Summary
PRCOM20192982
Building Permit - Commercial
Final Completion
CITY OF LEES SUMMIT
PARTIAL COMMERCIAL
FOUNDATION AND UNDERSLAB PERMIT FOR NEW GROCERY STORE FULL PERMIT - PRCOM20192156
10/11/2019
10/17/2019
04/02/2020
Locations
Contacts
CRANE CONSTRUCTION COMPANY, Address:PO BOX 298, Phone:(816) 324-5951  
APPLE ELECTRIC INTEGRATED SOLUTIONS INC, Address:PO BOX 998, Phone:(913) 837-5285  
WESTERN ENTERPRISE INC, Address:956 OSAGE AVE, Phone:(913) 342-0505  
Intertek-PSI, Address:2828 S. 44th Street, Phone:(913) 310-1600  
CITY OF LEES SUMMIT, Address:220 SE GREEN ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 10/16/2019
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Partial Commercial $1,400.00 $1,400.00 Paid 10/17/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Failed 12/5/2019 12/5/2019 at 1:40 PM 12/05/2019
Misc
Partial Correction
12/05/2019
RE-SCHEDULED TO 12/6
Footing Inspection - Commercial Partial 12/6/2019 at 1:05 PM 12/06/2019
Misc
Partial Correction
12/06/2019
OK TO POUR WHEN READY TRUCK WELL FOOTING: A/7 TO A/5 TO B/5 TO B/5.5;
Footing Inspection - Commercial Partial 12/9/2019 (11:00) 12/9/2019 at 11:00 AM 12/09/2019
Misc
Partial Correction
12/06/2019
OK TO POUR WHEN READY TRUCK WELL FOOTING: A/7 TO A/5 TO B/5 TO B/5.5; B/5.5 TO B/10.4; A.7/5 TO A.7/6.9;
Footing Inspection - Commercial Partial 12/10/2019 (11:00) 12/10/2019 at 11:20 AM 12/10/2019
Misc
Partial Correction
12/09/2019
OK TO POUR WHEN READY TRUCK DOCK WALL AND EXTERIOR WALL FOOTING: A/7 TO A/5 TO B/5 TO B/5.5; A.7/5 TO A.7/6.9; B/5.5 TO B/10.4; B/10.4 TO 11/B TO 11/G.9;
Underground Electrical Inspection - Commercial Partial 12/10/2019 12/10/2019 at 11:45 AM 12/10/2019
Misc
Partial Correction
12/10/2019
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: FROM (1) TO (2);
Footing Inspection - Commercial Partial 12/11/2019 (11:00) 12/11/2019 at 10:35 AM 12/11/2019
Misc
Partial Correction
12/10/2019
OK TO POUR WHEN READY TRUCK DOCK WALL AND EXTERIOR WALL FOOTING: A/7 TO A/5 TO B/5 TO B/5.5; A.7/5 TO A.7/6.9; B/5.5 TO B/10.4; B/10.4 TO 11/B TO 11/G.9; 2.4/J CCW TO A/5;
Misc
Partial Correction
12/11/2019
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: ALL ON (G) AND WEST;
Underground Electrical Inspection - Commercial Partial 12/11/2019 at 9:35 AM 12/11/2019
Misc
Partial Correction
12/10/2019
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3);
Underground Electrical Inspection - Commercial Partial 12/12/2019 12/12/2019 at 10:50 AM 12/12/2019
Misc
Partial Correction
12/11/2019
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6);
Footing Inspection - Commercial Partial 12/12/2019 (11:00) 12/12/2019 at 11:10 AM 12/12/2019
Misc
Partial Correction
12/11/2019
OK TO POUR WHEN READY TRUCK DOCK WALL AND EXTERIOR WALL FOOTING: A/7 TO A/5 TO B/5 TO B/5.5; A.7/5 TO A.7/6.9; B/5.5 TO B/10.4; B/10.4 TO 11/B TO 11/G.9; 2.4/J CCW TO A/5; A/5 CCW TO J/4.8;
Misc
Partial Correction
12/11/2019
