Permit Application Status

PRCOM20246374


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20246374
Building Permit - Commercial
Issued
MIDWEST DIVISION LSH LLC
ADDITION COMMERCIAL
LEE'S SUMMIT MEDICAL CENTER - ADDITION/RENOVATION 2024 - IP BED EXPANSION
12/12/2024
08/06/2025
06/28/2025
Locations
Contacts
NABHOLZ CONSTRUCTION CORPORATION, Address:PO BOX 2090, Phone:(501) 505-5800  
Ian Davies - Nabholz Construction, Phone:(913) 747-5226  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
ELECTRICAL CORP OF AMERICA, Address:7320 ARLINGTON, Phone:(816) 737-3206  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
Devenney Group, Address:6900 East Camelback Road, Phone:(602) 943-8950  
Intertek-PSI, Address:2828 S. 44th Street, Phone:(913) 310-1600  
MIDWEST DIVISION LSH LLC, Address:PO BOX 80610  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 09/17/2025 09/18/2025
Craig Hill
Construction documents for fire alarm systems
Corrective Action Required
09/09/2025

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide deferred submittal for fire alarm system.
Construction documents - Fire protection systems
Corrective Action Required
09/09/2025

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide deferred submittal for fire protection system.
Building Plan Review Approved with Conditions 09/17/2025 09/15/2025
Joe Frogge
License Tax - Payment
Corrective Action Required
09/09/2025

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $51,001.50 2/11/2025 - Acknowledged in letter.
Misc
Corrective Action Required
09/09/2025

Inadequate information as concerns fire rated assemblies to complete review. Provide the following: - Provide complete UL details for fire rated assemblies. Must, at a minimum, include nail/screw patterns. 2/11/2025 - Deferred per request. - -
Misc
Corrective Action Required
09/09/2025

Plans submitted are for multiple projects. After review is complete and approved we will create the other permits. (MOB vs. Hospital vs. Pedestrian walkway) Action required: Comment is informational. 2/11/2025 - Acknowledged in letter.
Health Dept Inspection
Corrective Action Required
09/09/2025

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 2/11/2025 - Acknowledged in letter.
Licensed Contractors Approved 02/14/2025 07/28/2025
Joe Frogge
LC - MEP Subs
Resolved
07/01/2025

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 2/11/2025 - This comment was unintentionally left off of original report.
LC - General Contractor
Resolved
02/11/2025

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Provide the name, email address & phone number for the on-site contact.
Building Plan Review Approved with Conditions 07/25/2025 07/28/2025
Joe Frogge
License Tax - Payment
Corrective Action Required
07/21/2025

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $51,001.50 2/11/2025 - Acknowledged in letter.
Misc
Corrective Action Required
07/21/2025

Inadequate information as concerns fire rated assemblies to complete review. Provide the following: - Provide complete UL details for fire rated assemblies. Must, at a minimum, include nail/screw patterns. 2/11/2025 - Deferred per request. - -
Misc
Corrective Action Required
07/21/2025

Plans submitted are for multiple projects. After review is complete and approved we will create the other permits. (MOB vs. Hospital vs. Pedestrian walkway) Action required: Comment is informational. 2/11/2025 - Acknowledged in letter.
Health Dept Inspection
Corrective Action Required
07/21/2025

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 2/11/2025 - Acknowledged in letter.
Fire Plan Review Approved with Conditions 07/25/2025 07/22/2025
Craig Hill
Construction documents for fire alarm systems
Corrective Action Required
07/22/2025

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide deferred submittal for fire alarm system.
Construction documents - Fire protection systems
Corrective Action Required
07/22/2025

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide deferred submittal for fire protection system.
Building Plan Review Approved with Conditions 02/14/2025 05/01/2025
Joe Frogge
Final Development Plan
Resolved
03/13/2025

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 2/11/2025 - Acknowledged in letter.
License Tax - Payment
Corrective Action Required
02/07/2025

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $51,001.50 2/11/2025 - Acknowledged in letter.
Project cost
Resolved
05/01/2025

The project cost, which is used to establish the permit fee, seems high. You can remove the site costs from this number to save in permit fees. Action required: Comment is informational. Also, we need a cost breakdown between MOB work, Hospital work, and Pedestrian walkway. 2/11/2025 - Acknowledged in letter.
Misc
Corrective Action Required
02/07/2025

