08/22/2017
Misc
Resolved
08/22/2017
-FINAL GRADE, SOD, SPLASHBLOCKS -RAISE WATER METER TO FINAL GRADE LEVEL.
Erosion Control Inspection Residential Passed 08/22/2017
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
08/22/2017
REPAIR EROSION CONTROL AROUND LOT. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Documents & Images
Date Uploaded File Type Document Name
09/16/2016 Receipt Receipt for transaction: 2016-005994
09/16/2016 Letter Codes Building Permit
09/19/2016 Plot Plan DOC091916-003
09/23/2016 Letter Inspection Summary
10/24/2016 Letter Inspection Summary
10/27/2016 Letter Inspection Summary
10/28/2016 Letter Inspection Summary
11/14/2016 Letter Inspection Summary
11/15/2016 Letter Inspection Summary
01/05/2017 Letter Inspection Summary
01/10/2017 Letter Inspection Summary
01/13/2017 Letter Inspection Summary
02/22/2017 Letter Inspection Summary
04/20/2017 Letter PW-Daily Inspection Summary
06/19/2017 Receipt Receipt for transaction: 2017-003954
06/19/2017 Letter Codes Building Permit
06/27/2017 Letter Inspection Summary
06/28/2017 Letter Inspection Summary
08/18/2017 Letter Inspection Summary
08/18/2017 Letter Codes Temporary Certificate of Occupancy
08/22/2017 Letter Field Certificate of Occupancy
08/23/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home