Permit Application Status

PRCOM20191957


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20191957
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
CHANGE OF TENANT
TENANT FINISH FOR MEDSPA
07/22/2019
09/23/2019
02/24/2020
12/18/2019
Locations
Contacts
3 SQUARE CONTRACTING INC, Address:1243 MERRIAM LANE, Phone:(913) 754-3033  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
HENSLEY ELECTRIC INC, Address:7911 BOND STREET, Phone:(913) 441-1064  
ALLIANCE MECHANICAL CONTRACTORS, Address:305 W CEDAR , Phone:(913) 553-2600  
BRASSTACKS INC, Address:2101 W 43RD AVE, Phone:(913) 283-7376  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 12/06/2019
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
12/06/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule alarm testing.
Sprinkler Plan Review Released for Construction 10/22/2019
Michael Weissenbach
Misc
Corrective Action Required
10/22/2019

(Action Required) Current annual inspection tag posted on the riser.
Licensed Contractors Approved 09/16/2019 09/11/2019
Joe Frogge
LC - General Contractor
Resolved
09/11/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
09/11/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved 09/16/2019 09/11/2019
Joe Frogge
Plan Submittal 2012 Codes
Resolved
09/11/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit Action required: Update code references.
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Resolved
09/11/2019

2018 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. ICC A117.1-2017 Section 904.3 Sales and service counters and windows. Sales and service counters and windows shall comply with Section 904.3.1 and either 904.3.2 or 904.3.3. Where counters are provided, the accessible portion of the countertop shall extend the same depth as the public portion of the sales and service countertop provided for standing customers. (see code for exception) 904.3.1 Vertical barriers. At service windows or service counters, any vertical barrier between service personnel and customers shall be at a height of 43 inches maximum above the floor. (see code for exception regarding security glazing) 904.3.2 Parallel Approach. A portion of the public use side of the counter surface 36 inches minimum in length and 26 inches minimum and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a parallel approach adjacent to the accessible counter shall be provided. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12 inches minimum. (see code for exception) 904.3.3 Forward Approach. A portion of the public use side of the counter surface 30 inches minimum in length and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a forward approach to the accessible counter shall be provided. Knee and toe clearance complying with Section 306 shall be provided under the accessible counter. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12” minimum. Action required: Reception desk to have at least 3' of accessible area. To be field verified
Bldg - Emergency power for illumination 1006.3
Resolved
09/11/2019

2018 IBC 1008.3 – Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior side of exit doors.
NEC - Receptacles - Other than dwelling units 210.8(B)
Resolved
09/11/2019

2017 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected. (ref: Exam Rooms 1 & 3)
Fire Plan Review Approved with Conditions 09/16/2019 09/09/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
09/09/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications made to the alarm system, provide three sets of PE stamped shop drawings.
Address numbers required
Corrective Action Required
09/09/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
09/09/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications made to the sprinkler system, provide three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
09/09/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/09/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (verified At Inspection) Provide one 2A10BC extinguisher
Illumination required
Corrective Action Required
09/09/2019

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Verified At Inspection) Provide exterior emergency lighting at the exit doors.
Fire Plan Review Approved with Conditions 09/03/2019 08/27/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
08/27/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications made to the alarm system, provide three sets of PE stamped shop drawings.
Address numbers required
Corrective Action Required
08/27/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
08/27/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications made to the sprinkler system, provide three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
08/27/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
08/27/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (verified At Inspection) Provide one 2A10BC extinguisher
Illumination required
Corrective Action Required
08/27/2019

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide exterior emergency lighting at the exit doors.
Building Plan Review Rejected 09/03/2019 08/22/2019
Joe Frogge
Plan Submittal 2012 Codes
Corrective Action Required
08/22/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit Action required: Update code references.
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Corrective Action Required
08/22/2019

2018 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. ICC A117.1-2017 Section 904.3 Sales and service counters and windows. Sales and service counters and windows shall comply with Section 904.3.1 and either 904.3.2 or 904.3.3. Where counters are provided, the accessible portion of the countertop shall extend the same depth as the public portion of the sales and service countertop provided for standing customers. (see code for exception) 904.3.1 Vertical barriers. At service windows or service counters, any vertical barrier between service personnel and customers shall be at a height of 43 inches maximum above the floor. (see code for exception regarding security glazing) 904.3.2 Parallel Approach. A portion of the public use side of the counter surface 36 inches minimum in length and 26 inches minimum and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a parallel approach adjacent to the accessible counter shall be provided. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12 inches minimum. (see code for exception) 904.3.3 Forward Approach. A portion of the public use side of the counter surface 30 inches minimum in length and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a forward approach to the accessible counter shall be provided. Knee and toe clearance complying with Section 306 shall be provided under the accessible counter. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12” minimum. Action required: Reception desk to have at least 3' of accessible area. To be field verified
Bldg - Emergency power for illumination 1006.3
Corrective Action Required
08/22/2019

