Permit Application Status

PRCOM20215365


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20215365
Building Permit - Commercial
Certificate of Occupancy
PREMIERLIFE REAL ESTATE HOLDING
CHANGE OF TENANT
TENANT FINISH FOR UROLOGY AND ONCOLOGY CLINIC - INCLUDES NEW EXTERIOR ENTRY WITH RETAINING WALL
10/13/2021
11/11/2021
04/26/2022
04/18/2022
Locations
Contacts
JAYGER CONSTRUCTION, Address:15010 W 106TH ST, Phone:(913) 951-3699  
Brian@JaygerLLC.com, Address:Brian@JaygerLLC.com  
BCI MECHANICAL INC, Address:P O BOX 441, Phone:(913) 856-6747  
QUESTEC MECHANICAL INC, Address:1390 E BOONE INDUSTRIAL DR, SUITE 260, Phone:(573) 875-0260  
NOLTE & ASSOCIATES, Address:9400 REEDS RD, Phone:(913) 922-2444  
PREMIERLIFE REAL ESTATE HOLDING, Address:400 NW MURRAY RD  
BCI Electrical, Inc, Address:PO Box 546  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 03/14/2022 03/14/2022
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
03/14/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Received 3/142022
Installation acceptance testing
Corrective Action Required
03/14/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Test scheduled.
Alarm Plan Review Released for Construction 03/14/2022 03/14/2022
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
03/14/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Installation acceptance testing
Corrective Action Required
03/14/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule a test.
Sprinkler Plan Review Released for Construction 12/16/2021 12/16/2021
Michael Weissenbach
Licensed Contractors Approved 11/03/2021 11/01/2021
Joe Frogge
LC - General Contractor
Resolved
10/27/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact.
LC - MEP Subs
Resolved
11/01/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/27/21 - BCI does not have a license as an electrical contractor
Building Plan Review Approved 11/03/2021 10/28/2021
Joe Frogge
IBC 602.1 Type of Construction - general
Resolved
10/27/2021

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Building type is 5B. Update Code Data Chart.
ICC A117.1 604.3.1 Water closet width
Resolved
10/27/2021

ICC A117.1 Section 604.3.1 Clearance Width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. Action required: Provide minimum 60" behind all water closets. Staff WC 116 not compliant as shown. (This room also needs turning space)
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Resolved
10/28/2021

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" clearance at latch side of doors. 10/27/28 - Most doors still not compliant. See ICC/ANSI Fig. 404.2.3.2 - detail (a) for front approach, pull side. (agreed that door in non-accessible restroom meets exception)
Misc
Resolved
10/28/2021

Retaining walls 48" and taller are required to have complete engineered design. Action required: Provide complete design for retaining wall or request deferral. Per local ordinance retaining wall height is measured from bottom of footing to top of wall. (section 7-128, Item A/1)
IBC 1209.2 Finish materials
Resolved
10/28/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish materials at walls adjacent to water closets. If paint is used it must be epoxy based. 10/27/21 - walls next to water closets still have PT-1 designation.
Miscellaneous Correction
Resolved
10/27/2021

Clarification required. What walls are fire rated (and why)? Demo plan doesn't match new work at mechanical room. Doors 120 & 120A may be backwards in schedule? How is Mech Room 120 to be used? Action required: Clarify.
Fire Plan Review Approved with Conditions 11/03/2021 10/28/2021
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
10/27/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Hazardous material identification
Corrective Action Required
10/27/2021

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5. (Verified At Inspection)
Address numbers required
Corrective Action Required
10/27/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
10/27/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
10/27/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Building Plan Review Rejected 10/25/2021 10/20/2021
Joe Frogge
IBC 602.1 Type of Construction - general
Corrective Action Required
10/20/2021

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Building type is 5B. Update Code Data Chart.
ICC A117.1 604.3.1 Water closet width
Corrective Action Required
10/20/2021

ICC A117.1 Section 604.3.1 Clearance Width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. Action required: Provide minimum 60" behind all water closets. Staff WC 116 not compliant as shown. (This room also needs turning space)
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Corrective Action Required
10/20/2021

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" clearance at latch side of doors.
Misc
Corrective Action Required
10/20/2021

Retaining walls 48" and taller are required to have complete engineered design. Action required: Provide complete design for retaining wall or request deferral.
IBC 1209.2 Finish materials
Corrective Action Required
10/20/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish materials at walls adjacent to water closets. If paint is used it must be epoxy based.
Miscellaneous Correction
Corrective Action Required
10/20/2021

Clarification required. What walls are fire rated (and why)? Demo plan doesn't match new work at mechanical room. Doors 120 & 120A may be backwards in schedule? How is Mech Room 120 to be used? Action required: Clarify.
Licensed Contractors Rejected 10/25/2021 10/20/2021
Joe Frogge
LC - General Contractor
Corrective Action Required
10/20/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact.
LC - MEP Subs
Corrective Action Required
10/20/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 10/25/2021 10/14/2021
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
10/14/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Hazardous material identification
Corrective Action Required
10/14/2021

