Permit Application Status

PRCOM20215974


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20215974
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
INTERIOR ALTERATIONS TO EMERGENCY ROOM AREA - RENOVATING/REMOVING EXISTING OFFICES TO CREATE OFFICE AND CT ROOM
11/16/2021
01/04/2022
05/22/2022
08/02/2022
Locations
Contacts
MCCOWN GORDON CONSTRUCTION LLC, Address:850 MAIN ST, Phone:(816) 960-1111  
TYLER STOTLER, Address:MCCOWN GORDON, Phone:(816) 518-0622  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
ACI BOLAND ARCHITECTS, Address:1710 WYANDOTTE ST, Phone:(816) 595-9513  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
gforsee@mccowngordon.com, Address:gforsee@mccowngordon.com  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 02/17/2022
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
02/17/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received February 14, 2022.
Installation acceptance testing
Corrective Action Required
02/17/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. A visual inspection will be completed at the final occupancy inspection.
Licensed Contractors Approved 12/03/2021 01/04/2022
Joe Frogge
LC - MEP Subs
Resolved
01/04/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
LC - General Contractor
Resolved
11/29/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved 12/03/2021 11/29/2021
Joe Frogge
Suite address
Resolved
11/29/2021

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: The address for this section of hospital is 80 NE Saint Lukes Blvd. Please update your records.
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Resolved
11/29/2021

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle within 25' of new roof mounted condensing unit or provide verification of existing.
NEC Article 210.8 (B) Other than dwelling units GFCI
Resolved
11/29/2021

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
Fire Plan Review Approved with Conditions 12/03/2021 11/29/2021
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
11/24/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Construction documents - Fire protection systems
Corrective Action Required
11/24/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
11/24/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Building Plan Review Rejected 11/30/2021 11/23/2021
Joe Frogge
Suite address
Corrective Action Required
11/23/2021

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: The address for this section of hospital is 80 NE Saint Lukes Blvd. Please update your records.
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
11/23/2021

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle within 25' of new roof mounted condensing unit or provide verification of existing.
NEC Article 210.8 (B) Other than dwelling units GFCI
Corrective Action Required
11/23/2021

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
Licensed Contractors Rejected 11/30/2021 11/23/2021
Joe Frogge
LC - MEP Subs
Corrective Action Required
11/23/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact which is where inspection reports will be sent.
Fire Plan Review Approved with Conditions 11/30/2021 11/17/2021
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
11/17/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Construction documents - Fire protection systems
Corrective Action Required
11/17/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
11/17/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $1,200.00 $1,200.00 Paid 01/04/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 3/17/2022 3/17/2022 03/17/2022
Misc
Informational
03/17/2022
Offices 1B053B, 1B053D, 1B053E, 1B053F and Corridor 1B060 - OK
Above Ceiling Inspection Partial 4/19/2022 4/19/2022 04/19/2022
Misc
Informational
04/19/2022
Offices 18053B, 1B053D, 1B053E, 1B053F and Corridor 18060 -APPROVED
Occupancy Inspection - Codes Commercial Failed 4/26/2022 4/26/2022 04/26/2022
Misc
Corrective Action Required
04/26/2022
THE FOLLOWING AREAS APPROVED BY CODES AND FIRE FOR OCCUPANCY: -OFFICES1B053B, 1B053D, 1B053E, 1B053F AND CORRIDOR 1B060
Underslab Electrical Inspection - Commercial Partial 5/4/2022 5/4/2022 05/04/2022
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
05/04/2022
- 5/4/22 CT 1B016 -
Underslab Plumbing Inspection - Commercial Partial 5/4/2022 5/4/2022 05/04/2022
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
05/04/2022
- 5/4/22 CT 1B016 -
In-wall Inspection Passed 5/27/2022 5/27/2022 05/27/2022
Misc
Informational
03/17/2022
Offices 1B053B, 1B053D, 1B053E, 1B053F and Corridor 1B060 - OK Rad supervisor 1B017, CT Control room 1B016A, CT 1B016- OK
Above Ceiling Inspection Partial 7/20/2022 7/20/2022 07/20/2022
Misc
Informational
04/19/2022
Offices 18053B, 1B053D, 1B053E, 1B053F and Corridor 18060, CT RM 02-1B016 -APPROVED
Rated Assembly Inspection Passed 8/2/2022 08/02/2022
Above Ceiling Inspection Passed 8/2/2022 08/02/2022
Misc
Informational
07/20/2022
Offices 18053B, 1B053D, 1B053E, 1B053F and Corridor 18060, CT RM 02-1B016 -APPROVED
Occupancy Inspection - Codes Commercial Full C of O 8/2/2022 8/2/2022 08/02/2022
Misc
Resolved
08/02/2022
THE FOLLOWING AREAS APPROVED BY CODES AND FIRE FOR OCCUPANCY: -OFFICES1B053B, 1B053D, 1B053E, 1B053F AND CORRIDOR 1B060
Alarm Test Passed 8/2/2022 08/02/2022
Occupancy Inspection - Fire Passed 8/2/2022 8/2/2022 08/02/2022
Documents & Images
Date Uploaded File Type Document Name
11/16/2021 Application Form Comm Permit Application - CT 21-1112
11/16/2021 Plans SLE CT Permit set 21-1116
11/17/2021 Letter Fire Building Plan Review
11/23/2021 Letter DS P/R Corrections Document
11/24/2021 Letter 3-21024-City-Code_Review Response_CT 21-1129
11/24/2021 Drawing A0-1-1 - COVER SHEET
11/24/2021 Drawing ME202-1 - ROOF - PIPING-ELECTRICAL
11/29/2021 Letter Fire Building Plan Review
11/29/2021 Approved Plans approved - SLE CT Permit set 21-1116
01/04/2022 Receipt Receipt for transaction:2022-000032
01/07/2022 Letter DS Building Permit
02/17/2022 Letter Fire (Sprinkler) Plan Review
02/17/2022 Letter Fire (Sprinkler) Plan Review
03/17/2022 Letter INSPECTION SUMMARY
04/19/2022 Letter INSPECTION SUMMARY
04/26/2022 Letter INSPECTION SUMMARY
05/04/2022 Letter INSPECTION SUMMARY
05/04/2022 Letter INSPECTION SUMMARY
05/27/2022 Letter INSPECTION SUMMARY
07/20/2022 Letter INSPECTION SUMMARY
08/02/2022 Letter INSPECTION SUMMARY
08/02/2022 Letter INSPECTION SUMMARY
08/02/2022 Letter Field Certificate of Occupancy
08/02/2022 Letter Codes Final Certificate of Occupancy
08/02/2022 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home