Inadequate information as concerns fire rated assemblies to complete review. Provide the following: - Provide complete UL details for fire rated assemblies. Must, at a minimum, include nail/screw patterns. 2/11/2025 - Deferred per request. - -
IBC 1803.1 General - geotech
Resolved
02/11/2025

2018 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf. (3,000psf shown on sheet S011)
Misc
Corrective Action Required
02/07/2025

Plans submitted are for multiple projects. After review is complete and approved we will create the other permits. (MOB vs. Hospital vs. Pedestrian walkway) Action required: Comment is informational. 2/11/2025 - Acknowledged in letter.
Health Dept Inspection
Corrective Action Required
02/07/2025

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 2/11/2025 - Acknowledged in letter.
IMC 306.5 Equipment on roofs
Resolved
02/11/2025

2018 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide side rail extender at roof hatch shown on 3/AE533.
IBC 716.2 Fire and Smoke Protection - fire door assemblies
Resolved
02/11/2025

2018 IBC 716.2.2 Performance requirements. Fire door assemblies shall be installed in the assemblies specified in Table 716.1(2) and shall comply with the fire protection rating specified. Action required: Amend door schedule to show that doors 3-2039B & 3-2121 are rated for 45 minutes.
IBC 603.1 Type of Construction - Allowable Materials
Resolved
02/11/2025

2018 IBC 603.1 Allowable Materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3: (see code for specific examples and exceptions) Action required: Amend designs to show that top plate nailers at exterior walls/parapets are fire retardant treated.
IPC 708.1 Cleanouts required
Resolved
02/11/2025

2018 IPC 708.1 Cleanouts Required. Cleanouts shall be provided for drainage piping in accordance with Sections 708.1.1 through 708.1.11. 2018 IPC 708.1.3 Building drain and building sewer junction. The junction of the building drain and the building sewer shall be served by a cleanout that is located at the junction or within 10 feet of the developed length of piping upstream of the junction. For the requirements of this section, the removal of a water closet shall not be required to provide cleanout access. Action required: Provide cleanouts near where SS leaves building.
IMC 506.3.13.3 Grease fan termination location
Resolved
02/11/2025

2018 IMC 506.3.13.3 Termination location. Exhaust outlets shall be located not less than 10 feet horizontally from parts of the same or contiguous buildings, adjacent buildings and adjacent property lines and shall be located not less than 10 feet above the adjoining grade level. Exhaust outlets shall be located not less than 10 feet horizontally from or not less than 3 feet above air intake openings into any buildings. (see code for exception) Action required: Relocated kitchen hood exhaust fans to comply. (too close to parapet)
IBC 1008.3 Emergency power for illumination - at exit discharge
Resolved
02/11/2025

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency illumination at exterior landings at exit doors and in stair wells.
IBC 1704.2 Special Inspections
Resolved
04/15/2025

2018 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Special Inspections Review Approved 04/15/2025
Joe Frogge
Final Development Plan Review Approved 02/18/2025 02/19/2025
Daniel Fernandez
Fire Plan Review Approved 02/14/2025 02/13/2025
Craig Hill
Construction documents for fire alarm systems
Corrective Action Required
02/07/2025

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide deferred submittal for alarm system.
Construction documents - Fire protection systems
Corrective Action Required
02/07/2025

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide deferred submittal for protection system.
Miscellaneous Correction
Resolved
02/13/2025

1008.1 Means of egress illumination. Illumination shall be provided in the means of egress in accordance with Section 1008.2. Under emergency power, means of egress illumination shall comply with Section 1008.3. Action required: Provide emergency illumination at exterior landings at exit doors and in stair wells.
Health Department Review Approved 01/08/2025
Joe Frogge
Fire Plan Review Rejected 12/30/2024 12/30/2024
Craig Hill
Construction documents for fire alarm systems
Corrective Action Required
12/30/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide deferred submittal for alarm system.
Construction documents - Fire protection systems
Corrective Action Required
12/30/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide deferred submittal for protection system.
Miscellaneous Correction
Corrective Action Required
12/30/2024

1008.1 Means of egress illumination. Illumination shall be provided in the means of egress in accordance with Section 1008.2. Under emergency power, means of egress illumination shall comply with Section 1008.3. Action required: Provide emergency illumination at exterior landings at exit doors and in stair wells.
Building Plan Review Rejected 12/30/2024 12/27/2024
Joe Frogge
Final Development Plan
Corrective Action Required
12/27/2024

