Summary
PRCOM20240574
Building Permit - Commercial
Certificate of Occupancy
REORGANIZED SCHOOL DISTRICT NO 7
NEW OTHER (COMMERCIAL)
MISSOURI INNOVATION CAMPUS - MODULAR CLASSROOM WITH ALUMINUM RAMP SYSTEM
02/09/2024
03/11/2024
08/28/2024
06/27/2024
Locations
Contacts
Brad Kiehl, Address:brad.kiehl@lsr7.net, Phone:(816) 819-9106  
REORGANIZED SCHOOL DIST #7, Address:301 NE Tudor Rd  
HOLLIS & MILLER ARCHITECTS, Address:1828 Walnut, Ste. 920, Phone:(816) 442-7700  
REORGANIZED SCHOOL DISTRICT NO 7, Address:301 NE TUDOR RD  
Satellite Shelters Inc, Address:3370 N Jackson Avenue  
QUALITY CUSTOM CONCEPTS INC, Address:9707 SOUTH CORN RD, Phone:(816) 697-3232  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 03/08/2024 03/08/2024
Joe Frogge
Fire Plan Review Approved with Conditions 03/08/2024 03/08/2024
Jim Eden
Portable fire extinguishers - general
Corrective Action Required
03/01/2024

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum 2A,10B,C fire extinguisher in each classroom. Verified at inspection.
Miscellaneous Correction
Resolved
03/08/2024

The building fire alarm shall communicate with the main building fire alarm.
Miscellaneous Correction
Resolved
03/08/2024

Provide a detail for the ramp and stairs.
Miscellaneous Correction
Resolved
03/08/2024

Provide an updated code review. The City of Lee's Summit has adopted the 2018 IFC and IBC. The documents shall ensure the modular unit meets the currently adopted codes.
Building Plan Review Approved 03/08/2024 03/04/2024
Joe Frogge
Misc
Resolved
03/04/2024

Provide designs for accessibility ramp. 2/23/24 - Pier design not found. Structure not allowed to be supported from grade.
Zoning Review Approved 03/01/2024 03/03/2024
Shannon McGuire
Corrective Action Required
02/23/2024

The proposed location and use are acceptable from a planning standpoint. You are showing a sidewalk connection from the main building to the modular classroom however it does not appear that this is an ADA accusable route as there are existing curbs along that path. Please show an ADA compliant path to the classroom. This should include ADA ramps at the curbing and should also include a striped crosswalk.
Building Plan Review Rejected 03/01/2024 02/28/2024
Joe Frogge
Misc
Corrective Action Required
02/23/2024

Provide designs for accessibility ramp. 2/23/24 - Pier design not found. Structure not allowed to be supported from grade.
Licensed Contractors Approved 03/01/2024 02/28/2024
Joe Frogge
LC - General Contractor
Resolved
02/23/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
Fire Plan Review Approved with Conditions 03/01/2024 02/27/2024
Jim Eden
Portable fire extinguishers - general
Corrective Action Required
02/23/2024

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum 2A,10B,C fire extinguisher in each classroom. Verified at inspection.
Miscellaneous Correction
Corrective Action Required
02/23/2024

The building fire alarm shall communicate with the main building fire alarm.
Miscellaneous Correction
Corrective Action Required
02/23/2024

Provide a detail for the ramp and stairs.
Miscellaneous Correction
Corrective Action Required
02/23/2024

Provide an updated code review. The City of Lee's Summit has adopted the 2018 IFC and IBC. The documents shall ensure the modular unit meets the currently adopted codes.
Fire Plan Review Rejected 02/23/2024 02/22/2024
Jim Eden
Portable fire extinguishers - general
Corrective Action Required
02/22/2024

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum 2A,10B,C fire extinguisher in each classroom. Verified at inspection.
Miscellaneous Correction
Corrective Action Required
02/22/2024

the building fire alarm shall communicate with the main building fire alarm.
Miscellaneous Correction
Corrective Action Required
02/22/2024

Provide a detail for the ramp and stairs.
Miscellaneous Correction
Corrective Action Required
02/22/2024

Provide an updated plan review. The City of Lee's Summit has adopted the 2018 IFC and IBC.
Zoning Review Rejected 02/23/2024 02/21/2024
Shannon McGuire
Corrective Action Required
02/21/2024

The proposed location and use are acceptable from a planning standpoint. You are showing a sidewalk connection from the main building to the modular classroom however it does not appear that this is an ADA accusable route as there are existing curbs along that path. Please show an ADA compliant path to the classroom. This should include ADA ramps at the curbing and should also include a striped crosswalk.
Licensed Contractors Rejected 02/23/2024 02/20/2024
Joe Frogge
LC - General Contractor
Corrective Action Required
02/20/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
Building Plan Review Rejected 02/23/2024 02/16/2024
Joe Frogge
Misc
Corrective Action Required
02/16/2024

Provide designs for accessibility ramp.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Other $180.00 $180.00 Paid 02/28/2024
Commercial Excise Tax Fee $1,567.50 $1,567.50 Paid 02/12/2024
$1,567.50
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Piers/Caissons Inspection - Commercial Passed 3/18/2024 3/18/2024 03/18/2024
Piers/Caissons Inspection - Commercial Passed 4/18/2024 4/18/2024 04/18/2024
Occupancy Inspection - Fire Failed 6/17/2024 6/17/2024 06/17/2024
Occupancy Inspection - Engineering Passed 6/17/2024 6/17/2024 06/17/2024
Misc
Informational
06/17/2024
6-17-24 RH. Two private ADA ramps were inspected and met ADA requirements. Passed.
Occupancy Inspection - Planning Passed 6/17/2024 6/17/2024 06/17/2024
Occupancy Inspection - Codes Commercial Failed 6/17/2024 6/17/2024 06/17/2024
Misc
Corrective Action Required
06/17/2024
UNDERGROUND ELECTRICAL AND TIEDOWNS COVERED WITHOUT INSPECTION -Provide approved, stamped plans for inspection -Remove skirtting to expose hold downs -Stripe crosswalk per plan -Provide engineered alternative to heilical hold downs -Open all electrical equipment and J boxes for inspection -(2) exterior GFCIs not working -Provide address for separate spaces -Provide occupant load sign at each space -Remove paint behind ground lug at shut off for direct metal to metal contact
Rough Electrical Inspection - Commercial Passed 6/27/2024 6/27/2024 06/27/2024
Occupancy Inspection - Codes Commercial Full C of O 6/27/2024 6/27/2024 06/27/2024
Misc
Resolved
06/27/2024
UNDERGROUND ELECTRICAL AND TIEDOWNS COVERED WITHOUT INSPECTION -Provide approved, stamped plans for inspection -Remove skirtting to expose hold downs -Stripe crosswalk per plan -Provide engineered alternative to heilical hold downs -Open all electrical equipment and J boxes for inspection -(2) exterior GFCIs not working -Provide address for separate spaces -Provide occupant load sign at each space -Remove paint behind ground lug at shut off for direct metal to metal contact
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home