Summary
PRRES20150816
Building Permit - Residential
Final Completion
DOLLAR TIM E & DEBORAH L
NEW OTHER (RESIDENTIAL)
IN-GROUND POOL
04/16/2015
10/13/2015
03/15/2017
Locations
Contacts
LAND & WATER LLC, Address:9003 E 92ND ST, Phone:(816) 761-8585  
SUPERIOR ELECTRICAL CONSTRUCTION, Address:PO BOX 3137, Phone:(816) 356-1163  
AXIOM PLUMBING LLC, Address:5703 CEDAR ST  
DOLLAR TIM E & DEBORAH L, Address:1079 LAKE POINT CRT  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 10/13/2015
Development Center
Plot Plan Review (P&D) Approved 10/12/2015
Development Center
Plot Plan Review Rejected 08/07/2015
Tara Mitchell
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Other $676.20 $676.20 Paid 10/13/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Pool Steel/Bonding - Residential Partial 11/10/2015 at 12:00 AM 11/10/2015
Misc
Corrective Action Required
11/10/2015
THE FOLLOWING COMPONENTS ARE BONDED: -RETAINING WALLS RABAR
Pool Steel/Bonding - Residential Partial 12/11/2015 at 12:00 AM 12/11/2015
Misc
Corrective Action Required
11/10/2015
THE FOLLOWING COMPONENTS ARE BONDED: -RETAINING WALLS RABAR; TWO LIGHT NICHES, POOL SHELL REBAR
Gas Piping Inspection - Residential Failed 4/11/2016 04/11/2016
Misc
Corrective Action Required
04/11/2016
-METALLIC GAS PIPING AND FITTINGS EXPOSED TO CORROSIVE CONDITION (SOIL, MOIST CONCRETE, ETC) SHALL BE PROTECTED IN AN APPROVED MANNER -INDIVIDUAL GAS LINE TO LIGHTS AND OTHER APPLIANCES SHALL BE MINIMUM 8" BELOW FINISHED GRADE, WHERE NOT SUBJECTED TO DAMAGE. EVERYWHERE ELSE, MIN. 12" BELOW GRADE
Gas Piping Inspection - Residential Failed 4/14/2016 4/14/2016 04/14/2016
Misc
Corrective Action Required
04/11/2016
-INDIVIDUAL GAS LINE TO LIGHTS AND OTHER APPLIANCES SHALL BE MINIMUM 8" BELOW FINISHED GRADE, WHERE NOT SUBJECTED TO DAMAGE. EVERYWHERE ELSE, MIN. 12" BELOW GRADE **PLASTIC GAS LINE IS ONLY ALLOWED TO BE BURIED. IF IT IS NOT BURIED, THEN YOU MUST CHOOSE OTHER TYPE OF GAS LINE (RIGID GAS PIPE, OR CSST INSTALLED PER MANUFACTURER'S REQUIREMENT) **GAS PRESSURE IS AT A LITTLE BELOW 6 PSI. NEED MIN. 10 PSI FOR TESTING
Gas Piping Inspection - Residential Passed 4/18/2016 4/18/2016 04/18/2016
Misc
Resolved
04/18/2016
-INDIVIDUAL GAS LINE TO LIGHTS AND OTHER APPLIANCES SHALL BE MINIMUM 8" BELOW FINISHED GRADE, WHERE NOT SUBJECTED TO DAMAGE. EVERYWHERE ELSE, MIN. 12" BELOW GRADE **PLASTIC GAS LINE IS ONLY ALLOWED TO BE BURIED. IF IT IS NOT BURIED, THEN YOU MUST CHOOSE OTHER TYPE OF GAS LINE (RIGID GAS PIPE, OR CSST INSTALLED PER MANUFACTURER'S REQUIREMENT) **GAS PRESSURE IS AT A LITTLE BELOW 6 PSI. NEED MIN. 10 PSI FOR TESTING
Pool Steel/Bonding - Residential Partial 5/5/2016 5/5/2016 05/05/2016
Misc
Corrective Action Required
12/11/2015
THE FOLLOWING COMPONENTS ARE BONDED: -RETAINING WALLS RABAR; TWO LIGHT NICHES, POOL SHELL REBAR, PERIMETER SURFACE, GAS LIGHTS
Pool Steel/Bonding - Residential Passed 11/15/2016
Misc
Resolved
11/15/2016
THE FOLLOWING COMPONENTS ARE BONDED: -RETAINING WALLS RABAR; TWO LIGHT NICHES, POOL SHELL REBAR, PERIMETER SURFACE, GAS LIGHTS
Pool Final - Residential Failed 11/15/2016 11/15/2016
Misc
Corrective Action Required
11/15/2016
-SECURE ALL LFNC RACEWAY WITHIN 12" OF ENCLOSURES -AT POND PUMPS LOCATION, CLOSE J-BOX HOLES -AT POND GFCI RECEPTACLE, PROVIDE A LISTED UNDAMAGED CORD WITH "W" SUFFIX FOR THE SUBMERSIBLE EQUIPMENT. -INSTALL A DISCONNECTING MEAN FOR THE SUBMERSIBLE EQUIPMENT. THE DISCONNECTING MEAN SHALL BE WITHIN 30" OF THE RECEPTACLE IT CONTROLS, ON THE SUPPLY SIDE OF THE RECEPTACLE, NOT CLOSER THAN 5 FT OF POND EDGE, AND MIN. 12" ABOVE FLOOD LEVEL. 682.14 A&B -PROVIDE GFCI PROTECTION FOR ALL SWIMMING POOL PUMPS. NEC 680.21(C)
Pool Final - Residential Passed 3/15/2017 3/15/2017 03/15/2017
Misc
Resolved
03/15/2017
-SECURE ALL LFNC RACEWAY WITHIN 12" OF ENCLOSURES -AT POND PUMPS LOCATION, CLOSE J-BOX HOLES -AT POND GFCI RECEPTACLE, PROVIDE A LISTED UNDAMAGED CORD WITH "W" SUFFIX FOR THE SUBMERSIBLE EQUIPMENT. -INSTALL A DISCONNECTING MEAN FOR THE SUBMERSIBLE EQUIPMENT. THE DISCONNECTING MEAN SHALL BE WITHIN 30" OF THE RECEPTACLE IT CONTROLS, ON THE SUPPLY SIDE OF THE RECEPTACLE, NOT CLOSER THAN 5 FT OF POND EDGE, AND MIN. 12" ABOVE FLOOD LEVEL. 682.14 A&B -PROVIDE GFCI PROTECTION FOR ALL SWIMMING POOL PUMPS. NEC 680.21(C)
Documents & Images
Date Uploaded File Type Document Name
10/13/2015 Letter Codes Building Permit
10/13/2015 Receipt Receipt for transaction: 2015-005745
10/13/2015 Drawing DOC101315-007
11/10/2015 Letter Inspection Summary
12/11/2015 Letter Inspection Summary
04/11/2016 Letter Inspection Summary
04/14/2016 Letter Inspection Summary
04/18/2016 Letter Inspection Summary
05/05/2016 Letter Inspection Summary
11/15/2016 Letter Inspection Summary
03/15/2017 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home