Permit Application Status

PRCOM20192310


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20192310
Building Permit - Commercial
Voided
HY VEE FOOD STORES INC
NEW COMMERCIAL
NEW BUILDING WITH CANOPY FOR ON-LINE SHOPPING STORAGE AND PICKUP discarded per email from hyvee
08/21/2019
02/24/2020
09/14/2020
Locations
Contacts
SENECA COMPANIES, Address:4140 E 14TH ST, Phone:(816) 761-1270  
HUSSMANN SERVICES CORP, Address:10542 LACKMAN ROAD, Phone:(816) 373-1077  
EMPOWERED ELECTRIC , Address:110 E 13TH AVE, Phone:(816) 401-8949  
PLUMBING BY FISHER INC, Address:9875 KILL CREEK RD, Phone:(913) 583-1971  
HY VEE FOOD STORES INC, Address:5820 WESTOWN PKWY  
SENECA COMPANIES, Address:4140 E 14TH ST, Phone:(816) 761-1270  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 10/03/2019 09/30/2019
Michael Weissenbach
Address numbers required
Corrective Action Required
09/30/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) 1205 SW 3rd St.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/30/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC fire extinguisher.
Misc
Resolved
09/30/2019

(Verified At Inspection) Plan shows height of canopy at highest point to be 14 feet. Canopy needs to stay above 13 feet 6 inches throughout.
Duct smoke detectors
Resolved
09/30/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Verified At Inspection) Duct detection required over 2000 CFM.
Door operations
Corrective Action Required
09/30/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Verified At Inspection) Automatic sliding door shall comply with IFC 2018 1010.1.4.3
Licensed Contractors Rejected 10/03/2019 09/27/2019
Joe Frogge
LC - MEP Subs
Corrective Action Required
09/26/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 9/27/19 - HyVee doesn't not have a Mechanical contractor's license.
Building Plan Review Approved with Conditions 10/03/2019 09/27/2019
Joe Frogge
License Tax Application
Corrective Action Required
09/26/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 9/27/19 - acknowledged in letter
Miscellaneous Correction
Resolved
09/27/2019

Missouri Board for Architects, Professional Engineers, Professional Land Surveyors and Professional Landscape Architects – Board Rules, Division 2030 – Chapter 3, 20 CSR 2030-3.060 Licensees Seal Documents must bear design professionals original seal with signature and date. (relevant portion paraphrased – reference original document for additional information) Action required: All drawings are to bear dated seal and signature from architect/engineer of record. (missing on most MEP and refrigerant drawings)
Accessibility - Turning space 603.2.1
Resolved
09/27/2019

304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Modify drawings to comply.
Bldg - Premises identification/address 501.2
Resolved
09/27/2019

2018 IBC 502.1 Address identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be a minimum of 4 inches high with a minimum stroke width of ½ inch. Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building address cannot be viewed from the public way, a monument, pole or other approved sign or means shall be used to identify the structure. Address identification shall be maintained. Action required: This structure has been assigned the address of 1205 SW 3rd St. Update all relevant records.
Miscellaneous Correction
Resolved
09/27/2019

Interior wall construction (at restrooms) not specified. Action required: Provide complete design for interior wall and door construction. (building construction type is currently IIB which would require that these walls be non-combustible. We recommend changing to VB for future flexibility)
Screening - Rooftop equipment
Resolved
09/27/2019

Unified Development Ordinance Article 8, Section 8.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment (refrigerant unit RC1) will be screened from all 4 sides per referenced UDO section.
Miscellaneous Correction
Resolved
09/27/2019

Anchoring of rooftop unit not specified. Action required: Provide detailed information as to how RCU1 will be anchored to roof.
Health Dept Inspection
Corrective Action Required
09/26/2019

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 9/27/19 - acknowledged in letter
Fire Plan Review Approved with Conditions 10/03/2019 09/27/2019
Michael Weissenbach
Address numbers required
Corrective Action Required
09/26/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) 1205 SW 3rd St.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/26/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC fire extinguisher.
Misc
Corrective Action Required
09/30/2019

