Permit Application Status

PRCOM20223181


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20223181
Building Permit - Commercial
Final Completion
NEW OTHER (COMMERCIAL)
RETAINING WALLS AT SOCCER FIELDS AND ELECTRICAL FOR SOCCER COMPLEX
07/12/2022
07/12/2022
10/25/2023
Locations
Contacts
FOGEL-ANDERSON CONSTRUCTION CO, Address:1212 E 8TH ST, Phone:(816) 842-6914  
CASEY WILLIAMS, Address:FOGEL ANDERSON  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 02/21/2023
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
7232302-Commercial License Tax Fee $135,547.50 $135,547.50 Paid 03/21/2023
$135,547.50
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 7/13/2022 (10:00) 7/13/2022 07/13/2022
Misc
Corrective Action Required
07/13/2022
Field 1 west side south end 52’ Field 1 East side at South end 64’. Ok to pour
Footing Inspection - Commercial Passed 7/14/2022 (1:00) 7/14/2022 07/14/2022
Misc
Corrective Action Required
07/13/2022
Field 1 west side south end 52’ Field 1 East side at South end 64’. Ok to pour 8/14/22 Field 2 East side , South end 13 x 60’ ok to pour
Footing Inspection - Commercial Partial 9/19/2022 (11:30) 9/19/2022 09/19/2022
Misc
Informational
09/19/2022
- SE CORNER FIELD # 3 RETAINING WALL OK TO POUR -
Footing Inspection - Commercial Partial 9/20/2022 (10:00) 9/20/2022 09/20/2022
Misc
Informational
09/19/2022
- SE CORNER FIELD # 3 RETAINING WALL OK TO POUR - - SW CORNER FIELD # 4 RETAIN WALL OK TO POUR -
Footing Inspection - Commercial Failed 9/26/2022 (1:00) 9/26/2022 09/26/2022
Misc
Informational
09/20/2022
- SE CORNER FIELD # 3 RETAINING WALL OK TO POUR - - SW CORNER FIELD # 4 RETAIN WALL OK TO POUR -
Miscellaneous Correction
Corrective Action Required
09/26/2022
NO CITY STAMPED PLANS ON SITE ( FAILED) (2) SPREAD FOOTINGS FOR BLEACHERS SW Ready at 1
Footing Inspection - Commercial Partial 9/27/2022 (1:00) 9/27/2022 09/27/2022
Misc
Informational
09/26/2022
- SE CORNER FIELD # 3 RETAINING WALL OK TO POUR - - SW CORNER FIELD # 4 RETAIN WALL OK TO POUR -
Misc
Informational
09/27/2022
NO CITY STAMPED PLANS ON SITE Bleachers Field 1 9/27/22 (8) footing/piers SW end line B details F2 Sheet 1-0 Line A (1) footing piers NE detail F1 Footings for bleacher footings only Permit # PRCOM20222476 Ok to pour after phone conversation with Joe Frogge 9/17/22 @ 14:19 Michael Harkins 09/27/2022 2:47 PM BLEACHERS FIELD 1 9/28/22 LINE A (7) FOOTING/PIERS DETAIL F1
Footing Inspection - Commercial Partial 9/28/2022 9/28/2022 09/28/2022
Misc
Informational
09/27/2022
- SE CORNER FIELD # 3 RETAINING WALL OK TO POUR - - SW CORNER FIELD # 4 RETAIN WALL OK TO POUR -
Footing Inspection - Commercial Partial 9/29/2022 9/29/2022 09/29/2022
Misc
Informational
09/28/2022
- SE CORNER FIELD # 3 RETAINING WALL OK TO POUR - - SW CORNER FIELD # 4 RETAIN WALL OK TO POUR -
