Permit Application Status

PRCOM20222464


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20222464
Building Permit - Commercial
Voided
SUMMIT POINT PROPERTY INVESTORS LLC
NEW MULTI-FAMILY
NEW APARTMENT BUILDING PLANS EXPIRED
06/06/2022
12/18/2022
10/17/2023
Locations
Contacts
SUMMIT POINT PROPERTY INVESTORS LLC, Address:331 SOQUEL AVE STE 100  
BCS ARCHITECTURE, Address:19920 WEST 161ST STREET, Phone:(913) 780-4820  
  
  
  
  
  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Rejected 06/20/2022 06/21/2022
Jim Eden
Miscellaneous Correction
Corrective Action Required
06/20/2022

All hydrants and the base layer of asphalt shall be in place before bringing combustible materials on site or going vertical with combustible construction.
Miscellaneous Correction
Corrective Action Required
06/20/2022

An approved Final Development Plan is required.
Locks on gates or barriers
Corrective Action Required
06/20/2022

2018 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. Action required- Provide a Knox padlock on the emergency access gate.
Knox box required
Corrective Action Required
06/20/2022

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Action required- A Knox box shall be located 6' AFF over the FDC on each building.
Group A alarm activation
Corrective Action Required
06/20/2022

2018 IFC 907.2.1.1- System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal using an emergency voice/alarm communications system in accordance with NFPA 72. Exception: Where approved, the prerecorded announcement is allowed to be manually deactivated for a period of time, not to exceed 3 minutes, for the sole purpose of allowing a live voice announcement from an approved, constantly attended location.
Construction documents for fire alarm systems
Corrective Action Required
06/20/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required- Provide alarm plans for review and approval.
Construction documents - Fire protection systems
Corrective Action Required
06/20/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Provide sprinkler plans for review and approval.
Installation acceptance testing
Corrective Action Required
06/20/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Miscellaneous Correction
Corrective Action Required
06/20/2022

Class 1 standpipes (hose valves are required).
Portable fire extinguishers - general
Corrective Action Required
06/21/2022

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Verified at inspection.
Building Plan Review Rejected 06/20/2022 06/14/2022
Joe Frogge
Final Development Plan
Corrective Action Required
06/14/2022

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
06/14/2022

This review covers all six apartment structures. Action required: Comment is for informational purposes.
Miscellaneous Correction
Corrective Action Required
06/14/2022

On sheet A001, fire partition notes refer to IBC 708.1 (#4) which is specific to elevator lobbies. Was this supposed to be #3? Action required: Clarify.
IBC 1704.2 Special Inspections
Corrective Action Required
06/16/2022

2018 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Actions required: - Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections. - Add Wood construction to list of special inspections per IBC 1705.5
Engineered truss package
Corrective Action Required
06/16/2022

Copies of the engineered truss package were not provided at the time of permit application. Action required: Deferred per plans. Must be approved prior to inspections.
Miscellaneous Correction
Corrective Action Required
06/16/2022

Final Development plan and Structural designs show a clubhouse but Architectural designs not found. Action required: Provide complete clubhouse designs.
Miscellaneous Correction
Corrective Action Required
06/16/2022

Water meters must be purchased from our Water Department. Action required: Remove or modify notes on A101a, A102a, & A103a.
ICC A117.1 1104.5.1 Type B Primary Entrance Door
Corrective Action Required
06/16/2022

ICC A117.1-2009 Section 1003.2 Primary Entrance. The accessible primary entrance shall be on an accessible route from public and common areas. The primary entrance shall not be to a bedroom unless it is the only entrance. Action required: Type A units must be on an accessible route. i.e. no stairs.
IBC 716.2.3 Fire and Smoke Protection - fire doors
Corrective Action Required
06/16/2022

2018 IBC 716.2.3 Fire doors. Fire doors installed within a fire door assembly shall meet the fire rating indicated in Table 716.1(2). Action required: Eliminate peep holes in fire rated doors or provide verification that they will not reduce fire rating.
IPC 708.1 Cleanouts required
Corrective Action Required
06/17/2022

2018 IPC 708.1 Cleanouts Required. Cleanouts shall be provided for drainage piping in accordance with Sections 708.1.1 through 708.1.11. 2018 IPC 708.1.3 Building drain and building sewer junction. The junction of the building drain and the building sewer shall be served by a cleanout that is located at the junction or within 10 feet of the developed length of piping upstream of the junction. For the requirements of this section, the removal of a water closet shall not be required to provide cleanout access. Action required: Provide cleanout near where waste exits foundation.
Miscellaneous Correction
Corrective Action Required
06/17/2022

Light pole base detail is incomplete. Action required: Modify detail to include all construction details that include connection, depth, diameter, reinforcement, etc.
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
06/17/2022

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Add and/or relocate receptacles to be within 25' of all condensing units. See E113
Licensed Contractors Rejected 06/20/2022 06/13/2022
Joe Frogge
LC - General Contractor
Corrective Action Required
06/13/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
06/13/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Inspections

There are no inspections for this permit application.

Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home