2018 IBC 1008.3 – Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior side of exit doors.
NEC - Receptacles - Other than dwelling units 210.8(B)
Corrective Action Required
08/22/2019

2017 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected. (ref: Exam Rooms 1 & 3)
Licensed Contractors Rejected 09/03/2019 08/22/2019
Joe Frogge
LC - General Contractor
Corrective Action Required
08/22/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
08/22/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $319.33 $319.33 Paid 09/23/2019
8331507-Sewer Connection Fee $120.00 $120.00 Paid 09/23/2019
7232302-Commercial License Tax Fee $1,260.00 $1,260.00 Paid 09/11/2019
$1,260.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 9/24/2019 9/24/2019 at 10:45 AM 09/24/2019
Underslab Plumbing Inspection - Commercial Passed 10/23/2019 10/23/2019 at 2:35 PM 10/23/2019
Underslab Electrical Inspection - Commercial Passed 10/23/2019 at 2:50 PM 10/23/2019
In-wall Inspection Failed 11/1/2019 11/1/2019 at 8:40 AM 11/01/2019
Misc
Corrective Action Required
11/01/2019
IN-WALL ELECTRICAL WORK INCOMPLETE
Misc
Corrective Action Required
11/01/2019
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE BOCA PLATES). CHECK ALL.
In-wall Inspection Passed 11/4/2019 11/4/2019 at 11:20 AM 11/04/2019
Misc
Resolved
11/04/2019
IN-WALL ELECTRICAL WORK INCOMPLETE
Misc
Resolved
11/04/2019
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE BOCA PLATES). CHECK ALL.
Above Ceiling Inspection Partial 11/11/2019 at 1:20 PM 11/11/2019
Misc
Partial Correction
11/11/2019
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS AT: EXAM 4
Above Ceiling Inspection Failed 12/3/2019 12/3/2019 at 9:30 AM 12/03/2019
Misc
Partial Correction
11/11/2019
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS AT: EXAM 4
Misc
Corrective Action Required
12/03/2019
ACT TILE AREAS: REMOVE TILE FOR INSPECTION
Misc
Corrective Action Required
12/03/2019
ELECTRICAL WORK STILL IN PROGRESS. COMPLETE FOR INSPECTION.
Misc
Corrective Action Required
12/03/2019
REMOVE TEMPORARY ELECTRICAL WIRING
Misc
Corrective Action Required
12/03/2019
SUPPORT ALL LOW-VOLTAGE CONDUCTORS WITH HARDWARE DESIGNED FOR PURPOSE. DO NOT SUPPORT FROM OTHER M/E/P SYSTEMS.
Misc
Corrective Action Required
12/03/2019
REMOVE STRAP HANGERS AND ANY OTHER UNUSED HARDWARE
Misc
Corrective Action Required
12/03/2019
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER. PLUG ANY UNUSED BOX OPENINGS.
Misc
Corrective Action Required
12/03/2019
OBTAIN A/E LETTER ALLOWING USE OF FLEX DUCT AS RETURN AIR BOOTS. IF ALLOWED, THEN ENSURE NONE ARE CONSTRICTED TO ACCOMODATE AIR MOVEMENT. CHECK ALL FLEX DUCT CONNECTIONS TO ENSURE BANDING IS PROPERLY DONE.
Above Ceiling Inspection Partial 12/4/2019 12/04/2019
Misc
Resolved
12/04/2019
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS AT: EXAM 4
Misc
Resolved
12/04/2019
ACT TILE AREAS: REMOVE TILE FOR INSPECTION
Misc
Resolved
12/04/2019
ELECTRICAL WORK STILL IN PROGRESS. COMPLETE FOR INSPECTION.
Misc
Resolved
12/04/2019
REMOVE TEMPORARY ELECTRICAL WIRING
Misc
Resolved
12/04/2019
SUPPORT ALL LOW-VOLTAGE CONDUCTORS WITH HARDWARE DESIGNED FOR PURPOSE. DO NOT SUPPORT FROM OTHER M/E/P SYSTEMS.
Misc
Resolved
12/04/2019
REMOVE STRAP HANGERS AND ANY OTHER UNUSED HARDWARE
Misc
Resolved
12/04/2019
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER. PLUG ANY UNUSED BOX OPENINGS.
Misc
Resolved
12/04/2019
OBTAIN A/E LETTER ALLOWING USE OF FLEX DUCT AS RETURN AIR BOOTS. IF ALLOWED, THEN ENSURE NONE ARE CONSTRICTED TO ACCOMODATE AIR MOVEMENT. CHECK ALL FLEX DUCT CONNECTIONS TO ENSURE BANDING IS PROPERLY DONE.
Misc