Misc
Informational
09/29/2022
PRCOM20223181 9/27/22 Bleachers Field 1 (8) footing/piers SW end line B details F2 Sheet 1-0 Line A (1) footing piers NE detail F1 Footings for bleacher footings only Permit # PRCOM20223476 Permit # PRCOM20224842 Ok to pour after phone conversation with Joe Frogge 9/17/22 @ 14:19 9/28/22 Bleachers Field 1 Line A (7) footing /piers 9/29/22 Bleachers field 1 Line C (3) footing/piers detail F3 Line B piers 1 Thru 8 Sonotubes w/ anchor bolts
Underground Electrical Inspection - Commercial Partial 10/5/2022 10/05/2022
Misc
Informational
10/05/2022
- 10/05/22 30' FOOTING 6"X6" MAT GRID FOR 8' CMU WALL SOUTH OF BLEACHERS NEAR TRANSFORMER PAD. UFER CLAMP IN CENTER OF FOOTING RUN TO TRANSFORMER PAD -
Footing Inspection - Commercial Partial 10/5/2022 (10:00) 10/5/2022 10/05/2022
Misc
Informational
09/29/2022
- SE CORNER FIELD # 3 RETAINING WALL OK TO POUR - - SW CORNER FIELD # 4 RETAIN WALL OK TO POUR -
Misc
Informational
09/29/2022
PRCOM20223181 9/27/22 Bleachers Field 1 (8) footing/piers SW end line B details F2 Sheet 1-0 Line A (1) footing piers NE detail F1 Footings for bleacher footings only Permit # PRCOM20223476 Permit # PRCOM20224842 Ok to pour after phone conversation with Joe Frogge 9/17/22 @ 14:19 9/28/22 Bleachers Field 1 Line A (7) footing /piers 9/29/22 Bleachers field 1 Line C (3) footing/piers detail F3 Line B piers 1 Thru 8 Sonotubes w/ anchor bolts
Misc
Informational
10/05/2022
- 10/05/22 30' FOOTING 6"X6" MAT GRID FOR 8' CMU WALL SOUTH OF BLEACHERS NEAR TRANSFORMER PAD. UFER CLAMP IN CENTER OF FOOTING RUN TO TRANSFORMER PAD -
Piers/Caissons Inspection - Commercial Partial 10/7/2022 10/07/2022
Misc
Informational
10/07/2022
- 10/7/22 PRECAST POLE BASE # 3 OF 27 BETWEEN FIELDS # 1 & # 2 23' DEEP PIER REBAR PER PLAN TYPE F3 -
Piers/Caissons Inspection - Commercial Partial 10/10/2022 10/10/2022
Misc
Informational
10/07/2022
: PRECAST FIELD LIGHT POLE BASES : * PUMP WATER FROM PIERS BEFORE POURING * - 10/7/22 PRECAST POLE BASE # 3 OF 27 BETWEEN FIELDS # 1 & # 2 23' DEEP PIER REBAR PER PLAN TYPE F3 - 10/10/22 # S4 BETWEEN FIELDS 1 & 2 42" DIA, 23' DEPTH, 18 # 7 BARS VERTICAL W/ #4 HORIZONTAL TIES @ 12" - - 10/10/22 S1 FIELD 1 AT BLEACHERS 42" DIA 21' DEPTH 18 # 7 BARS VERTICAL W/ #4 BARS HORIZONTAL TIES, S14 BETWEEN FIELDS 5 & 6 42" DIA 23' DEPTH 18 # 7 BARS W/ # 4 HORIZONTAL BARS @ 12" - : ALSO CALLED IN ON PERMIT # 20201955 :
Piers/Caissons Inspection - Commercial Partial 10/11/2022 10/11/2022 10/11/2022
Misc
Informational
10/10/2022
