Permit Application Status

PRCOM20192308


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20192308
Building Permit - Commercial
Final Completion
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
EXPANSION OF EXISTING DIALYSIS CLINIC
08/21/2019
09/23/2019
02/24/2020
01/09/2020
Locations
Contacts
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
MCCARTHY BUILDING COMPANIES INC, Address:12851 MANCHESTER RD, Phone:(314) 646-4179  
US ENGINEERING CONSTRUCTION LLC, Address:3433 ROANOKE RD , Phone:(816) 753-6969  
SHAW ELECTRIC COMPANY, Address:3600 FULLER, Phone:(816) 921-0033  
US ENGINEERING CONSTRUCTION LLC, Address:3433 ROANOKE RD , Phone:(816) 753-6969  
ACI BOLAND, Address:1421 EAST 104TH ST; SUITE 100, Phone:(816) 763-9600  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 09/17/2019 09/16/2019
Joe Frogge
LC - General Contractor
Corrective Action Required
09/10/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 9/11/19 - acknowledged in letter
LC - MEP Subs
Corrective Action Required
09/10/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 9/11/19 - acknowledged in letter
Building Plan Review Approved with Conditions 09/17/2019 09/12/2019
Joe Frogge
License Tax Application
Corrective Action Required
09/10/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 9/11/19 - acknowledged in letter
Project cost
Corrective Action Required
09/10/2019

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes. 9/11/19 - acknowledged in letter
Plan Submittal 2012 Codes
Resolved
09/11/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update accessibility code reference to show 2017 ICC/ANSI
Misc
Resolved
09/11/2019

2018 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. The fire-resistance rating of penetrations and fire-resistant joint systems shall be determined in accordance Sections 714 and 715, respectively. Action required: Clarify fire rating scenarios. Wall removed for new waiting room appears to be rated but not replaced? The only wall tags I can find are for double wall K with a note that untagged walls are A but the rating of the doors does not reflect this scenario.
Bldg - Toilet room wall finish 1210.2.2
Resolved
09/11/2019

2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish material at restroom. If paint is used it must be epoxy based. Is EP-1 and epoxy paint? Not shown in schedule.
Miscellaneous Correction
Corrective Action Required
09/10/2019

2017 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Comment is for informational purposes. To be verified during inspections. 9/11/19 - acknowledged in letter
NEC - Equipment outlet 210.63
Resolved
09/12/2019

2017 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected. 9/11/19 - Sheet E1 not provided in resubmit. Unable to verify.
Fire Plan Review Approved with Conditions 09/17/2019 09/11/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
09/10/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the system will require three sets of PE stamped shop drawings.
Hazardous material identification
Corrective Action Required
09/10/2019

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. (Verified At Inspection) Label all rooms
Construction documents - Fire protection systems
Corrective Action Required
09/10/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the system will require three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
09/10/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Fire Plan Review Approved with Conditions 09/03/2019 08/27/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
08/27/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the system will require three sets of PE stamped shop drawings.
Hazardous material identification
Corrective Action Required
08/27/2019

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. (Verified At Inspection) Label all rooms
Construction documents - Fire protection systems
Corrective Action Required
08/27/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the system will require three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
08/27/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Building Plan Review Rejected 09/03/2019 08/22/2019
Joe Frogge
License Tax Application
Corrective Action Required
08/22/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Project cost
Corrective Action Required
08/22/2019

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes.
Plan Submittal 2012 Codes
Corrective Action Required
08/22/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update accessibility code reference to show 2017 ICC/ANSI
Misc
Corrective Action Required
08/22/2019

2018 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. The fire-resistance rating of penetrations and fire-resistant joint systems shall be determined in accordance Sections 714 and 715, respectively. Action required: Clarify fire rating scenarios. Wall removed for new waiting room appears to be rated but not replaced? The only wall tags I can find are for double wall K with a note that untagged walls are A but the rating of the doors does not reflect this scenario.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
08/22/2019

2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish material at restroom. If paint is used it must be epoxy based. Is EP-1 and epoxy paint? Not shown in schedule.
Miscellaneous Correction
Corrective Action Required
08/22/2019

2017 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Comment is for informational purposes. To be verified during inspections.
NEC - Equipment outlet 210.63
Corrective Action Required
08/22/2019

2017 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
Licensed Contractors Rejected 09/03/2019 08/22/2019
Joe Frogge
LC - General Contractor
Corrective Action Required
08/22/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
08/22/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $1,820.00 $1,820.00 Paid 09/23/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 11/5/2019 at 8:25 AM 11/05/2019
Misc
Partial Correction
11/05/2019
OK TO TOP-OUT GWB ABOVE 10' AFF AT: B290 S WALL; ENTRY & B284 AT CORRIDOR;
In-wall Inspection Failed 11/20/2019 11/20/2019 at 7:10 AM 11/20/2019
Misc
Partial Correction
11/05/2019
OK TO TOP-OUT GWB ABOVE 10' AFF AT: B290 S WALL; ENTRY & B284 W WALL AT CORRIDOR;
Misc
Corrective Action Required
11/20/2019
PLUMBING NOT READY
In-wall Inspection Partial 12/4/2019 12/04/2019
Misc
Partial Correction
11/20/2019
OK TO TOP-OUT GWB ABOVE 10' AFF AT: B290 S WALL; ENTRY & B284 W WALL AT CORRIDOR; B273; B281; B283; B285
Misc
Resolved
12/04/2019
PLUMBING NOT READY
In-wall Inspection Passed 12/10/2019 12/10/2019 at 1:45 PM 12/10/2019
Misc
Resolved
12/10/2019
OK TO TOP-OUT GWB ABOVE 10' AFF AT: B290 S WALL; ENTRY & B284 W WALL AT CORRIDOR; B273; B281; B283; B285
Above Ceiling Inspection Passed 12/26/2019 12/26/2019 at 10:55 AM 12/26/2019
Alarm Test Passed 1/8/2020 01/08/2020
Occupancy Inspection - Fire Passed 11/5/2019 1/8/2020 01/08/2020
Final Inspection - Commercial Passed 1/8/2020 1/8/2020 at 9:00 AM 01/08/2020
Documents & Images
Date Uploaded File Type Document Name
08/21/2019 Letter License Tax Not Applicable
08/27/2019 Letter Fire Building Plan Review
08/28/2019 Letter DS P/R Corrections Document
09/11/2019 Letter Fire Building Plan Review
09/23/2019 Receipt Receipt for transaction: 2019-006365
09/23/2019 Letter DS Building Permit
11/05/2019 Letter INSPECTION SUMMARY
12/04/2019 Letter INSPECTION SUMMARY
12/10/2019 Letter INSPECTION SUMMARY
12/26/2019 Letter INSPECTION SUMMARY
01/08/2020 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home