Summary
PRCOM20202943
Building Permit - Commercial
Certificate of Occupancy
DACUR INVESTMENT COMPANY INC
CHANGE OF TENANT
TENANT FINISH FOR HEARING AID CONSULTING AND TESTING
09/11/2020
09/30/2020
03/13/2021
11/03/2020
Locations
Contacts
ZIPCO CONTRACTING INC, Address:4110 N CORRINGTON AVE, Phone:(816) 471-3797  
MORSE ELECTRIC, Address:815 NORTH ST, Phone:(816) 785-2385  
SCHARHAG ARCHITECTS, Address:6247 BROOKSIDE BLVD STE 204, Phone:(816) 656-5055  
kevin.fountain@zipcocontracting.com, Address:kevin.fountain@zipcocontracting.com  
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 09/23/2020 09/30/2020
Joe Frogge
LC - MEP Subs
Resolved
09/30/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed Electrical and Mechanical contractors. (Mechanical Contractor required to relocate diffusers and ensure that new rooms have supply and return air.) 9/16/20 - acknowledged in letter
LC - General Contractor
Resolved
09/30/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 9/16/20 - acknowledged in letter
Building Plan Review Approved with Conditions 09/23/2020 09/16/2020
Joe Frogge
Miscellaneous Correction
Corrective Action Required
09/16/2020

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 9/16/20 - acknowledged in letter
IBC 1109.12.9 Point of sale and service counters - accessibility
Resolved
09/16/2020

2018 IBC 1109.12.3 Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: At least 36" of reception counter to be maximum 36" tall. (can be verified during inspections)
NEC Article 517.13 Grounding of receptacles patient care
Resolved
09/16/2020

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system.
IBC 2902.3 Employee and public toilet facilities - access to public toilet
Corrective Action Required
09/16/2020

2018 IBC 2902.3 Employee and public toilet facilities. For structures and tenant spaces intended for public utilization, customers, patrons and visitors shall be provided with public toilet facilities. Employees associated with structures and tenant spaces shall be provided with toilet facilities. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 2902 for all users. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Exception: Public toilet facilities shall not be required for: 1. Parking garages where operated without parking attendants. 2. Structures and tenant spaces intended for quick transactions, including takeout, pickup and drop-off, having a public access area less than or equal to 300 square feet. Action required: Comment is for informational purposes. Restroom must remain accessible to patrons. Work Room must not be used for storage. 9/16/20 - acknowledged in letter
Fire Plan Review Approved 09/23/2020 09/16/2020
Michael Weissenbach
Address numbers required
Resolved
09/16/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address front and back exterior doors
Portable fire extinguishers - conspicuous locations
Resolved
09/16/2020

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC Fire Extinguisher
Building Plan Review Rejected 09/23/2020 09/14/2020
Joe Frogge
Miscellaneous Correction
Corrective Action Required
09/14/2020

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
IBC 1109.12.9 Point of sale and service counters - accessibility
Corrective Action Required
09/14/2020

2018 IBC 1109.12.3 Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: At least 36" of reception counter to be maximum 36" tall. (can be verified during inspections)
NEC Article 517.13 Grounding of receptacles patient care
Corrective Action Required
09/14/2020

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system.
IBC 2902.3 Employee and public toilet facilities - access to public toilet
Corrective Action Required
09/14/2020

2018 IBC 2902.3 Employee and public toilet facilities. For structures and tenant spaces intended for public utilization, customers, patrons and visitors shall be provided with public toilet facilities. Employees associated with structures and tenant spaces shall be provided with toilet facilities. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 2902 for all users. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Exception: Public toilet facilities shall not be required for: 1. Parking garages where operated without parking attendants. 2. Structures and tenant spaces intended for quick transactions, including takeout, pickup and drop-off, having a public access area less than or equal to 300 square feet. Action required: Comment is for informational purposes. Restroom must remain accessible to patrons. Work Room must not be used for storage.
Licensed Contractors Rejected 09/23/2020 09/14/2020
Joe Frogge
LC - MEP Subs
Corrective Action Required
09/14/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed Electrical and Mechanical contractors. (Mechanical Contractor required to relocate diffusers and ensure that new rooms have supply and return air.)
LC - General Contractor
Corrective Action Required
09/14/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
Fire Plan Review Approved with Conditions 09/11/2020
Michael Weissenbach
Address numbers required
Corrective Action Required
09/11/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address front and back exterior doors
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/11/2020

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC Fire Extinguisher
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $120.00 $120.00 Paid 09/30/2020
7232302-Commercial License Tax Fee $3,832.50 $3,832.50 Paid 09/14/2020
$3,832.50
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Framing Inspection - Commercial Passed 10/15/2020 10/15/2020
Misc
Informational
10/15/2020
- METAL STUD FRAMING FOR EXAM ROOMS -
In-wall Inspection Passed 10/15/2020 10/15/2020 10/15/2020
Misc
Informational
10/15/2020
- ELECTRICAL IN EXAM ROOM- - HVAC & PLUMBING EXISTING -
Occupancy Inspection - Fire Passed 10/29/2020 10/29/2020 10/29/2020
Above Ceiling Inspection Passed 10/15/2020 11/03/2020
Occupancy Inspection - Codes Commercial Failed 10/29/2020 10/29/2020 11/03/2020
Misc
Corrective Action Required
10/29/2020
- PIPE WATER HEATER RELIEF VALVE TO FLOOR - - REPAIR/ REPLACE EXIT SIGN LIGHT -
Occupancy Inspection - Codes Commercial Full C of O 11/3/2020 11/3/2020 11/03/2020
Misc
Resolved
11/03/2020
Documents & Images
Date Uploaded File Type Document Name
09/11/2020 Application Form Miracle Ear Permit Application
09/11/2020 Plans Miracle Ear 9.11.20 sealed
09/11/2020 Letter Fire Building Plan Review
09/14/2020 Letter DS P/R Corrections Document
09/16/2020 Plans Miracle Ear Plans rev 9_15_20 with seal
09/16/2020 Letter Miracle Ear Response Letter 9_15_20
09/16/2020 Letter Fire Building Plan Review
09/16/2020 Approved Plans approved - Miracle Ear Plans
09/30/2020 Receipt Receipt for transaction:2020-006598
09/30/2020 Letter DS Building Permit
10/15/2020 Letter INSPECTION SUMMARY
10/15/2020 Letter INSPECTION SUMMARY
10/29/2020 Letter INSPECTION SUMMARY
11/03/2020 Letter INSPECTION SUMMARY
11/03/2020 Letter Field Certificate of Occupancy
11/03/2020 Letter Codes Final Certificate of Occupancy
11/10/2020 Letter Codes Plan Review Conditions
11/10/2020 Letter INSPECTION SUMMARY
11/10/2020 Letter INSPECTION SUMMARY
11/10/2020 Letter Field Certificate of Occupancy
11/10/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents