Summary
PRCOM20192571
Building Permit - Commercial
Final Completion
TOWNSEND SUMMIT LLC
NEW OTHER (COMMERCIAL)
ELECTRIC SERVICE AND STREET LIGHTING
09/10/2019
09/12/2019
02/12/2021
Locations
Contacts
EMERY SAPP AND SONS INC, Address:2301 I-70 DR NW, Phone:(573) 445-8331  
SOSAYA & SONS CONSTRUCTION INC, Address:P O BOX 469, Phone:(913) 745-8800  
TOWNSEND SUMMIT LLC, Address:1311 MCCORMICK RD STE 470, Phone:(303) 947-2044  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 09/24/2019 09/10/2019
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Other $30.00 $30.00 Paid 09/12/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underground Electrical Inspection - Commercial Failed 10/9/2019 10/9/2019 at 9:00 AM 10/09/2019
Misc
Corrective Action Required
10/09/2019
POLE BASE HOLES NOT DUG TO 1/3 OF LP HEIGHT (8'-4")
Underground Electrical Inspection - Commercial Failed 10/11/2019 10/11/2019 at 12:45 PM 10/11/2019
Misc
Corrective Action Required
10/09/2019
POLE BASE HOLES NOT DUG TO 1/3 OF LP HEIGHT (8'-4")
Underground Electrical Inspection - Commercial Partial 10/12/2019 at 8:40 AM 10/12/2019
Misc
Partial Correction
10/12/2019
OK TO POUR WHEN READY LIGHT POLE BASES #2 - #12; PER 10/9/2019 ENGINEER LETTER REQUIRED DEPTH BELOW GRADE HAS BEEN REDUCED TO 6'.
Underground Electrical Inspection - Commercial Partial 10/12/2019 at 11:40 AM 10/12/2019
Misc
Partial Correction
10/12/2019
OK TO POUR WHEN READY LIGHT POLE BASES #1 - #15 PER 10/9/2019 ENGINEER LETTER REQUIRED DEPTH BELOW GRADE HAS BEEN REDUCED TO 6'.
Underground Electrical Inspection - Commercial Partial 10/22/2019 10/22/2019 at 9:25 AM 10/22/2019
Misc
Partial Correction
10/12/2019
OK TO POUR WHEN READY LIGHT POLE BASES #1 - #15 PER 10/9/2019 ENGINEER LETTER REQUIRED DEPTH BELOW GRADE HAS BEEN REDUCED TO 6'.
Misc
Partial Correction
10/22/2019
CONTROLLER BASE OK TO POUR WHEN READY. ENSURE MIN. 3" RE-BAR CLEARANCE TO BOTTOMS AND BANKS.
Electrical Service Inspection Passed 3/23/2020 3/23/2020 03/23/2020
Underground Electrical Inspection - Commercial Passed 4/14/2020 4/14/2020 03/23/2020
Misc
Resolved
03/23/2020
OK TO POUR WHEN READY LIGHT POLE BASES #1 - #15 PER 10/9/2019 ENGINEER LETTER REQUIRED DEPTH BELOW GRADE HAS BEEN REDUCED TO 6'.
Misc
Resolved
03/23/2020
CONTROLLER BASE OK TO POUR WHEN READY. ENSURE MIN. 3" RE-BAR CLEARANCE TO BOTTOMS AND BANKS.
Final Electrical Inspection - Commercial Passed 2/12/2021 02/12/2021
Documents & Images
Date Uploaded File Type Document Name
09/12/2019 Receipt Receipt for transaction: 2019-006195
09/12/2019 Letter DS Building Permit
10/09/2019 Letter INSPECTION SUMMARY
10/12/2019 Letter INSPECTION SUMMARY
10/12/2019 Letter INSPECTION SUMMARY
10/22/2019 Letter INSPECTION SUMMARY
03/23/2020 Letter INSPECTION SUMMARY
03/23/2020 Letter INSPECTION SUMMARY
08/10/2020 Letter Codes 140 Day Letter
08/10/2020 Letter Codes 140 Day Letter
02/12/2021 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home