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: ALL ON (G) AND WEST; H/4.2; H/4.8; H/5.3; H/6.2; H/6.7;
Footing Inspection - Commercial Partial 12/13/2019 (11:00) 12/13/2019 at 11:55 AM 12/13/2019
Misc
Partial Correction
12/12/2019
OK TO POUR WHEN READY EXTERIOR WALL FOOTING & TRUCK DOCK WALL FOOTING: A/7 TO A/5 TO B/5 TO B/5.5; A.7/5 TO A.7/6.9; B/5.5 TO B/10.4; B/10.4 TO 11/B TO 11/G.9; 2.4/J CCW TO A/5; A/5 CCW TO J/4.8; H/2.4 TO J/2.4 TO J/4.8;
Misc
Partial Correction
12/12/2019
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: ALL ON (G) AND WEST; H/4.2; H/4.8; H/5.3; H/6.2; H/6.7; [H/3.3; K/5.4; K/6.2; K/6.6; K/7.2; H/10.7; G.7/10.7; G.7/8.6
Underground Electrical Inspection - Commercial Partial 12/13/2019 12/13/2019 at 3:00 PM 12/13/2019
Misc
Partial Correction
12/12/2019
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (7); TWO 1" FROM (6) TO (8);
Underslab Plumbing Inspection - Commercial Partial 12/19/2019 12/19/2019 at 8:25 AM 12/19/2019
Misc
Partial Correction
12/19/2019
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: BUILDING DRAIN ON (3.3) FROM 5' OUTSIDE B/L AT (A) TO 30' EAST INSIDE BLDG; ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Underslab Plumbing Inspection - Commercial Partial 12/20/2019 at 9:50 AM 12/20/2019
Misc
Partial Correction
12/19/2019
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 4" PVC BUILDING DRAIN ON (3.3) FROM 5' OUTSIDE B/L AT(A) TO 3.3/D.6; THEN 20' N & S; ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Underslab Plumbing Inspection - Commercial Partial 12/23/2019 12/23/2019 at 8:20 AM 12/23/2019
Misc
Partial Correction
12/20/2019
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 4" PVC BUILDING DRAIN ON (3.3) FROM 5' OUTSIDE B/L AT(A) TO 3.3/D.6; THEN 20' N & S; N TO D.5/1.5; ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Underground Electrical Inspection - Commercial Partial 12/26/2019 12/26/2019 at 9:25 AM 12/26/2019
Misc
Partial Correction
12/13/2019
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (7); TWO 1" FROM (6) TO (8); FIVE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (13); ONE 1" FROM (7) TO (9); ONE 1" FROM (10) TO (12);
Underslab Plumbing Inspection - Commercial Partial 12/26/2019 at 10:00 AM 12/26/2019
Misc
Partial Correction
12/23/2019
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 4" PVC BUILDING DRAIN ON (3.3) FROM 5' OUTSIDE B/L AT(A) TO 3.3/D.6; D.6/3.3 TO D.6/5.8; D.6/3.3 TO D.7/1.2; ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Underground Electrical Inspection - Commercial Partial 12/27/2019 12/27/2019 at 8:35 AM 12/27/2019
Misc
Partial Correction
12/26/2019
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (7); TWO 1" FROM (6) TO (8); FIVE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (13); ONE 1" FROM (7) TO (9); ONE 1" FROM (10) TO (12); ONE 1" FROM (9) TO (12); NUMBERED LOCATIONS ARE HAND-WRITTEN ON G.C. WORKING PRINT SET SITE ELECTRICAL PLAN.