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5. (Verified At Inspection)
Address numbers required
Corrective Action Required
10/14/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
10/14/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
10/14/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $2,000.00 $2,000.00 Paid 11/01/2021
$17,325.00
8331507-Sewer Connection Fee $720.00 $720.00 Paid 11/01/2021
Commercial Excise Tax Fee $9,180.00 $9,180.00 Paid 11/01/2021
$8,662.50
Not Ready Inspection Fee $50.00 $50.00 Paid 03/16/2022
Not Ready Inspection Fee $50.00 $50.00 Paid 03/16/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 12/2/2021 12/02/2021
In-wall Inspection Partial 12/29/2021 12/29/2021
Misc
Informational
12/29/2021
: THE FOLLOWING AREAS ARE APPROVED : ALL AREAS EXCEPT BREAKROOM/KITCHEN/STAFF
Gas Service Inspection - Commercial Passed 1/28/2022 1/28/2022 01/28/2022
Above Ceiling Inspection Passed 2/14/2022 2/14/2022 02/14/2022
In-wall Inspection Passed 2/14/2022 03/02/2022
Misc
Informational
12/29/2021
Rated Assembly Inspection Passed 2/14/2022 03/02/2022
Occupancy Inspection - Codes Commercial Not Ready 3/2/2022 3/2/2022 03/02/2022
Electrical Service Inspection Passed 3/10/2022 3/10/2022 03/10/2022
Alarm Test Passed 3/15/2022 03/15/2022
Occupancy Inspection - Fire Passed 3/2/2022 3/15/2022 03/15/2022
Occupancy Inspection - Codes Commercial Failed 3/15/2022 3/15/2022 03/15/2022
Misc
Corrective Action Required
03/15/2022
Pay not ready fees Exam B cover plate receptacle under window Provide GFCI protection dishwasher break room Secure switch & provide cover plate outside mechanical room Service panel covers with doors Provide GFCI protection at mop sink ( soiled lab) Provide anti siphon device at mop sink Provide GFCI protection south side Lab 2 Provide guardrail at retaining wall : OK TO STOCK & TRAIN :
Retaining Wall Inspection Passed 3/16/2022 03/16/2022
Occupancy Inspection - Codes Commercial Temporary C of O 3/16/2022 3/16/2022 03/16/2022
Misc
Corrective Action Required
03/15/2022
Pay not ready fees Provide guardrail at retaining wall Remove spoil pile near retaining wall : TCO EXPIRES 4/15/20222 :
Occupancy Inspection - Codes Commercial Full C of O 4/18/2022 4/18/2022 04/18/2022
Misc
Resolved
04/18/2022
Documents & Images
Date Uploaded File Type Document Name
10/13/2021 Application Form LS Commercial Permit Application SIGNED
10/13/2021 Plans KCUC LEE'S SUMMIT ALL DRAWINGS IN ORDER
10/13/2021 Application Form Lees Summit Excise Tax for Streets License Tax Application Signed2
10/14/2021 Letter Fire Building Plan Review
10/20/2021 Letter DS P/R Corrections Document
10/27/2021 Letter City Comments Response 10-27-2021
10/27/2021 Plans KCUC REVISED PLANS 10-27-2021
10/28/2021 Letter Fire Building Plan Review
10/28/2021 Letter DS P/R Corrections Document
10/28/2021 Letter Response to City Comments - Fire Dept 10-28-2021
10/28/2021 Drawing 2021027 A-101 FLOOR PLAN
10/28/2021 Drawing 2021027 A-401 INT ELEVS
10/28/2021 Plans ALL DRAWINGS IN ORDER COMBO
11/01/2021 Approved Plans approved - ALL DRAWINGS IN ORDER COMBO
11/01/2021 Letter License Tax Bill
11/01/2021 Receipt Receipt for transaction:2021-008408
11/11/2021 Letter DS Building Permit
11/11/2021 Scan_0932
12/02/2021 Letter INSPECTION SUMMARY
12/16/2021 Letter Fire (Sprinkler) Plan Review
12/29/2021 Letter INSPECTION SUMMARY
01/28/2022 Letter INSPECTION SUMMARY
02/14/2022 Letter INSPECTION SUMMARY
03/02/2022 Letter INSPECTION SUMMARY
03/02/2022 Letter INSPECTION SUMMARY
03/02/2022 Letter INSPECTION SUMMARY
03/10/2022 Letter INSPECTION SUMMARY
03/14/2022 Fire Alarm Plan - 22-1054L Phase 22-05 KCUC
03/14/2022 Letter Fire (Alarm) Plan Review Notice
03/15/2022 Letter INSPECTION SUMMARY
03/16/2022 Receipt Receipt for transaction:2022-001423
03/16/2022 Letter Fire (Alarm) Plan Review Notice
03/16/2022 Letter Codes Temporary Certificate of Occupancy
03/16/2022 Letter Codes Temporary Certificate of Occupancy
03/16/2022 Letter INSPECTION SUMMARY
04/18/2022 Letter Codes Final Certificate of Occupancy
04/18/2022 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home