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational.
License Tax - Payment
Corrective Action Required
12/27/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $51,001.50
Project cost
Corrective Action Required
12/27/2024

The project cost, which is used to establish the permit fee, seems high. You can remove the site costs from this number to save in permit fees. Action required: Comment is informational. Also, we need a cost breakdown between MOB work, Hospital work, and Pedestrian walkway.
Misc
Corrective Action Required
12/27/2024

Inadequate information as concerns fire rated assemblies to complete review. Provide the following: - Provide complete UL details for fire rated assemblies. Must, at a minimum, include nail/screw patterns. - Pipe material schedule. - Complete light pole base detail.
IBC 1803.1 General - geotech
Corrective Action Required
12/27/2024

2018 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf. (3,000psf shown on sheet S011)
Misc
Corrective Action Required
12/27/2024

Plans submitted are for multiple projects. After review is complete and approved we will create the other permits. (MOB vs. Hospital vs. Pedestrian walkway) Action required: Comment is informational.
Health Dept Review
Resolved
01/08/2025

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 797-7162. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection
Corrective Action Required
12/27/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational.
IMC 306.5 Equipment on roofs
Corrective Action Required
12/27/2024

2018 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide side rail extender at roof hatch shown on 3/AE533.
IBC 716.2 Fire and Smoke Protection - fire door assemblies
Corrective Action Required
12/27/2024

2018 IBC 716.2.2 Performance requirements. Fire door assemblies shall be installed in the assemblies specified in Table 716.1(2) and shall comply with the fire protection rating specified. Action required: Amend door schedule to show that doors 3-2039B & 3-2121 are rated for 45 minutes.
IBC 603.1 Type of Construction - Allowable Materials
Corrective Action Required
12/27/2024

2018 IBC 603.1 Allowable Materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3: (see code for specific examples and exceptions) Action required: Amend designs to show that top plate nailers at exterior walls/parapets are fire retardant treated.
IPC 708.1 Cleanouts required
Corrective Action Required
12/30/2024

2018 IPC 708.1 Cleanouts Required. Cleanouts shall be provided for drainage piping in accordance with Sections 708.1.1 through 708.1.11. 2018 IPC 708.1.3 Building drain and building sewer junction. The junction of the building drain and the building sewer shall be served by a cleanout that is located at the junction or within 10 feet of the developed length of piping upstream of the junction. For the requirements of this section, the removal of a water closet shall not be required to provide cleanout access. Action required: Provide cleanouts near where SS leaves building.
IMC 506.3.13.3 Grease fan termination location
Corrective Action Required
12/30/2024

2018 IMC 506.3.13.3 Termination location. Exhaust outlets shall be located not less than 10 feet horizontally from parts of the same or contiguous buildings, adjacent buildings and adjacent property lines and shall be located not less than 10 feet above the adjoining grade level. Exhaust outlets shall be located not less than 10 feet horizontally from or not less than 3 feet above air intake openings into any buildings. (see code for exception) Action required: Relocated kitchen hood exhaust fans to comply. (too close to parapet)
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
12/30/2024