Underground Electrical Inspection - Commercial Partial 1/2/2020 12/31/2019 at 2:10 PM 12/31/2019
Misc
Partial Correction
12/27/2019
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (7); TWO 1" FROM (6) TO (8); FIVE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (13); ONE 1" FROM (7) TO (9); ONE 1" FROM (10) TO (12); ONE 1" FROM (9) TO (12); ONE 1" FROM (X) TO (Y); ONE 1" FROM (X) TO (Y); FOUR 1" FROM (X) TO (Y);
Underslab Plumbing Inspection - Commercial Partial 1/2/2020 at 1:40 PM 01/02/2020
Misc
Partial Correction
12/26/2019
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 4" PVC BUILDING DRAIN ON (3.3) FROM 5' OUTSIDE B/L AT(A) TO 3.3/D.6; D.6/3.3 TO D.6/5.8; D.6/3.3 TO D.7/1.2; 1.45/D.6 TO G/9; 1.2/D.6 TO 1.2/F.9; ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Underground Electrical Inspection - Commercial Partial 1/2/2020 at 9:55 AM 01/02/2020
Misc
Partial Correction
12/31/2019
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (7); TWO 1" FROM (6) TO (8); FIVE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (13); ONE 1" FROM (7) TO (9); ONE 1" FROM (10) TO (12); ONE 1" FROM (9) TO (12); ONE 1" FROM (X) TO (Y); ONE 1" FROM (X) TO (Y); FOUR 1" FROM (X) TO (Y);
Underground Electrical Inspection - Commercial Partial 1/3/2020 1/3/2020 at 7:20 AM 01/03/2020
Misc
Partial Correction
01/02/2020
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (7); TWO 1" FROM (6) TO (8); FIVE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (13); ONE 1" FROM (7) TO (9); ONE 1" FROM (10) TO (12); ONE 1" FROM (9) TO (12); ONE 1" FROM (X) TO (Y); ONE 1" FROM (X) TO (Y); FOUR 1" FROM (X) TO (Y); ONE 1" FROM (13) TO (16);
Underground Electrical Inspection - Commercial Partial 1/7/2020 1/7/2020 at 1:15 PM 01/07/2020
Misc
Partial Correction
01/03/2020
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (7); TWO 1" FROM (6) TO (8); FIVE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (13); ONE 1" FROM (7) TO (9); ONE 1" FROM (10) TO (12); ONE 1" FROM (9) TO (12); ONE 1" FROM (X) TO (Y); ONE 1" FROM (X) TO (Y); FOUR 1" FROM (X) TO (Y); ONE 1" FROM (13) TO (16); TWO 1" FROMM SW CORNER OF BLDG TO (18); ONE 1" FROM (18) TO (19);
Underslab Electrical Inspection - Commercial Partial 1/8/2020 1/7/2020 at 1:40 PM 01/07/2020
Misc
Partial Correction
01/07/2020
OK TO COVER WHEN READY UNDER-SLAB PVC CONDUIT: TWO 4" ENTERING BLDG AT A.5/3 AND EXTENDING ~25' SE;
Underslab Plumbing Inspection - Commercial Failed 1/8/2020 at 7:45 AM 01/08/2020
Misc
Partial Correction
01/02/2020
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 4" PVC BUILDING DRAIN ON (3.3) FROM 5' OUTSIDE B/L AT(A) TO 3.3/D.6; D.6/3.3 TO D.6/5.8; D.6/3.3 TO D.7/1.2; 1.45/D.6 TO G/9; 1.2/D.6 TO 1.2/F.9; ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Misc
Corrective Action Required
01/08/2020
PIPE REQUESTED FOR INSPECTION SUBSTANTIALLY COVERED.
Underslab Plumbing Inspection - Commercial Partial 1/9/2020 1/9/2020 at 9:00 AM 01/09/2020
Misc
Partial Correction
01/08/2020
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 4" PVC BUILDING DRAIN ON (3.3) FROM 5' OUTSIDE B/L AT(A) TO 3.3/D.6; D.6/3.3 TO D.6/5.8; D.6/3.3 TO D.7/1.2; 1.45/D.6 TO G/9; 1.2/D.6 TO 1.2/F.9; ONE 4"/3" FROM 1.2/F.9 TO H.4/5.1; ONE 4" SAN & ONE 4" GW FROM 5' O/S B/L @ F.1/11 TO F.1/9.4 TO 9.4/C.6; ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Misc
Resolved
01/09/2020
PIPE REQUESTED FOR INSPECTION SUBSTANTIALLY COVERED.
