Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved with Conditions
|
01/30/2024
|
01/26/2024
|
|
Joe Frogge
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Provide a minimum of one, 2A,10B,C fire extinguisher if not already present. Verified at inpection.
|
|
Miscellaneous Correction
Corrective Action Required
Relocate the emergency light and any alarm notification appliances that may be on the demo'd partition wall, to the south. Verified at inspection.
|
|
MISC
Corrective Action Required
All reported existing conditions will be subject to inspection for code compliance.
|
|
|
Building Plan Review
|
Approved
|
01/30/2024
|
01/26/2024
|
|
Joe Frogge
|
|
IBC 1209.2 Finish materials
2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4.
2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches.
2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.)
Action required: Modify drawings to demonstrate compliance at walls near toilets. If paint is used it must be epoxy based.
|
|
Code analysis required
A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Action required: Provide code analysis.
|
|
Miscellaneous Correction
Inadequate information.
Action required: Provide floor plan that shows complete final design with each room labelled for specific use.
|
|
IPC 403.1 Minimum number of fixtures
2018 IPC 403.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code.
Action required: Provide mop sink and drinking fountain.
|
|
|
Licensed Contractors
|
Approved
|
01/30/2024
|
01/23/2024
|
|
Joe Frogge
|
|
|
Building Plan Review
|
Rejected
|
01/19/2024
|
01/19/2024
|
|
Tracy Deister
|
|
IBC 1209.2 Finish materials
Corrective Action Required
2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4.
2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches.
2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.)
Action required: Modify drawings to demonstrate compliance at walls near toilets. If paint is used it must be epoxy based.
|
|
Code analysis required
Corrective Action Required
A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Action required: Provide code analysis.
|
|
Miscellaneous Correction
Corrective Action Required
Inadequate information.
Action required: Provide floor plan that shows complete final design with each room labelled for specific use.
|
|
IPC 403.1 Minimum number of fixtures
Corrective Action Required
2018 IPC 403.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code.
Action required: Provide mop sink and drinking fountain.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
01/22/2024
|
01/19/2024
|
|
Jim Eden
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Provide a minimum of one, 2A,10B,C fire extinguisher if not already present. Verified at inpection.
|
|
Miscellaneous Correction
Corrective Action Required
Relocate the emergency light and any alarm notification appliances that may be on the demo'd partition wall, to the south. Verified at inspection.
|
|
MISC
Corrective Action Required
All reported existing conditions will be subject to inspection for code compliance.
|
|
|
Licensed Contractors
|
Approved
|
01/09/2024
|
01/09/2024
|
|
Joe Frogge
|
|
|