: PRECAST FIELD LIGHT POLE BASES : * PUMP WATER FROM PIERS BEFORE POURING * - 10/7/22 PRECAST POLE BASE # 3 OF 27 BETWEEN FIELDS # 1 & # 2 23' DEEP PIER REBAR PER PLAN TYPE F3 - 10/10/22 # S4 BETWEEN FIELDS 1 & 2 42" DIA, 23' DEPTH, 18 # 7 BARS VERTICAL W/ #4 HORIZONTAL TIES @ 12" - - 10/10/22 S1 FIELD 1 AT BLEACHERS 42" DIA 21' DEPTH 18 # 7 BARS VERTICAL W/ #4 BARS HORIZONTAL TIES, S14 BETWEEN FIELDS 5 & 6 42" DIA 23' DEPTH 18 # 7 BARS W/ # 4 HORIZONTAL BARS @ 12" - : ALSO CALLED IN ON PERMIT # 20201955 : - 10/11/22 S2 FIELD 1 AT BLEACHERS 21' DEPTH S12 WEST SIDE FIELD 5/ PARKING LOT 21' DEPTH S13 BETWEEN FIELDS 5 & 6 23' DEPTH, ALL SAME REBAR CAGE AS ABOVE -
Piers/Caissons Inspection - Commercial Partial 10/13/2022 (10:00) 10/13/2022 10/13/2022
Misc
Informational
10/11/2022
: PRECAST FIELD LIGHT POLE BASES : * PUMP WATER FROM PIERS BEFORE POURING * - 10/7/22 PRECAST POLE BASE S3 OF 28 BETWEEN FIELDS # 1 & # 2 23' DEEP PIER REBAR PER PLAN TYPE F3 - 10/10/22 # S4 BETWEEN FIELDS 1 & 2 42" DIA, 23' DEPTH, 18 # 7 BARS VERTICAL W/ #4 HORIZONTAL TIES @ 12" - - 10/10/22 S1 FIELD 1 AT BLEACHERS 42" DIA 21' DEPTH 18 # 7 BARS VERTICAL W/ #4 BARS HORIZONTAL TIES, S14 BETWEEN FIELDS 5 & 6 42" DIA 23' DEPTH 18 # 7 BARS W/ # 4 HORIZONTAL BARS @ 12" - : ALSO CALLED IN ON PERMIT # 20201955 : - 10/11/22 S2 FIELD 1 AT BLEACHERS 21' DEPTH S12 WEST SIDE FIELD 5/ PARKING LOT 21' DEPTH S13 BETWEEN FIELDS 5 & 6 23' DEPTH, ALL SAME REBAR CAGE AS ABOVE - - 10/13/22 S5 & S6 BETWEEN FIELDS 2 & 3 23' DEPTH S11 FIELD 5 @ PARKING LOT 21' -
Piers/Caissons Inspection - Commercial Partial 11/3/2022 (11:00) 11/3/2022 11/03/2022
Misc
Informational
10/13/2022
: PRECAST FIELD LIGHT POLE BASES : * PUMP WATER FROM PIERS BEFORE POURING * - 10/7/22 PRECAST POLE BASE # 3 OF 27 BETWEEN FIELDS # 1 & # 2 23' DEEP PIER REBAR PER PLAN TYPE F3 - 10/10/22 # S4 BETWEEN FIELDS 1 & 2 42" DIA, 23' DEPTH, 18 # 7 BARS VERTICAL W/ #4 HORIZONTAL TIES @ 12" - - 10/10/22 S1 FIELD 1 AT BLEACHERS 42" DIA 21' DEPTH 18 # 7 BARS VERTICAL W/ #4 BARS HORIZONTAL TIES, S14 BETWEEN FIELDS 5 & 6 42" DIA 23' DEPTH 18 # 7 BARS W/ # 4 HORIZONTAL BARS @ 12" - : ALSO CALLED IN ON PERMIT # 20201955 : - 10/11/22 S2 FIELD 1 AT BLEACHERS 21' DEPTH S12 WEST SIDE FIELD 5/ PARKING LOT 21' DEPTH S13 BETWEEN FIELDS 5 & 6 23' DEPTH, ALL SAME REBAR CAGE AS ABOVE - - 10/13/22 S5 & S6 BETWEEN FIELDS 2 & 3 23' DEPTH S11 FIELD 5 @ PARKING LOT 21' - - 11/3/22 S15 & S16 BETWEEN FIELDS 6 & 7 23'-
Piers/Caissons Inspection - Commercial Partial 11/3/2022 11/03/2022
Misc
Informational
11/03/2022
: PRECAST FIELD LIGHT POLE BASES : * PUMP WATER FROM PIERS BEFORE POURING * - 10/7/22 PRECAST POLE BASE # 3 OF 27 BETWEEN FIELDS # 1 & # 2 23' DEEP PIER REBAR PER PLAN TYPE F3 - 10/10/22 # S4 BETWEEN FIELDS 1 & 2 42" DIA, 23' DEPTH, 18 # 7 BARS VERTICAL W/ #4 HORIZONTAL TIES @ 12" - - 10/10/22 S1 FIELD 1 AT BLEACHERS 42" DIA 21' DEPTH 18 # 7 BARS VERTICAL W/ #4 BARS HORIZONTAL TIES, S14 BETWEEN FIELDS 5 & 6 42" DIA 23' DEPTH 18 # 7 BARS W/ # 4 HORIZONTAL BARS @ 12" - : ALSO CALLED IN ON PERMIT # 20201955 : - 10/11/22 S2 FIELD 1 AT BLEACHERS 21' DEPTH S12 WEST SIDE FIELD 5/ PARKING LOT 21' DEPTH S13 BETWEEN FIELDS 5 & 6 23' DEPTH, ALL SAME REBAR CAGE AS ABOVE - - 10/13/22 S5 & S6 BETWEEN FIELDS 2 & 3 23' DEPTH S11 FIELD 5 @ PARKING LOT 21' - - 11/3/22 S15 & S16 BETWEEN FIELDS 6 & 7 23'- - 11/3/22 2ND TRIP S7 & S8 BETWEEN FIELDS 3 & 4 -