Underground Electrical Inspection - Commercial Partial 1/10/2020 1/10/2020 at 7:10 AM 01/10/2020
Misc
Partial Correction
01/07/2020
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (7); TWO 1" FROM (6) TO (8); FIVE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (13); ONE 1" FROM (7) TO (9); ONE 1" FROM (10) TO (12); ONE 1" FROM (9) TO (12); ONE 1" FROM (X) TO (Y); ONE 1" FROM (X) TO (Y); FOUR 1" FROM (X) TO (Y); ONE 1" FROM (13) TO (16); TWO 1" FROM SW CORNER OF BLDG TO (18); ONE 1" FROM (18) TO (19); SEVEN 4", ONE 1-1/4", THREE 1" FROM MDP TO EXTERIOR THEN NORTH TO SERVICE EQUIPMENT AT C/2;
Underslab Plumbing Inspection - Commercial Partial 1/14/2020 1/14/2020 01/14/2020
Misc
Partial Correction
01/09/2020
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 4" PVC BUILDING DRAIN ON (3.3) FROM 5' OUTSIDE B/L AT(A) TO 3.3/D.6; D.6/3.3 TO D.6/5.8; D.6/3.3 TO D.7/1.2; 1.45/D.6 TO G/9; 1.2/D.6 TO 1.2/F.9; ONE 4"/3" FROM 1.2/F.9 TO H.4/5.1; ONE 4" SAN & ONE 4" GW FROM 5' O/S B/L @ F.1/11 TO F.1/9.4 TO 9.4/C.6; ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Misc
Informational
01/14/2020
Grease line & sanitary sewer 4” main G10 to F10 OK to cover
Underslab Plumbing Inspection - Commercial Partial 1/16/2020 1/16/2020 01/16/2020
Misc
Partial Correction
01/14/2020
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 4" PVC BUILDING DRAIN ON (3.3) FROM 5' OUTSIDE B/L AT(A) TO 3.3/D.6; D.6/3.3 TO D.6/5.8; D.6/3.3 TO D.7/1.2; 1.45/D.6 TO G/9; 1.2/D.6 TO 1.2/F.9; ONE 4"/3" FROM 1.2/F.9 TO H.4/5.1; ONE 4" SAN & ONE 4" GW FROM 5' O/S B/L @ F.1/11 TO F.1/9.4 TO 9.4/C.6; ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Misc
Informational
01/14/2020
Grease line & sanitary sewer 4” main G10 to F10 OK to cover Sanitary sewer G 10 TO H 10 TO H 6.5
Underslab Plumbing Inspection - Commercial Partial 1/22/2020 at 7:30 AM 01/22/2020
Misc
Partial Correction
01/16/2020
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: 4" PVC BUILDING DRAIN ON (3.3) FROM 5' OUTSIDE B/L AT(A) TO 3.3/D.6; D.6/3.3 TO D.6/5.8; D.6/3.3 TO D.7/1.2; 1.45/D.6 TO G/9; 1.2/D.6 TO 1.2/F.9; ONE 4"/3" FROM 1.2/F.9 TO H.4/5.1; ONE 4" SAN & ONE 4" GW FROM 5' O/S B/L @ F.1/11 TO F.1/9.4 TO 9.4/C.6; Grease line & sanitary sewer 4” main G10 to F10 OK to cover Sanitary sewer G 10 TO H 10 TO H 6.5; 4" DRAIN FROM FLORAL 103 S TO COFFEE AREA 108 TO CONNECTION AT RESTROOMS 112/113; ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Misc
Resolved
01/22/2020
Grease line & sanitary sewer 4” main G10 to F10 OK to cover Sanitary sewer G 10 TO H 10 TO H 6.5
Underground Plumbing Inspection - Commercial Failed 1/8/2020 1/28/2020 at 7:40 AM 01/28/2020
Misc
Partial Correction
12/19/2019
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: BUILDING DRAIN ON (3.3) FROM 5' OUTSIDE B/L AT (A) TO 30' EAST INSIDE BLDG; ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Misc
Corrective Action Required
01/28/2020
VENT PIPING NOT INSTALLED AS SHOWN ON APPROVED DRAWINGS. VERTICAL DROPS INSIDE TANKS NOT INSTALLED AS SHOWN ON APPROVED DRAWINGS.
Underground Plumbing Inspection - Commercial Partial 1/29/2020 1/29/2020 at 7:20 AM 01/29/2020
Misc
Partial Correction
01/28/2020
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: BUILDING DRAIN ON (3.3) FROM 5' OUTSIDE B/L AT (A) TO 30' EAST INSIDE BLDG; ENSURE PRESSURE-TESTING OF PIPING SYSTEM IS PERFORMED PER IPC 312 / IRC P2503.5.1
Misc
Partial Correction
01/29/2020
PER IPC SLOPE VENT PIPE FOR POSITIVE DRAINAGE SOUTH TO CONNECTION WITH SANITARY. THEN OK TO COVER INTERCEPTORS AND PIPING WHEN READY.