(Verified At Inspection) Plan shows height of canopy at highest point to be 14 feet. Canopy needs to stay above 13 feet 6 inches throughout.
Duct smoke detectors
Corrective Action Required
09/30/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Verified At Inspection) Duct detection required over 2000 CFM.
Door operations
Corrective Action Required
09/26/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Verified At Inspection) Automatic sliding door shall comply with IFC 2018 1010.1.4.3
Fire Plan Review Rejected 09/05/2019 08/27/2019
Michael Weissenbach
Address numbers required
Corrective Action Required
08/27/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) 1205 SW 3rd St.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
08/27/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC fire extinguisher.
Miscellaneous Correction
Resolved
08/27/2019

(Informational Purposes) Final development plan needs to be approved to continue the permitting process.
Misc
Corrective Action Required
08/27/2019

(Action Required) Plan shows height of canopy at highest point to be 14 feet. Canopy needs to stay above 13 feet 6 inches throughout.
Duct smoke detectors
Corrective Action Required
08/27/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Action Required) Duct detection required over 2000 CFM.
Door operations
Corrective Action Required
08/27/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Action Required) Automatic sliding door shall comply with IFC 2018 1010.1.4.3
Health Department Review Approved 09/05/2019 08/27/2019
Joe Frogge
Building Plan Review Rejected 09/05/2019 08/22/2019
Joe Frogge
Final Development Plan
Resolved
09/13/2019

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
License Tax Application
Corrective Action Required
08/22/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Miscellaneous Correction
Corrective Action Required
08/22/2019

Missouri Board for Architects, Professional Engineers, Professional Land Surveyors and Professional Landscape Architects – Board Rules, Division 2030 – Chapter 3, 20 CSR 2030-3.060 Licensees Seal Documents must bear design professionals original seal with signature and date. (relevant portion paraphrased – reference original document for additional information) Action required: All drawings are to bear dated seal and signature from architect/engineer of record. (missing on most MEP and refrigerant drawings)
Accessibility - Turning space 603.2.1
Corrective Action Required
08/22/2019

304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Modify drawings to comply.
Bldg - Premises identification/address 501.2
Corrective Action Required
08/22/2019

2018 IBC 502.1 Address identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be a minimum of 4 inches high with a minimum stroke width of ½ inch. Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building address cannot be viewed from the public way, a monument, pole or other approved sign or means shall be used to identify the structure. Address identification shall be maintained. Action required: This structure has been assigned the address of 1205 SW 3rd St. Update all relevant records.
Miscellaneous Correction
Corrective Action Required
08/22/2019

Interior wall construction (at restrooms) not specified. Action required: Provide complete design for interior wall and door construction. (building construction type is currently IIB which would require that these walls be non-combustible. We recommend changing to VB for future flexibility)
Screening - Rooftop equipment
Corrective Action Required
08/22/2019

Unified Development Ordinance Article 8, Section 8.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment (refrigerant unit RC1) will be screened from all 4 sides per referenced UDO section.
Miscellaneous Correction
Corrective Action Required
08/22/2019

Anchoring of rooftop unit not specified. Action required: Provide detailed information as to how RCU1 will be anchored to roof.
Health Dept Inspection
Corrective Action Required
08/27/2019

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Review
Resolved
08/27/2019

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Licensed Contractors Rejected 09/05/2019 08/22/2019
Joe Frogge
LC - General Contractor
Resolved
09/11/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
08/22/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Final Development Plan Review Approved 09/05/2019 08/21/2019
Joe Frogge
Inspections

There are no inspections for this permit application.

Documents & Images
Date Uploaded File Type Document Name
08/21/2019 Letter License Tax Bill
08/27/2019 New Food Establishment Plan Review - Approved FTG 0001895
08/27/2019 address info
08/27/2019 Letter Fire Building Plan Review
08/28/2019 Letter DS P/R Corrections Document
09/27/2019 Letter Fire Building Plan Review
09/30/2019 Letter Fire Building Plan Review
09/08/2020 Email RE Hyvee Aisles Online - PRCOM20192310
09/14/2020 Email RE Hyvee Aisles Online - PRCOM20192310
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home