Piers/Caissons Inspection - Commercial Partial 11/4/2022 11/04/2022
Misc
Informational
11/03/2022
: PRECAST FIELD LIGHT POLE BASES : * PUMP WATER FROM PIERS BEFORE POURING * - 10/7/22 PRECAST POLE BASE # 3 OF 27 BETWEEN FIELDS # 1 & # 2 23' DEEP PIER REBAR PER PLAN TYPE F3 - 10/10/22 # S4 BETWEEN FIELDS 1 & 2 42" DIA, 23' DEPTH, 18 # 7 BARS VERTICAL W/ #4 HORIZONTAL TIES @ 12" - - 10/10/22 S1 FIELD 1 AT BLEACHERS 42" DIA 21' DEPTH 18 # 7 BARS VERTICAL W/ #4 BARS HORIZONTAL TIES, S14 BETWEEN FIELDS 5 & 6 42" DIA 23' DEPTH 18 # 7 BARS W/ # 4 HORIZONTAL BARS @ 12" - : ALSO CALLED IN ON PERMIT # 20201955 : - 10/11/22 S2 FIELD 1 AT BLEACHERS 21' DEPTH S12 WEST SIDE FIELD 5/ PARKING LOT 21' DEPTH S13 BETWEEN FIELDS 5 & 6 23' DEPTH, ALL SAME REBAR CAGE AS ABOVE - - 10/13/22 S5 & S6 BETWEEN FIELDS 2 & 3 23' DEPTH S11 FIELD 5 @ PARKING LOT 21' - - 11/3/22 S15 & S16 BETWEEN FIELDS 6 & 7 23'- - 11/3/22 2ND TRIP S7 & S8 BETWEEN FIELDS 3 & 4 -11/14/22 PRECAST LIGHT POLS BASES P7 + P8
Piers/Caissons Inspection - Commercial Partial 11/8/2022 (11:00) 11/8/2022 11/08/2022
Misc
Informational
11/04/2022
: PRECAST FIELD LIGHT POLE BASES : * PUMP WATER FROM PIERS BEFORE POURING * - 10/7/22 PRECAST POLE BASE # 3 OF 27 BETWEEN FIELDS # 1 & # 2 23' DEEP PIER REBAR PER PLAN TYPE F3 - 10/10/22 # S4 BETWEEN FIELDS 1 & 2 42" DIA, 23' DEPTH, 18 # 7 BARS VERTICAL W/ #4 HORIZONTAL TIES @ 12" - - 10/10/22 S1 FIELD 1 AT BLEACHERS 42" DIA 21' DEPTH 18 # 7 BARS VERTICAL W/ #4 BARS HORIZONTAL TIES, S14 BETWEEN FIELDS 5 & 6 42" DIA 23' DEPTH 18 # 7 BARS W/ # 4 HORIZONTAL BARS @ 12" - : ALSO CALLED IN ON PERMIT # 20201955 : - 10/11/22 S2 FIELD 1 AT BLEACHERS 21' DEPTH S12 WEST SIDE FIELD 5/ PARKING LOT 21' DEPTH S13 BETWEEN FIELDS 5 & 6 23' DEPTH, ALL SAME REBAR CAGE AS ABOVE - - 10/13/22 S5 & S6 BETWEEN FIELDS 2 & 3 23' DEPTH S11 FIELD 5 @ PARKING LOT 21' - - 11/3/22 S15 & S16 BETWEEN FIELDS 6 & 7 23'- - 11/3/22 2ND TRIP S7 & S8 BETWEEN FIELDS 3 & 4 -11/4/22 PRECAST LIGHT POLS BASES P7 + P8 - 11/8/22 S22 & S23 EAST OF FIELD 8 21', S9 & S10 EAST OF FIELD 4 21' - -
Piers/Caissons Inspection - Commercial Partial 11/9/2022 (11:00) 11/9/2022 11/09/2022
Misc
Informational
11/08/2022