Underground Electrical Inspection - Commercial Partial 2/4/2020 2/4/2020 at 8:35 AM 02/04/2020
Misc
Partial Correction
01/10/2020
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (7); TWO 1" FROM (6) TO (8); FIVE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (13); ONE 1" FROM (7) TO (9); ONE 1" FROM (10) TO (12); ONE 1" FROM (9) TO (12); ONE 1" FROM (X) TO (Y); ONE 1" FROM (X) TO (Y); FOUR 1" FROM (X) TO (Y); ONE 1" FROM (13) TO (16); TWO 1" FROM SW CORNER OF BLDG TO (18); ONE 1" FROM (18) TO (19); SEVEN 4", ONE 1-1/4", THREE 1" FROM MDP TO EXTERIOR THEN NORTH TO SERVICE EQUIPMENT AT C/2; TWO 4" FROM UNDER FOOTING AT B/3 THEN W TO A/3; FIVE 3/4" + TWO 1" + ONE 2" FROM UNDER FOOTING AT B/3 N TO GENERATOR LOCATION;
Underground Electrical Inspection - Commercial Partial 2/18/2020 2/18/2020 at 1:20 PM 02/18/2020
Misc
Partial Correction
02/04/2020
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (7); TWO 1" FROM (6) TO (8); FIVE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (13); ONE 1" FROM (7) TO (9); ONE 1" FROM (10) TO (12); ONE 1" FROM (9) TO (12); ONE 1" FROM (X) TO (Y); ONE 1" FROM (X) TO (Y); FOUR 1" FROM (X) TO (Y); ONE 1" FROM (13) TO (16); TWO 1" FROM SW CORNER OF BLDG TO (18); ONE 1" FROM (18) TO (19); SEVEN 4", ONE 1-1/4", THREE 1" FROM MDP TO EXTERIOR THEN NORTH TO SERVICE EQUIPMENT AT C/2; TWO 4" FROM UNDER FOOTING AT B/3 THEN W TO A/3; FIVE 3/4" + TWO 1" + ONE 2" FROM UNDER FOOTING AT B/3 N TO GENERATOR LOCATION;
Misc
Partial Correction
02/18/2020
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS: 12 AT EAST PARKING LOT;
Underground Electrical Inspection - Commercial Partial 2/19/2020 2/19/2020 at 12:50 PM 02/19/2020
Misc
Partial Correction
02/18/2020
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (7); TWO 1" FROM (6) TO (8); FIVE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (13); ONE 1" FROM (7) TO (9); ONE 1" FROM (10) TO (12); ONE 1" FROM (9) TO (12); ONE 1" FROM (X) TO (Y); ONE 1" FROM (X) TO (Y); FOUR 1" FROM (X) TO (Y); ONE 1" FROM (13) TO (16); TWO 1" FROM SW CORNER OF BLDG TO (18); ONE 1" FROM (18) TO (19); SEVEN 4", ONE 1-1/4", THREE 1" FROM MDP TO EXTERIOR THEN NORTH TO SERVICE EQUIPMENT AT C/2; TWO 4" FROM UNDER FOOTING AT B/3 THEN W TO A/3; FIVE 3/4" + TWO 1" + ONE 2" FROM UNDER FOOTING AT B/3 N TO GENERATOR LOCATION;
Misc
Partial Correction
02/18/2020
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS: TWELVE AT EAST PARKING LOT; TWO AT WEST LOT
Underground Electrical Inspection - Commercial Partial 2/27/2020 2/27/2020 at 10:20 AM 02/27/2020
Misc
Partial Correction
02/19/2020
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (7); TWO 1" FROM (6) TO (8); FIVE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (13); ONE 1" FROM (7) TO (9); ONE 1" FROM (10) TO (12); ONE 1" FROM (9) TO (12); ONE 1" FROM (X) TO (Y); ONE 1" FROM (X) TO (Y); FOUR 1" FROM (X) TO (Y); ONE 1" FROM (13) TO (16); TWO 1" FROM SW CORNER OF BLDG TO (18); ONE 1" FROM (18) TO (19); SEVEN 4", ONE 1-1/4", THREE 1" FROM MDP TO EXTERIOR THEN NORTH TO SERVICE EQUIPMENT AT C/2; TWO 4" FROM UNDER FOOTING AT B/3 THEN W TO A/3; FIVE 3/4" + TWO 1" + ONE 2" FROM UNDER FOOTING AT B/3 N TO GENERATOR LOCATION; SEVEN 4" PVC FROM SWITCHGEAR OUTSIDE NW CORNER OF BUILDING TO 80' TOWARD TRANSFORMER LOCATION;
