Permit Application Status

PRCOM20203989


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20203989
Building Permit - Commercial
Certificate of Occupancy
HALLBUSTER SUMMIT LLC
CHANGE OF TENANT
TENANT FINISH FOR OPTOMETRIST WITH SOME RETAIL
10/28/2020
12/11/2020
04/26/2021
02/01/2021
Locations
Contacts
CALIBER 1 CONSTRUCTION, INC., Address:110 W. MONTGOMERY ST., Phone:(770) 212-2190  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
PRO DESIGN CONTRACTORS LLC, Address:918 E WARREN ST, Phone:(913) 308-6900  
Caroline Ma, Architect, Address:1720 Dale Ford Rd, Phone:(740) 919-9184  
ewilson@caliber1construction.com, Address:ewilson@caliber1construction.com  
HALLBUSTER SUMMIT LLC, Address:605 W 47TH ST STE 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 11/05/2020 12/11/2020
Joe Frogge
LC - General Contractor
Resolved
12/04/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. Also provide email address for on-site contact 10/29/20 - Acknowledged in letter.
LC - MEP Subs
Resolved
12/11/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/29/20 - Acknowledged in letter.
Building Plan Review Approved 11/05/2020 12/04/2020
Joe Frogge
Misc
Resolved
12/04/2020

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 10/29/20 - Acknowledged in letter.
IBC 706.1 Fire and Smoke Protection - General
Resolved
10/29/2020

2018 IBC 706.1 General. Fire walls shall be constructed in accordance with Sections 706.2 through 706.11. The extent and location of such fire walls shall provide a complete separation. Where a fire wall also separates occupancies that are required to be separated by a fire barrier wall, the most restrictive requirements of each separation shall apply. Action required: Provide complete construction details for fire rated partition including nail/screw patterns. (fyi - this wall is not required to be rated)
IMC 606.2.1 Duct detector
Resolved
10/29/2020

2018 IMC 606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm, in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances. Exception: Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. The area smoke detection system shall comply with Section 606.4. Action required: Provide smoke detector in RTU-2 return air.
Fire Plan Review Approved with Conditions 11/05/2020 10/29/2020
Michael Weissenbach
Address numbers required
Corrective Action Required
10/29/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Miscellaneous Correction
Resolved
10/29/2020

(Verified At Inspection) 1. Remove exit sign in retail area leading occupants to the hall(117) 2. Remove exit sign in hall(117) outside of the lab leading to the retail area.
Building Plan Review Rejected 11/09/2020 10/28/2020
Joe Frogge
Misc
Corrective Action Required
10/28/2020

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
IBC 706.1 Fire and Smoke Protection - General
Corrective Action Required
10/28/2020

2018 IBC 706.1 General. Fire walls shall be constructed in accordance with Sections 706.2 through 706.11. The extent and location of such fire walls shall provide a complete separation. Where a fire wall also separates occupancies that are required to be separated by a fire barrier wall, the most restrictive requirements of each separation shall apply. Action required: Provide complete construction details for fire rated partition including nail/screw patterns. (fyi - this wall is not required to be rated)
IMC 606.2.1 Duct detector
Corrective Action Required
10/28/2020

2018 IMC 606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm, in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances. Exception: Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. The area smoke detection system shall comply with Section 606.4. Action required: Provide smoke detector in RTU-2 return air.
Licensed Contractors Rejected 11/09/2020 10/28/2020
Joe Frogge
LC - General Contractor
Corrective Action Required
10/28/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. Also provide email address for on-site contact
LC - MEP Subs
Corrective Action Required
10/28/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 11/09/2020 10/28/2020
Michael Weissenbach
Address numbers required
Corrective Action Required
10/28/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Miscellaneous Correction
Corrective Action Required
10/28/2020