: PRECAST FIELD LIGHT POLE BASES : * PUMP WATER FROM PIERS BEFORE POURING * - 10/7/22 PRECAST POLE BASE # 3 OF 27 BETWEEN FIELDS # 1 & # 2 23' DEEP PIER REBAR PER PLAN TYPE F3 - 10/10/22 # S4 BETWEEN FIELDS 1 & 2 42" DIA, 23' DEPTH, 18 # 7 BARS VERTICAL W/ #4 HORIZONTAL TIES @ 12" - - 10/10/22 S1 FIELD 1 AT BLEACHERS 42" DIA 21' DEPTH 18 # 7 BARS VERTICAL W/ #4 BARS HORIZONTAL TIES, S14 BETWEEN FIELDS 5 & 6 42" DIA 23' DEPTH 18 # 7 BARS W/ # 4 HORIZONTAL BARS @ 12" - : ALSO CALLED IN ON PERMIT # 20201955 : - 10/11/22 S2 FIELD 1 AT BLEACHERS 21' DEPTH S12 WEST SIDE FIELD 5/ PARKING LOT 21' DEPTH S13 BETWEEN FIELDS 5 & 6 23' DEPTH, ALL SAME REBAR CAGE AS ABOVE - - 10/13/22 S5 & S6 BETWEEN FIELDS 2 & 3 23' DEPTH S11 FIELD 5 @ PARKING LOT 21' - - 11/3/22 S15 & S16 BETWEEN FIELDS 6 & 7 23'- - 11/3/22 2ND TRIP S7 & S8 BETWEEN FIELDS 3 & 4 -11/4/22 PRECAST LIGHT POLS BASES P7 + P8 - 11/8/22 S22 & S23 EAST OF FIELD 8 21', S9 & S10 EAST OF FIELD 4 21' - - 11/9/22 P9 & P10 NORTH END FIELD #7 21', P5 & P6 SOUTH END FIELDS 9 & 10 -
Piers/Caissons Inspection - Commercial Partial 11/10/2022 11/10/2022 11/10/2022
Misc
Informational
11/09/2022
: PRECAST FIELD LIGHT POLE BASES : * PUMP WATER FROM PIERS BEFORE POURING * - 10/7/22 PRECAST POLE BASE # 3 OF 27 BETWEEN FIELDS # 1 & # 2 23' DEEP PIER REBAR PER PLAN TYPE F3 - 10/10/22 # S4 BETWEEN FIELDS 1 & 2 42" DIA, 23' DEPTH, 18 # 7 BARS VERTICAL W/ #4 HORIZONTAL TIES @ 12" - - 10/10/22 S1 FIELD 1 AT BLEACHERS 42" DIA 21' DEPTH 18 # 7 BARS VERTICAL W/ #4 BARS HORIZONTAL TIES, S14 BETWEEN FIELDS 5 & 6 42" DIA 23' DEPTH 18 # 7 BARS W/ # 4 HORIZONTAL BARS @ 12" - : ALSO CALLED IN ON PERMIT # 20201955 : - 10/11/22 S2 FIELD 1 AT BLEACHERS 21' DEPTH S12 WEST SIDE FIELD 5/ PARKING LOT 21' DEPTH S13 BETWEEN FIELDS 5 & 6 23' DEPTH, ALL SAME REBAR CAGE AS ABOVE - - 10/13/22 S5 & S6 BETWEEN FIELDS 2 & 3 23' DEPTH S11 FIELD 5 @ PARKING LOT 21' - - 11/3/22 S15 & S16 BETWEEN FIELDS 6 & 7 23'- - 11/3/22 2ND TRIP S7 & S8 BETWEEN FIELDS 3 & 4 -11/4/22 PRECAST LIGHT POLS BASES P7 + P8 - 11/8/22 S22 & S23 EAST OF FIELD 8 21', S9 & S10 EAST OF FIELD 4 21' - - 11/9/22 P9 & P10 NORTH END FIELD #7 21', P5 & P6 SOUTH END FIELDS 9 & 10 - - 11/10/22 P1 & P2 EAST SIDE FIELD 10 21' P3 & P4 WEST SIDE FIELD 9 21' -
Electrical Service Inspection Partial 2/17/2023 2/17/2023 02/17/2023
Misc
Informational
02/17/2023
Service 2 of 2 approved
Underground Electrical Inspection - Commercial Partial 3/2/2023 3/2/2023 03/02/2023
Misc
Informational
10/05/2022
- 10/05/22 30' FOOTING 6"X6" MAT GRID FOR 8' CMU WALL SOUTH OF BLEACHERS NEAR TRANSFORMER PAD. UFER CLAMP IN CENTER OF FOOTING RUN TO TRANSFORMER PAD - 3/2/23 Conduit for services and lights north of fields 9 and 10 ending just west of field 9
Underground Electrical Inspection - Commercial Partial 4/18/2023 4/18/2023 03/27/2023
Misc
Informational
03/02/2023
- 10/05/22 30' FOOTING 6"X6" MAT GRID FOR 8' CMU WALL SOUTH OF BLEACHERS NEAR TRANSFORMER PAD. UFER CLAMP IN CENTER OF FOOTING RUN TO TRANSFORMER PAD - 3/2/23 Conduit for services and lights north of fields 9 and 10 ending just west of field 9 3/27/23 Conduit for service lf3 at restroom/concession wall west of field 9
