Permit Application Status

PRCOM20203667


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20203667
Building Permit - Commercial
Voided
SAINT LUKES EAST HOSPITAL
NEW TENANT FINISH
SAINT LUKE'S EAST 9-ROOM TENANT FINISH WITH NURSE STATION AND SUPPORTING ROOMS 11/6/2020 - jdf - this permit has been moved/merged with PRCOM20200845
10/12/2020
11/06/2020
Locations
Contacts
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
ACI BOLAND ARCHITECTS, Address:1710 WYANDOTTE ST, Phone:(816) 595-9513  
ACI BOLAND ARCHITECTS, Address:1710 WYANDOTTE ST, Phone:(816) 595-9513  
ADECK@ACIBOLAND.COM  
  
  
  
  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Rejected 10/22/2020 10/19/2020
Joe Frogge
Building Plan Review Approved 10/22/2020 10/16/2020
Tracy Deister
Zoning Review Approved 10/22/2020 10/14/2020
Mike Weisenborn
Fire Plan Review Approved with Conditions 10/26/2020 10/13/2020
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
10/13/2020

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Informational Purposes) Provide PE stamped electronic shop drawings for the fire alarm sytem to mike.weissenbach@cityofls.net
Hazardous material identification
Corrective Action Required
10/13/2020

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
10/13/2020

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Informational Purposes) Provide PE stamped electronic shop drawings for the fire sprinkler system to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
10/13/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Duct smoke detectors
Corrective Action Required
10/13/2020

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Action Required) Duct detection required with CFM above 2000.
Inspections

There are no inspections for this permit application.

Documents & Images
Date Uploaded File Type Document Name
10/12/2020 Application Form Comm Permit Application - SLE 9 room addition
10/12/2020 Plans SLE Flex Capacity Expansion Phase II
10/13/2020 Letter Fire Building Plan Review
10/16/2020 Approved Plans SLE Flex Capacity Expansion Phase II Approved Plans
10/19/2020 Letter License Tax Not Applicable
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home