Permit Application Status

PRCOM20223920


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20223920
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
MEDICAL OFFICE BUILDING RENOVATION OF THERAPY SPACE INTO OUTPATIENT PULMONARY CLINIC
08/16/2022
09/19/2022
02/26/2023
01/13/2023
Locations
Contacts
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
ACI BOLAND ARCHITECTS, Address:1710 WYANDOTTE ST, Phone:(816) 595-9513  
DAVID E ROSS CONSTRUCTION CO, Address:10201 E 75TH ST, Phone:(816) 737-2953  
rellis@derossconstruction.com, Address:rellis@derossconstruction.com, Phone:(816) 499-1140  
RAND CONSTRUCTION COMPANY, Address:1428 W 9TH ST, Phone:(816) 421-4143  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
RAND CONSTRUCTION COMPANY, Address:1428 W 9TH ST, Phone:(816) 421-4143  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 09/16/2022
Jim Eden
Licensed Contractors Approved 08/31/2022 08/31/2022
Joe Frogge
LC - General Contractor
Resolved
08/31/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Provide an email address & phone number for the on-site contact which is where inspection reports will be sent.
Building Plan Review Approved with Conditions 09/08/2022 08/31/2022
Joe Frogge
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Resolved
08/31/2022

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" at latch side of door 131.5. 8/31/22
NEC Article 517.13 Grounding of receptacles patient care
Corrective Action Required
08/31/2022

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Redundant grounding method verified at inspections.
Fire Plan Review Approved with Conditions 09/08/2022 08/31/2022
Joe Frogge
Construction documents - Fire protection systems
Corrective Action Required
08/31/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Provide shop drawings for review and approval.
Alarms connected to automatic sprinkler system
Corrective Action Required
08/31/2022

2018 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Action required-Provide shop drawings for review and approval.
Installation acceptance testing
Corrective Action Required
08/31/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule alarm testing.
Fire Plan Review Approved with Conditions 08/26/2022 08/25/2022
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
08/25/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Provide shop drawings for review and approval.
Alarms connected to automatic sprinkler system
Corrective Action Required
08/25/2022

2018 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Action required-Provide shop drawings for review and approval.
Installation acceptance testing
Corrective Action Required
08/25/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule alarm testing.
Building Plan Review Rejected 08/26/2022 08/22/2022
Joe Frogge
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Corrective Action Required
08/22/2022

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" at latch side of door 131.5.
NEC Article 517.13 Grounding of receptacles patient care
Corrective Action Required
08/22/2022

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Redundant grounding method verified at inspections.
Licensed Contractors Rejected 08/26/2022 08/16/2022
Joe Frogge
LC - General Contractor
Corrective Action Required
08/16/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Provide an email address & phone number for the on-site contact which is where inspection reports will be sent.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $4,980.00 $4,980.00 Paid 09/01/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 9/22/2022 9/22/2022 09/22/2022
Misc
Informational
09/22/2022
TOLIET ROOM 102 ( FORMER POOL) OK TO POUR
Underslab Plumbing Inspection - Commercial Passed 10/5/2022 10/5/2022 10/05/2022
Misc
Informational
09/22/2022
TOLIET ROOM 102 ( FORMER POOL) OK TO POUR - EXAM ROOMS.RESTROOMS, 3 GUAGES PRESSURE STEADY OK TO COVER -
In-wall Inspection Partial 10/26/2022 10/26/2022 10/26/2022
Misc
Informational
10/26/2022
IN WALL PHASE 1 COMPLETE
Above Ceiling Inspection Failed 12/9/2022 12/9/2022 12/09/2022
Misc
Corrective Action Required
12/09/2022
Phase 1: -Secure all mc within 12' of boxes -Support all mc and low voltage off of grid -Seal penetrations in soil room 109
Above Ceiling Inspection Passed 12/13/2022 12/13/2022
Misc
Resolved
12/13/2022
Phase 1: -Secure all mc within 12' of boxes -Support all mc and low voltage off of grid -Seal penetrations in soil room 109
Alarm Test Passed 1/13/2023 01/13/2023
Occupancy Inspection - Fire Passed 1/13/2023 1/13/2023 01/13/2023
Occupancy Inspection - Codes Commercial Full C of O 1/13/2023 1/13/2023 01/13/2023
Documents & Images
Date Uploaded File Type Document Name
08/16/2022 Application Form Commercial Building Permit
08/16/2022 Plans SLE 1st Floor MOB PERMIT SUBMITTAL 22-0816
08/30/2022 Letter DS P/R Corrections Document
08/31/2022 Drawing A2-1 - FIRST FLOOR DIMENSION AND ANNOTATION PLAN A
08/31/2022 Letter 3-22015-City-Code_Review Response_1st floor MOB 22-0831
08/31/2022 Approved Plans approved - SLE 1st Floor MOB PERMIT SUBMITTAL 22-0816
09/01/2022 Receipt Receipt for transaction:2022-007206
09/16/2022 Letter Fire (Sprinkler) Plan Review
09/19/2022 Letter DS Building Permit
09/22/2022 Letter INSPECTION SUMMARY
10/05/2022 Letter INSPECTION SUMMARY
10/26/2022 Letter INSPECTION SUMMARY
12/09/2022 Letter INSPECTION SUMMARY
12/13/2022 Letter INSPECTION SUMMARY
12/13/2022 Letter Fire Building Plan Review
01/13/2023 Letter Fire Loss Reduction Form
01/13/2023 Letter Codes Final Certificate of Occupancy
01/13/2023 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home