Underground Electrical Inspection - Commercial Partial 4/14/2023 4/14/2023 04/14/2023
Misc
Informational
03/27/2023
- 10/05/22 30' FOOTING 6"X6" MAT GRID FOR 8' CMU WALL SOUTH OF BLEACHERS NEAR TRANSFORMER PAD. UFER CLAMP IN CENTER OF FOOTING RUN TO TRANSFORMER PAD - 3/2/23 Conduit for services and lights north of fields 9 and 10 ending just west of field 9 3/27/23 Conduit for service lf3 at restroom/concession wall west of field 9 4/14/23 Conduit for service lf2 at restroom/concession wall near field 3
Underground Electrical Inspection - Commercial Partial 4/18/2023 4/18/2023 04/18/2023
Misc
Informational
04/14/2023
- 10/05/22 30' FOOTING 6"X6" MAT GRID FOR 8' CMU WALL SOUTH OF BLEACHERS NEAR TRANSFORMER PAD. UFER CLAMP IN CENTER OF FOOTING RUN TO TRANSFORMER PAD - 3/2/23 Conduit for services and lights north of fields 9 and 10 ending just west of field 9 3/27/23 Conduit for service lf3 at restroom/concession wall west of field 9 4/14/23 Conduit for service lf2 at restroom/concession wall near field 3 4/18/23 Conduit from lf2 for field lighting heading east to first musco light north of field 7 (partial)
Underground Electrical Inspection - Commercial Partial 4/19/2023 4/19/2023 04/19/2023
Misc
Informational
04/18/2023
- 10/05/22 30' FOOTING 6"X6" MAT GRID FOR 8' CMU WALL SOUTH OF BLEACHERS NEAR TRANSFORMER PAD. UFER CLAMP IN CENTER OF FOOTING RUN TO TRANSFORMER PAD - 3/2/23 Conduit for services and lights north of fields 9 and 10 ending just west of field 9 3/27/23 Conduit for service lf3 at restroom/concession wall west of field 9 4/14/23 Conduit for service lf2 at restroom/concession wall near field 3 4/18/23 Conduit from lf2 for field lighting heading east to first musco light north of field 7 (partial) 4/19/23 Contintuing east to last musco light north of field 7 (partial)
Underground Electrical Inspection - Commercial Partial 4/21/2023 04/21/2023
Misc
Informational
04/19/2023
- 10/05/22 30' FOOTING 6"X6" MAT GRID FOR 8' CMU WALL SOUTH OF BLEACHERS NEAR TRANSFORMER PAD. UFER CLAMP IN CENTER OF FOOTING RUN TO TRANSFORMER PAD - 3/2/23 Conduit for services and lights north of fields 9 and 10 ending just west of field 9 3/27/23 Conduit for service lf3 at restroom/concession wall west of field 9 4/14/23 Conduit for service lf2 at restroom/concession wall near field 3 4/18/23 Conduit from lf2 for field lighting heading east to first musco light north of field 7 (partial) 4/19/23 Contintuing east to last musco light north of field 7 (partial) 4/21/23 Finished line east to north of field 7
Underground Electrical Inspection - Commercial Passed 4/26/2023 4/26/2023 04/26/2023
Misc
Resolved
04/26/2023