Misc
Partial Correction
02/19/2020
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS: TWELVE AT EAST PARKING LOT; TWO AT WEST LOT
Underground Electrical Inspection - Commercial Partial 2/28/2020 2/28/2020 at 1:10 PM 02/28/2020
Misc
Partial Correction
02/27/2020
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: ONE 1" FROM (1) TO (2); TWO 1" (2) TO (3); ONE 1" FROM (4) TO (5); THREE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (7); TWO 1" FROM (6) TO (8); FIVE 1" FROM (2) TO (6); TWO 1" FROM (6) TO (13); ONE 1" FROM (7) TO (9); ONE 1" FROM (10) TO (12); ONE 1" FROM (9) TO (12); ONE 1" FROM (X) TO (Y); ONE 1" FROM (X) TO (Y); FOUR 1" FROM (X) TO (Y); ONE 1" FROM (13) TO (16); TWO 1" FROM SW CORNER OF BLDG TO (18); ONE 1" FROM (18) TO (19); SEVEN 4", ONE 1-1/4", THREE 1" FROM MDP TO EXTERIOR THEN NORTH TO SERVICE EQUIPMENT AT C/2; TWO 4" FROM UNDER FOOTING AT B/3 THEN W TO A/3; FIVE 3/4" + TWO 1" + ONE 2" FROM UNDER FOOTING AT B/3 N TO GENERATOR LOCATION; SEVEN 4" PVC FROM SWITCHGEAR OUTSIDE NW CORNER OF BUILDING TO 80' TOWARD TRANSFORMER LOCATION, THEN EXTENDED TO TRANSFORMER LOCATION;
Misc
Partial Correction
02/27/2020
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS: TWELVE AT EAST PARKING LOT; TWO AT WEST LOT
Rough Electrical Inspection - Commercial Passed 3/5/2020 3/5/2020 at 8:45 AM 03/05/2020
Final Inspection - Commercial Passed 04/02/2020
Documents & Images
Date Uploaded File Type Document Name
10/17/2019 Receipt Receipt for transaction: 2019-006841
10/17/2019 Letter DS Building Permit
12/06/2019 Letter INSPECTION SUMMARY
12/09/2019 Letter INSPECTION SUMMARY
12/10/2019 Letter INSPECTION SUMMARY
12/10/2019 Letter INSPECTION SUMMARY
12/11/2019 Letter INSPECTION SUMMARY
12/11/2019 Letter INSPECTION SUMMARY
12/12/2019 Letter INSPECTION SUMMARY
12/12/2019 Letter INSPECTION SUMMARY
12/13/2019 Letter INSPECTION SUMMARY
12/13/2019 Letter INSPECTION SUMMARY
12/19/2019 Letter INSPECTION SUMMARY
12/19/2019 Letter INSPECTION SUMMARY
12/20/2019 Letter INSPECTION SUMMARY
12/23/2019 Letter INSPECTION SUMMARY
12/23/2019 Letter 2019-12-20 McKeevers 950 - RFI #10 - Light Pole Base Detail_Henderson Response
12/26/2019 Letter INSPECTION SUMMARY
12/26/2019 Letter INSPECTION SUMMARY
12/27/2019 Letter INSPECTION SUMMARY
01/02/2020 Letter INSPECTION SUMMARY
01/03/2020 Letter INSPECTION SUMMARY
01/07/2020 Letter INSPECTION SUMMARY
01/07/2020 Letter INSPECTION SUMMARY
01/08/2020 Letter INSPECTION SUMMARY
01/09/2020 Letter INSPECTION SUMMARY
01/10/2020 Letter INSPECTION SUMMARY
01/10/2020 PTR_03533177-1-S3.rev_1
01/10/2020 PTR_03533177-2-S2.rev_1
01/10/2020 PTR_03533177-2-S5.rev_1
01/10/2020 PTR_03533177-1-S1.rev_1
01/10/2020 PTR_03533177-1-S4.rev_1
01/14/2020 Letter INSPECTION SUMMARY
01/16/2020 Letter INSPECTION SUMMARY
01/22/2020 Letter INSPECTION SUMMARY
01/28/2020 Letter INSPECTION SUMMARY
01/29/2020 Letter INSPECTION SUMMARY
02/04/2020 Letter INSPECTION SUMMARY
02/18/2020 Letter INSPECTION SUMMARY
02/19/2020 Letter INSPECTION SUMMARY
02/27/2020 Letter INSPECTION SUMMARY
02/28/2020 Letter INSPECTION SUMMARY
03/05/2020 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.