Permit Application Status

PRCOM20220280


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20220280
Building Permit - Commercial
Final Completion
SUMMIT WOODS SPE LLC
ALTERATION COMMERCIAL
Owner RED Dev work for separation of existing space into 2 separate spaces.
01/21/2022
02/18/2022
06/15/2022
Locations
Contacts
SUMMIT WOODS SPE LLC, Address:1 E WASHINGTON ST STE 300  
RED DEVELOPMENT LLC, Address:7500 COLLEGE BLVD, STE 750, Phone:(913) 214-4603  
CAMM CONSTRUCTION INC, Address:4006 E 137TH TERR, Phone:(816) 607-3602  
CADSTONE STUDIO ARCHITECTURE, Address:1213 W 32ND ST, Phone:(816) 550-0130  
cody@cammconstructioninc.com, Address:cody@cammconstructioninc.com, Phone:(816) 317-5021  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 04/22/2022
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
04/22/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received 4/121/2022.
Installation acceptance testing
Corrective Action Required
04/22/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. A visual inspection will be completed at occupancy. The existing system shall have documentation of a current annual inspection.
Licensed Contractors Approved 02/02/2022 02/18/2022
Joe Frogge
LC - General Contractor
Corrective Action Required
01/31/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
01/31/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved with Conditions 02/02/2022 01/31/2022
Joe Frogge
ICC A117.1 604.5.1 Fixed side wall grab bars
Corrective Action Required
01/31/2022

ICC A117.1 604.5.1 Fixed side wall grab bars. Fixed side-wall grab bars shall include a horizontal bar complying with Section 604.5.1.1 and a vertical grab bar complying with Section 604.5.12. The vertical grab bar at water closets primarily for children’s use shall comply with Section 609.4.2. ICC A117.1 604.5.1.1 Horizontal grab bar. A horizontal grab bar 42 inches minimum in length shall be located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. ICC A117.1 604.5.1.2 Vertical grab bar. A vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Action required: Comment is for informational purposes. Section at standard details does not show a vertical side grab bar at water closet. Given that there are no restroom modifications to this project plans are not rejected.
Fire Plan Review Approved with Conditions 02/02/2022 01/28/2022
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
01/27/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required- Provide plans for any modification to alarm notification and initiarting appliances.
Address numbers required
Corrective Action Required
01/27/2022

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action reguired- Adjust door numbering Address) . Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
01/27/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Submit plans for sprinkler modification to the spaces to maintain coverage.
Alarm testing.
Corrective Action Required
01/27/2022

2018 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation. Call (816) 969-1300 to schedule testing, preferably before regular business hours.
Portable fire extinguishers - general
Corrective Action Required
01/27/2022

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required- Provide a minimum of one 2A:10B:C fire extinguisher in each of the spaces. Verified at inspection.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Alteration to Commercial $440.00 $440.00 Paid 02/18/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 3/15/2022 3/15/2022 03/15/2022
Misc
Corrective Action Required
03/15/2022
PARTIAL METAL STUD DEMISING WALL A1 INCOMPLETE AT VESTIBULE & AT RTU IN MIDDLE OF WALL
In-wall Inspection Partial 4/6/2022 04/06/2022
Misc
Corrective Action Required
03/15/2022
PARTIAL METAL STUD DEMISING WALL A1
Rated Assembly Inspection Partial 4/6/2022 04/06/2022
Misc
Corrective Action Required
04/06/2022
PARTIAL PASS SCREW PATTERN APPROVED FOR TAPE DIMISING WALL REPAIR DRYWALL CUT 18" FROM FLOOR REPAIR DRYWALL AT DOOR OPENING PASSING THROUGH NEAR RESTROOMS FIRE CAULK ALL PENETRATIONS & ROOF DECK
Rated Assembly Inspection Failed 4/26/2022 4/26/2022 04/26/2022
Misc
Corrective Action Required
04/06/2022
PARTIAL PASS SCREW PATTERN APPROVED FOR TAPE DIMISING WALL REPAIR DRYWALL AT DOOR OPENING PASSING THROUGH NEAR RESTROOMS FIRE TAPE SEAMS NEAR FRONT ENTRY PROVIDE CORRECT ADDRESS COMPLETE SPRINKLER & ALARM TEST
Rated Assembly Inspection Passed 5/19/2022 5/18/2022 05/18/2022
Misc
Corrective Action Required
04/26/2022
SCREW PATTERN APPROVED FOR TAPE DIMISING WALL APPROVED SCREW PATTERN AT DOOR OPENING APPROVED
Alarm Test Passed 6/7/2022 06/07/2022
In-wall Inspection Passed 06/15/2022
Misc
Corrective Action Required
04/06/2022
METAL STUD DEMISING WALL A1
Final Inspection - Commercial Passed 6/15/2022 6/15/2022 06/15/2022
Misc
Informational
06/15/2022
White box unit is now addressed as 1750
Documents & Images
Date Uploaded File Type Document Name
01/21/2022 Application Form 1752 NW Chipman Road - Commercial Permit Application
01/21/2022 Plans swc Lenscrafters Permit 011922
01/27/2022 Letter Fire Building Plan Review
01/28/2022 Letter Fire Building Plan Review
01/31/2022 Approved Plans approved - swc Lenscrafters Permit 011922
02/18/2022 Receipt Receipt for transaction:2022-000894
02/18/2022 Letter DS Building Permit
03/15/2022 Letter INSPECTION SUMMARY
04/06/2022 Letter INSPECTION SUMMARY
04/06/2022 Letter INSPECTION SUMMARY
04/22/2022 Letter Fire (Sprinkler) Plan Review
04/26/2022 Letter INSPECTION SUMMARY
04/26/2022 Letter INSPECTION SUMMARY
05/18/2022 Letter INSPECTION SUMMARY
06/07/2022 Letter Fire Loss Reduction Form
06/15/2022 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home