Corrective Action Required
12/04/2019
Rear wall at firewall to corridor. Hole in firewall above wall switch above ceiling. Contractor to leave ceiling visible for reinspection.
Alarm Test Passed 12/12/2019 12/12/2019
Miscellaneous Inspection Passed 12/13/2019 at 7:55 AM 12/13/2019
Above Ceiling Inspection Passed 12/13/2019
Misc
Resolved
12/13/2019
Rear wall at firewall to corridor. Hole in firewall above wall switch above ceiling. Contractor to leave ceiling visible for reinspection.
Occupancy Inspection - Codes Commercial Failed 12/13/2019 12/13/2019 at 10:50 AM 12/13/2019
Misc
Corrective Action Required
12/13/2019
NEC 600.3 UL LISTING OF EXTERIOR LIGHTED SIGNS / DECORATIVE ELEMENTS: IF INTERNALLY LIGHTED, MUST BE UL SHOP-LABELED AS INDICATION OF LISTING.
Misc
Corrective Action Required
12/13/2019
NEC 408.4 ELECTRICAL PANEL SCHEDULES: ENSURE ALL CIRCUIT POSITIONS ARE PROPERLY LABELED. MUST BE LEGIBLE, COMPLETE, CURRENT, SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Corrective Action Required
12/13/2019
SOME DEVICES NOT INSTALLED OR NOT HOT FOR TEST. EXAMPLES: EXAM 1 E WALL; EXAM 4 E WALL;
Misc
Corrective Action Required
12/13/2019
NO LIGHTING AT OFFICE
Misc
Corrective Action Required
12/13/2019
GLASS DOORS NOT HUNG
Misc
Corrective Action Required
12/13/2019
CORRECT FIRE DEPT ISSUES
Misc
Partial Correction
12/13/2019
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. STAFFING, TRAINING, FIXTURING, STOCKING OK. NO PUBLIC/CUSTOMERS/PATIENTS PRIOR TO APPROVAL.
Occupancy Inspection - Fire Temporary C of O 12/13/2019 12/13/2019
Occupancy Inspection - Codes Commercial Temporary C of O 12/17/2019 12/17/2019 at 2:10 PM 12/17/2019
Misc
Corrective Action Required
12/13/2019
NEC 600.3 UL LISTING OF EXTERIOR LIGHTED SIGNS / DECORATIVE ELEMENTS: IF INTERNALLY LIGHTED, MUST BE UL SHOP-LABELED AS INDICATION OF LISTING.
Misc
Resolved
12/17/2019
NEC 408.4 ELECTRICAL PANEL SCHEDULES: ENSURE ALL CIRCUIT POSITIONS ARE PROPERLY LABELED. MUST BE LEGIBLE, COMPLETE, CURRENT, SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Resolved
12/17/2019
SOME DEVICES NOT INSTALLED OR NOT HOT FOR TEST. EXAMPLES: EXAM 1 E WALL; EXAM 4 E WALL;
Misc
Resolved
12/17/2019
NO LIGHTING AT OFFICE
Misc
Resolved
12/17/2019
GLASS DOORS NOT HUNG
Misc
Resolved
12/17/2019
CORRECT FIRE DEPT ISSUES
Misc
Resolved
12/17/2019
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. STAFFING, TRAINING, FIXTURING, STOCKING OK. NO PUBLIC/CUSTOMERS/PATIENTS PRIOR TO APPROVAL.
Occupancy Inspection - Codes Commercial Full C of O 12/18/2019 at 1:05 PM 12/18/2019
Misc
Resolved
12/18/2019
NEC 600.3 UL LISTING OF EXTERIOR LIGHTED SIGNS / DECORATIVE ELEMENTS: IF INTERNALLY LIGHTED, MUST BE UL SHOP-LABELED AS INDICATION OF LISTING.
Documents & Images
Date Uploaded File Type Document Name
08/27/2019 Letter Fire Building Plan Review
08/28/2019 Letter DS P/R Corrections Document
09/09/2019 Letter Fire Building Plan Review
09/11/2019 Letter License Tax Bill
09/23/2019 Receipt Receipt for transaction: 2019-006363
09/23/2019 Letter DS Building Permit
10/22/2019 Letter Fire (Sprinkler) Plan Review
10/23/2019 Letter INSPECTION SUMMARY
10/23/2019 Letter INSPECTION SUMMARY
11/01/2019 Letter INSPECTION SUMMARY
11/04/2019 Letter INSPECTION SUMMARY
11/11/2019 Letter INSPECTION SUMMARY
12/03/2019 Letter INSPECTION SUMMARY
12/04/2019 Letter INSPECTION SUMMARY
12/06/2019 Letter Fire (Alarm) Plan Review Notice
12/13/2019 Letter INSPECTION SUMMARY
12/17/2019 Letter Codes Temporary Certificate of Occupancy
12/18/2019 Letter Field Certificate of Occupancy
12/20/2019 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home