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency illumination at exterior landings at exit doors and in stair wells.
Licensed Contractors Rejected 12/30/2024 12/27/2024
Joe Frogge
LC - General Contractor
Corrective Action Required
12/27/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
LC - MEP Subs
Corrective Action Required
12/27/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Provide the name, email address & phone number for the on-site contact.
Alarm Plan Review Pending
Craig Hill
Sprinkler Plan Review Pending
Craig Hill
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Addition to Commercial $100,786.11 $100,786.11 Paid 08/06/2025
Commercial Excise Tax Fee $51,001.50 $51,001.50 Paid 08/06/2025
Right of Way Permit Fee $85.00 $85.00 Paid 08/06/2025
Storm Sewer Inspection Fee $1,367.25 $1,367.25 Paid 08/06/2025
Paved Surface Inspection Fee $30,021.96 $30,021.96 Paid 08/06/2025
Site Grading Fee $8,557.14 $8,557.14 Paid 08/06/2025
Parks Impact Fee Non-Residential - Zone 2 $4,080.80 $4,080.80 Paid 08/06/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Hood/Duct Inspection Pending
Alternate Protection Systems Inspection Pending
Erosion Control Inspection Pending
Underslab Plumbing Inspection - Commercial Pending
Water Service Inspection Pending
Electrical Service Inspection Pending
Gas Service Inspection - Commercial Pending
In-wall Inspection Pending
Above Ceiling Inspection Pending
Rated Assembly Inspection Pending
Underground Electrical Inspection - Commercial Pending
Misc
Informational
10/09/2025
-Underground conduit for light poles, and emergency phones east side of parking lot to West side, excluding West side 5 to 6 poles to be determined placement -under ground conduit on N side of lot continuing to W entrance -all remaining conduit W side of parking lot.
Piers/Caissons Inspection - Commercial Pending
Misc
Informational
10/21/2025
The following approved -2 light pole bases center of parking lot
Pavement-Proof Roll Pending
Curb - Proof Roll Pending
Misc
Corrective Action Required
10/28/2025
10/28/25 Tyler S. Curb was poured before proof roll inspection was done. Proof roll failed in a couple spots on the south east side or parking lot. Curb will need to be removed and before pouring curb a pre pour inspection will need to be done.
Miscellaneous Inspection Pending
Misc
Corrective Action Required
10/29/2025
Discussion of special inspections
Suspended Slab Inspection Pending
Misc
Corrective Action Required
10/31/2025
Provide 3rd party inspection report.
Footing Inspection - Commercial Pending 11/4/2025 11/4/2025
Misc
Informational
10/31/2025
Following areas inspected -Retaining wall footing on NE side of parking lot -4 footing pads for pedestrian bridge -rebar for pedestrian bridge columns Provide 3rd party inspection report for “top footings”
Underground Electrical Inspection - Commercial Partial 10/3/2025 10/3/2025 10/03/2025
Misc
Informational
10/03/2025
Underground conduit for light poles, and emergency phones east side of parking lot to West side, excluding West side 5 to 6 poles to be determined placement
Underground Electrical Inspection - Commercial Partial 10/6/2025 10/6/2025 10/06/2025
Misc
Informational
10/03/2025
-Underground conduit for light poles, and emergency phones east side of parking lot to West side, excluding West side 5 to 6 poles to be determined placement -under ground conduit on N side of lot continuing to W entrance
Underground Electrical Inspection - Commercial Partial 10/9/2025 10/9/2025 10/09/2025
Misc
Informational
10/06/2025
-Underground conduit for light poles, and emergency phones east side of parking lot to West side, excluding West side 5 to 6 poles to be determined placement -under ground conduit on N side of lot continuing to W entrance -all remaining conduit W side of parking lot.
Footing Inspection - Commercial Partial 10/14/2025 10/14/2025 10/14/2025
