Permit Application Status

PRCOM20220644


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20220644
Building Permit - Commercial
Certificate of Occupancy
LALLY STEVEN E TRUSTEE
ALTERATION COMMERCIAL
REMODEL EXISTING EYE CLINIC
02/22/2022
03/29/2022
08/30/2022
09/01/2022
Locations
Contacts
BGS CONSTRUCTION, Address:34607 E COLBERN RD, Phone:(816) 566-0351  
bgsmanagement2@Gmail.com, Address:bgsmanagement2@Gmail.com  
PRO PLATINUM LLC, Address:6116 ALDEN RD, Phone:(913) 908-3512  
ENDEAVOR ELECTRICAL CONSTRUCTION LLP, Address:P O BOX 1201, Phone:(816) 591-5867  
SLOCUM & SONS PLUMBING, Address:3804 S MARSHALL CT, Phone:(816) 373-4817  
KANSAS CITY DESIGN GROUP, Address:4006 N 126TH ST, Phone:(816) 682-0329  
LALLY STEVEN E TRUSTEE, Address:200 TEAKWOOD  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 03/23/2022 03/28/2022
Joe Frogge
LC - MEP Subs
Resolved
03/28/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 3/16/22 - Endeavor Electric not currently licensed with us.
Fire Plan Review Approved 03/23/2022 03/22/2022
Jim Eden
Portable fire extinguishers - general
Corrective Action Required
03/16/2022

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required- Provide or maintain a minimum of one 2A:10B:C fire extinguisher at a conspicuous location in a normal pathway. Verified at inspection.
Building Plan Review Approved 03/23/2022 03/16/2022
Joe Frogge
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Resolved
03/16/2022

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Actions required: At vestiblue rovide minimum 60" depth (currently 56") and 36" latch side wall clearance. At multiple other doors provide minimum 18" clearance at latch side. 3/16/22 - vestibule is unchanged
ICC A117.1 904.3 Sales and Service Counters
Resolved
03/16/2022

ICC A117.1 Section 904.3 Sales and service counters and windows. Sales and service counters and windows shall comply with Section 904.3.1 and either 904.3.2 or 904.3.3. Where counters are provided, the accessible portion of the countertop shall extend the same depth as the public portion of the sales and service countertop provided for standing customers. (see code for exception) 904.3.1 Vertical barriers. At service windows or service counters, any vertical barrier between service personnel and customers shall be at a height of 43 inches maximum above the floor. (see code for exception regarding security glazing) 904.3.2 Parallel Approach. A portion of the public use side of the counter surface 36 inches minimum in length and 26 inches minimum and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a parallel approach adjacent to the accessible counter shall be provided. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12 inches minimum. (see code for exception) 904.3.3 Forward Approach. A portion of the public use side of the counter surface 30 inches minimum in length and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a forward approach to the accessible counter shall be provided. Knee and toe clearance complying with Section 306 shall be provided under the accessible counter. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12” minimum. Action required: Provide minimum 36" of accessible counter at reception.
Miscellaneous Correction
Resolved
03/16/2022

Inadequate information to complete review. Action required: Provide complete HVAC and plumbing designs.
NEC Article 517.13 Grounding of receptacles patient care
Resolved
03/16/2022

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system.
Fire Plan Review Approved with Conditions 03/04/2022 03/02/2022
Jim Eden
Portable fire extinguishers - general
Corrective Action Required
03/02/2022

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required- Provide or maintain a minimum of one 2A:10B:C fire extinguisher at a conspicuous location in a normal pathway. Verified at inspection.
Building Plan Review Rejected 03/04/2022 02/25/2022
Joe Frogge
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Corrective Action Required
02/25/2022

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Actions required: At vestiblue rovide minimum 60" depth (currently 56") and 36" latch side wall clearance. At multiple other doors provide minimum 18" clearance at latch side.
ICC A117.1 904.3 Sales and Service Counters
Corrective Action Required
02/25/2022

