Permit Application Status

PRRES20132531


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20132531
Building Permit - Residential
Final Completion
WYSS HOME BUILDING LLC
NEW OTHER (RESIDENTIAL)
POOL WITH ELECTRIC HEATER - IN GROUND
11/19/2013
11/22/2013
06/13/2014
Locations
Contacts
RECREATION WHOLESALE LLC, Address:2321 NE INDEPENDENCE AVE, Phone:(816) 730-6198  
WE CONNECT ELECTRIC, Address:1429 INDIANA AVE, Phone:(816) 695-2692  
WYSS HOME BUILDING LLC, Address:PO BOX 6620, Phone:(816) 820-0142  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 11/22/2013
Gene Williams, P.E.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Other $157.78 $157.78 Paid 11/22/2013
$157.78
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Pool Steel/Bonding - Residential Partial 12/3/2013 12/3/2013 at 12:00 AM 12/03/2013
Misc
Corrective Action Required
12/03/2013
THE FOLLOWINGS ARE BONDED: -POOL METAL SHELL, LIGHT NICHE
Pool Steel/Bonding - Residential Partial 2/27/2014 2/27/2014 at 12:00 AM 02/27/2014
Misc
Corrective Action Required
12/03/2013
THE FOLLOWINGS ARE BONDED: -POOL METAL SHELL, LIGHT NICHE **THE UNDERGROUND PVC CONDUITS FROM POOL TO POOL EQUIPMENTS LOCATION SHALL BE MIN. 18" BELOW GRADE.
Pool Steel/Bonding - Residential Partial 3/7/2014 at 12:00 AM 03/07/2014
Misc
Corrective Action Required
02/27/2014
THE FOLLOWINGS ARE BONDED: -POOL METAL SHELL, LIGHT NICHE **OK TO BACKFILL CONDUITS TRENCH
Pool Steel/Bonding - Residential Partial 3/12/2014 3/12/2014 at 12:00 AM 03/12/2014
Misc
Corrective Action Required
03/07/2014
THE FOLLOWINGS ARE BONDED: -POOL METAL SHELL, LIGHT NICHE **SHALL USE LISTED REBAR BONDING/GROUNDING CLAMPS **EXPOSE THE BONDING CONDUCTOR TO BOND THE POOL COVER MOTOR & FRAME **UNDERGROUND CONDUCTORS SHALL BE LISTED FOR WET LOCATION. CANNOT USE NM CABLE
Pool Steel/Bonding - Residential Passed 3/13/2014 3/12/2014 at 12:00 AM 03/12/2014
Misc
Resolved
03/12/2014
THE FOLLOWINGS ARE BONDED: -POOL METAL SHELL, LIGHT NICHE, DECK REBAR, LADDER AND HANDRAIL BASES **UNDERGROUND CONDUCTORS SHALL BE LISTED FOR WET LOCATION. CANNOT USE NM CABLE. CHECK ON FINAL
Pool Steel/Bonding - Residential Passed 03/12/2014
Misc
Resolved
03/12/2014
THE FOLLOWINGS ARE BONDED: -POOL METAL SHELL, LIGHT NICHE, DECK REBAR, LADDER AND HANDRAIL BASES **UNDERGROUND CONDUCTORS SHALL BE LISTED FOR WET LOCATION. CANNOT USE NM CABLE. CHECK ON FINAL
Pool Final - Residential Failed 5/8/2014 (8:00 to 5:00) 5/8/2014 at 12:00 AM 05/08/2014
Misc
Corrective Action Required
05/08/2014
-THE FENCE GATES SHALL BE SELF-CLOSING AND SELF-LATCHING -THE POOL EQUIPMENTS SHALL NOT BE LOCATED IN THE WORKING AREA IN FRONT OF THE ELECTRICAL EQUIPMENTS (METER BOX AND THE POOL PANEL). WORKING AREA DEFINITION-30" WIDE X 36" DEEP SPACE IN FRONT OF THE EQUIPMENTS -THE POOL J-BOX SHALL BE MIN. 4" ABOVE THE DECK AND 8" ABOVE THE MAXIMUM WATER LEVEL, WHICH EVER IS GREATER, MEASURED FROM THE BOTTOM OF THE J-BOX -TERMINATE THE POOL COVER CIRCUIT INSIDE J-BOX -THE FEEDER TO THE POOL PANEL SHALL BE APPROVED WIRING METHOD PER NEC 680.25(A) -THE EQUIPMENT GROUNDING CONDUCTOR OF THE FEEDER ABOVE SHALL BE INSULATED AS REQUIRED PER 680.25(B)
Pool Final - Residential Failed 5/8/2014 at 12:00 AM 05/08/2014
Misc
Corrective Action Required
05/08/2014
-THE FENCE GATES SHALL BE SELF-CLOSING AND SELF-LATCHING -THE POOL EQUIPMENTS SHALL NOT BE LOCATED IN THE WORKING AREA IN FRONT OF THE ELECTRICAL EQUIPMENTS (METER BOX AND THE POOL PANEL). WORKING AREA DEFINITION-30" WIDE X 36" DEEP SPACE IN FRONT OF THE EQUIPMENTS -INSTALL AN INSUILATED EQUIPMENT GROUNDING CONDUCTOR FOR THE HEAT PUMP -THE POOL J-BOX SHALL BE MIN. 4" ABOVE THE DECK AND 8" ABOVE THE MAXIMUM WATER LEVEL, WHICH EVER IS GREATER, MEASURED FROM THE BOTTOM OF THE J-BOX -TERMINATE THE POOL COVER CIRCUIT INSIDE J-BOX -THE FEEDER TO THE POOL PANEL SHALL BE APPROVED WIRING METHOD PER NEC 680.25(A) -THE EQUIPMENT GROUNDING CONDUCTOR OF THE FEEDER ABOVE SHALL BE INSULATED AS REQUIRED PER 680.25(B) -NEED ACCESS TO INSIDE FOR INXSPECTION
Pool Final - Residential Failed 6/11/2014 6/11/2014 at 12:00 AM 06/11/2014
Misc
Corrective Action Required
05/08/2014
-TERMINATE THE POOL COVER CIRCUIT INSIDE J-BOX
Pool Final - Residential Passed 6/13/2014 at 12:00 AM 06/13/2014
Misc
Resolved
06/13/2014
-TERMINATE THE POOL COVER CIRCUIT INSIDE J-BOX
Documents & Images
Date Uploaded File Type Document Name
11/22/2013 Letter Codes Building Permit
11/25/2013 Plot Plan
12/03/2013 Letter Inspection Summary
02/27/2014 Letter Inspection Summary
03/07/2014 Letter Inspection Summary
03/12/2014 Letter Inspection Summary
03/12/2014 Letter Inspection Summary
05/08/2014 Letter Inspection Summary
05/08/2014 Letter Inspection Summary
06/11/2014 Letter Inspection Summary
06/13/2014 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home