Permit Application Status

PRCOM20241448


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20241448
Building Permit - Commercial
In Plan Review
PFIZER INC
ALTERATION COMMERCIAL
Replace existing Siemens proprietary fire alarm control panel and initiating devices with new Silent Knight non-proprietary fire alarm control panel and the following initiating devices: (7) dual monitor modules, (2) mini monitor modules, (1) control module, (4) smoke detectors, (6) relay modules, (10) heat detectors, (6) duct detectors and (20) pull stations. Install (2) new power supplies and (2) new remote annunciators. Power up, program and test new fire alarm control panel to ensure proper operation and reporting to panel. Reset system and restore to normal operation.
03/26/2024
Locations
Contacts
PFIZER INC, Address:150 E 42ND ST FL 38TH  
CINTAS FIRE PROTECTION, Address:6800 CINTAS BLVD, Phone:(913) 441-4477  
smothermanj@cintas.com  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Rejected 04/05/2024 04/05/2024
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
04/05/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Incomplete alarm plan submittal provided on 3/26/2024. Provide equipment specifications. Correct code and standards information to include the 2018 International Fire Code and the 2016 Edition of NFPA 72.
Installation acceptance testing
Corrective Action Required
04/05/2024

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
Miscellaneous Correction
Corrective Action Required
04/05/2024

A fire watch shall be maintained during any system impairment.
Licensed Contractors Approved 04/05/2024 03/26/2024
Andrea Sessler
Inspections

There are no inspections for this permit application.

Documents & Images
Date Uploaded File Type Document Name
03/26/2024 Drawing ZOETIS FIRE ALARM DRAWINGS SEALED
04/05/2024 Letter Fire (Alarm) Plan Review Notice
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home