(Verified At Inspection) 1. Remove exit sign in retail area leading occupants to the hall(117) 2. Remove exit sign in hall(117) outside of the lab leading to the retail area.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $1,280.00 $1,280.00 Paid 12/11/2020
$0.00
8331507-Sewer Connection Fee $270.00 $270.00 Paid 12/11/2020
7232302-Commercial License Tax Fee $5,595.00 $5,595.00 Paid 12/11/2020
$5,280.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 12/17/2020 12/17/2020 12/17/2020
In-wall Inspection Partial 12/23/2020 12/23/2020 12/23/2020
Misc
Informational
12/23/2020
In-wall Inspection Failed 12/28/2020 12/28/2020 12/28/2020
Miscellaneous Correction
Corrective Action Required
12/28/2020
-SUPPORT VERTICAL CONDUIT PER CODE -MIDPOINT STRAP ON ALL DWV 2” AND SMALLER
Miscellaneous Correction
Corrective Action Required
12/28/2020
-SUPPORT VERTICAL CONDUIT PER CODE -MIDPOINT STRAP ON ALL DWV 2” AND SMALLER
Rough Electrical Inspection - Commercial Partial 12/29/2020 12/29/2020 12/29/2020
In-wall Inspection Passed 12/29/2020 12/29/2020 12/29/2020
Miscellaneous Correction
Corrective Action Required
12/28/2020
-SUPPORT VERTICAL CONDUIT PER CODE -MIDPOINT STRAP ON ALL DWV 2” AND SMALLER
Miscellaneous Correction
Corrective Action Required
12/28/2020
-SUPPORT VERTICAL CONDUIT PER CODE -MIDPOINT STRAP ON ALL DWV 2” AND SMALLER
Gas Piping Inspection - Commercial Passed 12/29/2020 12/29/2020
Gas Service Inspection - Commercial Passed 12/29/2020 12/29/2020
Underslab Electrical Inspection - Commercial Passed 1/11/2021 1/11/2021 01/11/2021
Misc
Informational
01/11/2021
- UNDERSLAB CONDUIT FOR FLOOR OUTLETS -
Rough Electrical Inspection - Commercial Failed 1/19/2021 1/19/2021 01/19/2021
Misc
Corrective Action Required
01/19/2021
- PROVIDE CITY STAMPED REVISION OF ENGINEERS DRAWINGS -
Rough Electrical Inspection - Commercial Passed 1/21/2021 1/20/2021 01/20/2021
Misc
Resolved
01/20/2021
Above Ceiling Inspection Passed 1/20/2021 1/20/2021 01/20/2021
Electrical Service Inspection Passed 1/20/2021 01/20/2021
Final Electrical Inspection - Commercial Passed 1/29/2021 01/29/2021
Final Mechanical Inspection Passed 1/29/2021 01/29/2021
Final Plumbing Inspection - Commercial Passed 1/29/2021 01/29/2021
Rough Plumbing Inspection - Commercial Passed 12/29/2020 01/29/2021
Occupancy Inspection - Fire Passed 1/29/2021 1/29/2021 01/29/2021
Occupancy Inspection - Codes Commercial Full C of O 1/29/2021 1/29/2021 02/01/2021
Documents & Images
Date Uploaded File Type Document Name
10/28/2020 Application Form Signed--Comm Permit Application-Eyemart
10/28/2020 Plans Eyemart Dwgs-LSMO
10/28/2020 Engineer Report/Study Eyemart-Struct Letter-Cals-LSMO
10/28/2020 Letter Fire Building Plan Review
10/28/2020 Letter DS P/R Corrections Document
10/29/2020 Letter Response-REV01-Eyemart-LSMO
10/29/2020 Drawing REV01-Eyemart Dwg-LSMO
10/29/2020 Letter Fire Building Plan Review
10/29/2020 Approved Plans approved - Eyemart Dwgs-LSMO
12/04/2020 Application Form License Tax Affidavit
12/11/2020 Letter License Tax Bill
12/11/2020 Receipt Receipt for transaction:2020-007981
12/11/2020 Letter Codes Plan Review Conditions
12/11/2020 Letter DS Building Permit
12/17/2020 Letter INSPECTION SUMMARY
12/23/2020 Letter INSPECTION SUMMARY
12/28/2020 Letter INSPECTION SUMMARY
12/29/2020 Letter INSPECTION SUMMARY
12/29/2020 Letter INSPECTION SUMMARY
12/29/2020 Letter INSPECTION SUMMARY
12/29/2020 Letter INSPECTION SUMMARY
01/11/2021 Letter INSPECTION SUMMARY
01/19/2021 Drawing Eyemart LS Riser Diagram
01/19/2021 Letter INSPECTION SUMMARY
01/19/2021 Drawing 23_E4-1_R3
01/20/2021 Approved Plans APPROVED - 23_E4-1_R3
01/20/2021 Letter INSPECTION SUMMARY
01/20/2021 Letter INSPECTION SUMMARY
01/20/2021 Letter INSPECTION SUMMARY
01/29/2021 Letter INSPECTION SUMMARY
01/29/2021 Letter INSPECTION SUMMARY
01/29/2021 Letter INSPECTION SUMMARY
02/01/2021 Letter INSPECTION SUMMARY
02/01/2021 Letter Field Certificate of Occupancy
02/01/2021 Letter Codes Final Certificate of Occupancy
02/01/2021 Letter INSPECTION SUMMARY
02/01/2021 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home