Permit Application Status

PRCOM20201329


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20201329
Building Permit - Commercial
Voided
LEES SUMMIT SELF STORAGE LLC
NEW SHELL BUILDING
SHELL FOR FAST FOOD RESTAURANT WITH DRIVE-THRU voided per architect - 6/14/21 - jdf
05/21/2020
11/24/2020
05/23/2022
Locations
Contacts
  
  
  
  
SCHARHAG ARCHITECTS, Address:6247 BROOKSIDE BLVD STE 204, Phone:(816) 656-5055  
LEES SUMMIT SELF STORAGE LLC, Address:6651 LONGHORN DR  
STAR ACQUISITIONS & DEVELOPMENT LLC, Address:244 W MILL STE 101  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Rejected 06/05/2020 05/27/2020
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
05/27/2020

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide PE stamped electronic shop drawings for the fire alarm system. Send them to mike.weissenbach@cityofls.net
Knox box required
Corrective Action Required
05/27/2020

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. (Action Required) Order a Knox box at knoxbox.com. Placement to be made by FDC.
Construction documents - Fire protection systems
Corrective Action Required
05/27/2020

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide PE stamped electronic shop drawings for the fire sprinkler system. Send them to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
05/27/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Misc
Corrective Action Required
05/27/2020

(Action Required) Provide a plan with a hydrant within 100' of the FDC. Show the FDC on the building.
Duct smoke detectors
Corrective Action Required
05/27/2020

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Action Required) Provide duct detection with CFM over 2000.
Building Plan Review Rejected 06/05/2020 05/26/2020
Joe Frogge
Final Development Plan
Corrective Action Required
05/26/2020

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is for informational purposes.
Miscellaneous Correction
Corrective Action Required
05/26/2020

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Engineered truss package
Corrective Action Required
05/26/2020

Copies of the engineered truss package were not provided at the time of permit application. Action required: Truss package deferred per request. Must be reviewed and approved prior to inspections.
Misc
Corrective Action Required
05/26/2020

Rooftop Unit Mounting Detail #5 on Sheet MP002 has conflicting information. Action required: Modify detail to depict wood truss construction.
IMC 306.5 Equipment on roofs
Corrective Action Required
05/26/2020

2018 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide permanent access to roof.
IMC 606.2.1 Duct detector
Corrective Action Required
05/26/2020

2018 IMC 606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm, in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances. Exception: Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. The area smoke detection system shall comply with Section 606.4. Action required: Provide duct mounted smoke detection as required.
Licensed Contractors Rejected 06/05/2020 05/26/2020
Joe Frogge
LC - MEP Subs
Corrective Action Required
05/26/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
LC - General Contractor
Corrective Action Required
05/26/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
Inspections

There are no inspections for this permit application.

Documents & Images
Date Uploaded File Type Document Name
05/21/2020 Application Form Panera Bread Building Application Form
05/22/2020 Plans Panera Bread Building Complete Plan Set sealed 5.22.20
05/22/2020 Engineer Report/Study Panera Bread Structural Calcs 5.15.20
05/27/2020 Letter Fire Building Plan Review
05/28/2020 Letter DS P/R Corrections Document
11/19/2020 Engineer Report/Study Oakview Storage - Lee's Summit Final SI Report.docx
06/14/2021 Email Re Panera Bread - PRCOM20201329
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home