Misc
Informational
10/14/2025
Retaining wall footing on NE side of parking lot okay to pour
Footing Inspection - Commercial Partial 10/15/2025 10/15/2025 10/15/2025
Misc
Informational
10/14/2025
Following areas inspected -Retaining wall footing on NE side of parking lot
Footing Inspection - Commercial Partial 10/20/2025 10/20/2025 10/20/2025
Misc
Informational
10/15/2025
Following areas inspected -Retaining wall footing on NE side of parking lot -4 footing pads for pedestrian bridge (upload RFI as discussed on site)
Footing Inspection - Commercial Failed 10/21/2025 10/21/2025 10/21/2025
Misc
Informational
10/20/2025
Following areas inspected -Retaining wall footing on NE side of parking lot -4 footing pads for pedestrian bridge (upload RFI as discussed on site)
Misc
Corrective Action Required
10/21/2025
Inspection denied pending engineered uploads
Piers/Caissons Inspection - Commercial Partial 10/21/2025 10/21/2025 10/21/2025
Misc
Informational
10/21/2025
The following approved -2 light pole bases center of parking lot
Footing Inspection - Commercial Partial 10/21/2025 10/21/2025
Misc
Informational
10/21/2025
Following areas inspected -Retaining wall footing on NE side of parking lot -4 footing pads for pedestrian bridge -rebar for pedestrian bridge columns
Misc
Resolved
10/21/2025
Inspection denied pending engineered uploads
Curb - Proof Roll Failed 10/28/2025 10/28/2025 10/28/2025
Misc
Corrective Action Required
10/28/2025
10/28/25 Tyler S. Curb was poured before proof roll inspection was done. Proof roll failed in a couple spots on the south east side or parking lot. Curb will need to be removed and before pouring curb a pre pour inspection will need to be done.
Miscellaneous Inspection Partial 10/29/2025 10/29/2025
Misc
Corrective Action Required
10/29/2025
Discussion of special inspections
Suspended Slab Inspection Partial 10/31/2025 10/31/2025 10/31/2025
Misc
Corrective Action Required
10/31/2025
Provide 3rd party inspection report.
Footing Inspection - Commercial Partial 10/31/2025 10/31/2025 10/31/2025
Misc
Informational
10/21/2025
Following areas inspected -Retaining wall footing on NE side of parking lot -4 footing pads for pedestrian bridge -rebar for pedestrian bridge columns Provide 3rd party inspection report for “top footings”
Documents & Images
Date Uploaded File Type Document Name
12/12/2024 Application Form Commercial Permit Application - Med Surg and Dietary
12/16/2024 Plans MEPT & Vendor
12/16/2024 Plans Arch Civil Struct Interiors
12/17/2024 Letter License Tax Bill
12/30/2024 Letter DS P/R Corrections Document
01/08/2025 Letter Jackson County Health approval
02/07/2025 Plans 250206_ARCH & INTERIOR DWG SET - ADD A & ADD B
02/07/2025 Plans 250206_CIVIL-LAND-STRUC DWG SET-ADD B
02/07/2025 Plans 250206_MEP DWG SET - ADD A & ADD B
02/07/2025 Letter 250206_NARRATIVE - ADD A
02/07/2025 Letter 250206_NARRATIVE - ADD B
02/07/2025 Specifications City Comment #6 - Pipe Material Schedules
02/07/2025 Engineer Report/Study City Comment #7 - 003132 - GEOTECHNICAL DATA
02/07/2025 Engineer Report/Study City Comment #7 - 003132_01 - GEOTECHNICAL REPORT
02/07/2025 Specifications 250206_SPECS_ADD B
04/15/2025 Special Inspection Letter for HCA Lee's Summit Medical Center Med Surg & Dietary Expansion
04/15/2025 Applicant Letter - FDP (DFDP)
05/15/2025 Approved Plans Stamped Approved FDP Plans_PL2024191
06/04/2025 Approved Plans Approved Arch plans
06/04/2025 Approved Plans Approved Struct plans
06/04/2025 Approved Plans Approved MEP plans
07/15/2025 Plans Revised Stamped Approved FDP Plans_PL2024191
07/18/2025 Plans HCA - LSMC Medsurg & Dietary_ REV 1 DWG SET
07/18/2025 Letter LSMC Medsurg & Dietary_ REV 1 Change log
07/25/2025 Approved Plans Approved revisions
08/06/2025 Receipt Receipt for transaction: 2025-006142
08/06/2025 Letter DS Building Permit
08/19/2025 Approved Plans Revised Stamped Approved FDP Plans No. 2_PL2024191