ICC A117.1 Section 904.3 Sales and service counters and windows. Sales and service counters and windows shall comply with Section 904.3.1 and either 904.3.2 or 904.3.3. Where counters are provided, the accessible portion of the countertop shall extend the same depth as the public portion of the sales and service countertop provided for standing customers. (see code for exception) 904.3.1 Vertical barriers. At service windows or service counters, any vertical barrier between service personnel and customers shall be at a height of 43 inches maximum above the floor. (see code for exception regarding security glazing) 904.3.2 Parallel Approach. A portion of the public use side of the counter surface 36 inches minimum in length and 26 inches minimum and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a parallel approach adjacent to the accessible counter shall be provided. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12 inches minimum. (see code for exception) 904.3.3 Forward Approach. A portion of the public use side of the counter surface 30 inches minimum in length and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a forward approach to the accessible counter shall be provided. Knee and toe clearance complying with Section 306 shall be provided under the accessible counter. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12” minimum. Action required: Provide minimum 36" of accessible counter at reception.
Miscellaneous Correction
Corrective Action Required
02/25/2022

Inadequate information to complete review. Action required: Provide complete HVAC and plumbing designs.
NEC Article 517.13 Grounding of receptacles patient care
Corrective Action Required
02/25/2022

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system.
Licensed Contractors Rejected 03/04/2022 02/25/2022
Joe Frogge
LC - MEP Subs
Corrective Action Required
02/25/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Alteration to Commercial $360.00 $360.00 Paid 03/28/2022
8331507-Sewer Connection Fee $60.00 $60.00 Paid 03/28/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 3/30/2022 3/30/2022 03/30/2022
Miscellaneous Correction
Corrective Action Required
03/30/2022
Phase 1 Exam room 1 & 2 & patient lav : ELECTRICAL ONLY : Seal all upward penetrations Seal stud penetrations in plenum DO NOT COVER ABOVE ITEMS UNTIL AFTER RE INSPECTION (Ok to One side at optical area & exam 2 west wall)
In-wall Inspection Partial 3/31/2022 3/31/2022 03/31/2022
Misc
Informational
03/31/2022
Phase 1 Exam room 1 & 2 & patient lav. OK TO DRYWALL PHASE 1 -
In-wall Inspection Partial 6/13/2022 06/13/2022
Misc
Informational
03/31/2022
Phase 1 Exam room 1 & 2 & patient lav. OK TO DRYWALL PHASE 1 - Phase 2 Insurance 103 ok to cover -Fireblock all plate penetrations -Provide bocca plates at all dwv less than 1.25" to face of framing
In-wall Inspection Failed 6/14/2022 6/14/2022 06/14/2022
Misc
Informational
06/13/2022
Phase 1 Exam room 1 & 2 & patient lav. OK TO DRYWALL PHASE 1 - Phase 2 Insurance 103 ok to cover -Fireblock all plate penetrations-NOT DONE -Provide bocca plates at all dwv less than 1.25" to face of framing-NOT DONE-PROTECT DWV 2" PAST PLATE TOP AND BOTTOM
In-wall Inspection Passed 6/15/2022 6/15/2022 06/15/2022
Misc
Resolved
06/15/2022
Phase 1 Exam room 1 & 2 & patient lav. OK TO DRYWALL PHASE 1 - Phase 2 Insurance 103 ok to cover -Seal all plate penetrations -Provide bocca plates at all dwv less than 1.25" to face of framing
Occupancy Inspection - Codes Commercial Failed 8/18/2022 8/18/2022 08/18/2022
Miscellaneous Correction
Corrective Action Required
08/18/2022
-Provide accessible restroom signage -Grab bar at back of toilet to be max 6" off of wall to min. 42" to end of bar -Provide address at back door -Mount fire extinguishers -Provide GFCI within 6' of sink in exam room 1
Occupancy Inspection - Fire Passed 8/18/2022 8/18/2022 08/18/2022
Corrective Action Required
08/18/2022
All life safety was appropriate. Okay to occupy with approval form codes.
Occupancy Inspection - Codes Commercial Failed 8/26/2022 8/26/2022 08/26/2022
Miscellaneous Correction
Corrective Action Required
08/18/2022
-Grab bar at back of toilet to be max 6" off of wall to min. 42" to end of bar-SEE 604.5.2 OF 2017 A117.1
Occupancy Inspection - Codes Commercial Full C of O 9/1/2022 9/1/2022 09/01/2022
Miscellaneous Correction
Resolved
09/01/2022
-Grab bar at back of toilet to be max 6" off of wall to min. 42" to end of bar-SEE 604.5.2 OF 2017 A117.1
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home

*PLEASE NOTE - You must be logged in with your registered user account to view any documents related to your permit