- 10/05/22 30' FOOTING 6"X6" MAT GRID FOR 8' CMU WALL SOUTH OF BLEACHERS NEAR TRANSFORMER PAD. UFER CLAMP IN CENTER OF FOOTING RUN TO TRANSFORMER PAD - 3/2/23 Conduit for services and lights north of fields 9 and 10 ending just west of field 9 3/27/23 Conduit for service lf3 at restroom/concession wall west of field 9 4/14/23 Conduit for service lf2 at restroom/concession wall near field 3 4/18/23 Conduit from lf2 for field lighting heading east to first musco light north of field 7 (partial) 4/19/23 Contintuing east to last musco light north of field 7 (partial) 4/21/23 Finished line east to north of field 7
Rough Electrical Inspection - Commercial Partial 3/28/2023 4/27/2023 04/27/2023
Final Inspection - Commercial Passed 05/12/2023
Electrical Service Inspection Passed 6/7/2023 6/7/2023 06/07/2023
Misc
Informational
06/06/2023
*2/17/23 Service 2 of 2 approved *6/7/23 Service 1 of 2 approved
Documents & Images
Date Uploaded File Type Document Name
04/26/2022 Approved Plans Approved Soccer Field Plans Civil Only 2020_11_04_PL2019407_Part1
07/13/2022 Letter INSPECTION SUMMARY
07/14/2022 Letter INSPECTION SUMMARY
08/11/2022 Approved Plans approved - Paragon Sports Complex - ELEC - SS
09/19/2022 Letter INSPECTION SUMMARY
09/20/2022 Letter INSPECTION SUMMARY
09/26/2022 Letter INSPECTION SUMMARY
09/26/2022 Letter INSPECTION SUMMARY
09/28/2022 Letter INSPECTION SUMMARY
09/29/2022 Letter INSPECTION SUMMARY
10/05/2022 Letter INSPECTION SUMMARY
10/05/2022 Letter INSPECTION SUMMARY
10/07/2022 Letter INSPECTION SUMMARY
10/10/2022 Letter INSPECTION SUMMARY
10/11/2022 Letter INSPECTION SUMMARY
10/13/2022 Letter INSPECTION SUMMARY
11/03/2022 Letter INSPECTION SUMMARY
11/03/2022 Letter INSPECTION SUMMARY
11/04/2022 Letter INSPECTION SUMMARY
11/08/2022 Letter INSPECTION SUMMARY
11/09/2022 Letter INSPECTION SUMMARY
11/10/2022 Letter INSPECTION SUMMARY
02/17/2023 Letter INSPECTION SUMMARY
02/17/2023 Letter INSPECTION SUMMARY
02/21/2023 Letter License Tax Bill
01/24/2023 Letter INSPECTION SUMMARY
02/09/2023 Letter INSPECTION SUMMARY
07/14/2022 Letter INSPECTION SUMMARY
09/12/2022 Letter INSPECTION SUMMARY
09/12/2022 Letter INSPECTION SUMMARY
10/04/2022 Letter INSPECTION SUMMARY
01/13/2023 Letter INSPECTION SUMMARY
01/17/2023 Letter INSPECTION SUMMARY
03/02/2023 Letter INSPECTION SUMMARY
03/21/2023 Application Form Paragon Star Sports Complex Excise Tax Application
03/21/2023 Application Form 7762 - Highlighting for Political Subdivision
03/21/2023 Application Form CID Act - Highlights for Political Subdivision
03/27/2023 Letter INSPECTION SUMMARY
04/14/2023 Letter INSPECTION SUMMARY
04/18/2023 Letter INSPECTION SUMMARY
04/19/2023 Letter INSPECTION SUMMARY
04/21/2023 Letter INSPECTION SUMMARY
04/26/2023 Letter INSPECTION SUMMARY
04/26/2023 Letter License Tax Bill
04/27/2023 Letter INSPECTION SUMMARY
06/07/2023 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.