09/08/2025 Plans 250725 - HCA_LSMC - MED SURG & DIETARY - REV 2 DWGS
09/08/2025 Specifications 000001 - TABLE OF CONTENTS
09/08/2025 Specifications 072726 - fluid applied membrane air-moisture barrier
09/08/2025 Letter 250725 - HCA_LSMC - MED SURG & DIETARY - REV 2 Change Log
09/30/2025 Plans 250919_HCA_LSMC_MED SURG & DIETARY_CURRENT DRAWINGS COMBINED_PART 1 REDUCED
09/30/2025 Plans 250919_HCA_LSMC_MED SURG & DIETARY_CURRENT DRAWINGS COMBINED_PART 2 REDUCED
10/01/2025 Approved Plans Approved construction plans Vol1
10/01/2025 Approved Plans Approved construction plans Vol2
10/03/2025 Letter INSPECTION SUMMARY
10/03/2025 3RD Party Insp Report SWPPP (9-24-25)
10/06/2025 SWPPP (10-3-25)
10/06/2025 Letter INSPECTION SUMMARY
10/09/2025 Letter INSPECTION SUMMARY
10/13/2025 SWPPP (10-13-25)
10/14/2025 Letter INSPECTION SUMMARY
10/15/2025 Letter INSPECTION SUMMARY
10/17/2025 FDR_03534146-9_rev_1
10/17/2025 PRO_03534146-4-01
10/17/2025 PRO_03534146-5-01
10/17/2025 PTR_03534146-3-S1
10/17/2025 PTR_03534146-3-S1_rev_1
10/17/2025 RSI_03534146-16_rev_1
10/17/2025 SLP_03534146-13-01_rev_1
10/18/2025 SWPPP (10-17-25)
10/20/2025 Letter INSPECTION SUMMARY
10/20/2025 hca_lsmc_campus_expansion-rfi#006-anchor_embedment_at_hss_columns_Ans
10/20/2025 hca_lsmc_campus_expansion-rfi#008-elastomeric_pad_thickness_Ans
10/20/2025 hca_lsmc_campus_expansion-rfi#014-struct__-_bridge_shallow_foundations_memo-2025_05_23
10/20/2025 hca_lsmc_campus_expansion-rfi#015-arch__-_expansion_joint,_air_barrier,_&_sealant_details-2025_06_10
10/20/2025 hca_lsmc_campus_expansion-rfi#023-dietex_footings_and_columns-2025_07_03
10/20/2025 hca_lsmc_campus_expansion-rfi#024-struct__-_dietex_steel_deck_&_bent_plate_dimensions-2025_08_07
10/20/2025 hca_lsmc_campus_expansion-rfi#025-missing_spec_section_072726-2025_08_04
10/20/2025 hca_lsmc_campus_expansion-rfi#026-pedestrian_bridge_footings-2025_07_18
10/20/2025 hca_lsmc_campus_expansion-rfi#027-civil_-_drainage_basin_details-2025_07_28
10/20/2025 hca_lsmc_campus_expansion-rfi#033-remote_parking_grade_elevation_confirmation-2025_09_05
10/20/2025 hca_lsmc_campus_expansion-rfi#041-civil_-_pedestrian_bridge_concrete_clarifications-2025_10_02
10/20/2025 hca_lsmc_campus_expansion-rfi#050-retaining_wall_elevations_and_footing_steps-2025_10_03
10/20/2025 hca_lsmc_campus_expansion-rfi#055-civil_-_pedestrian_bridge_elevated_walk_confirmation-2025_10_03
10/20/2025 hca_lsmc_dietary_expansion-rfi#034-dietex_-_life_safety_dampers-202509101842
10/20/2025 hca_lsmc_dietary_expansion-rfi#049-canopy_concrete_pedestal_dimension_and_cladding-202509251858
10/20/2025 hca_lsmc_dietary_expansion-rfi#076-dietex_-_kitchen_grease_duct_access_door-2025_10_15
10/20/2025 RFI-051-irrigation_tap_clarification_CDG Response
10/21/2025 RFI 026 - Pedestrian_Bridge_Footings-2025_07_07-SDL_Stamped
10/21/2025 RFI 041 - Civil - Pedestrian_bridge_concrete_clarifications-SDL-Rev1_Stamped
10/21/2025 RFI 8 Continuous Deck Over Girders_SDL_Stamped
10/21/2025 Geotech Report
10/21/2025 Letter INSPECTION SUMMARY
10/21/2025 Letter INSPECTION SUMMARY
10/21/2025 Letter INSPECTION SUMMARY
10/22/2025 RFI 023 - Diet EX Footings_and_columns-SDL Stamped
10/22/2025 RFI 049 - Canopy_Concrete_Pedestal_Dimension_and_cladding-SDL_09_23_2025-Stamped
10/24/2025 CTR_03534146-15-C1_rev_1
10/24/2025 3RD Party Insp Report hca_lsmc_campus_expansion-rfi#084-pedestrian_bridge_--_rebar_footing_clarification-2025_10_24
10/28/2025 Letter INSPECTION SUMMARY
10/28/2025 Letter INSPECTION SUMMARY
10/29/2025 Letter INSPECTION SUMMARY
10/29/2025 CTR_03534146-19-C1_rev_1
10/29/2025 OS_03534146-24-01_rev_1
10/29/2025 UTSW @ Lee's Summit Med 10-23-25-Final_pdf moment weld for east ipex
10/31/2025 Letter INSPECTION SUMMARY
10/31/2025 Letter INSPECTION SUMMARY
11/03/2025 CTR_03534146-27-C1_rev_1
11/03/2025 CTR_03534146-25-C1_rev_1
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home