Permit Application Status

PRCOM20191681


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20191681
Building Permit - Commercial
Certificate of Occupancy
NEW COMMERCIAL
NEW GROCERY STORE
06/26/2019
11/21/2019
01/04/2020
06/04/2020
Locations
Contacts
CROSSLAND CONSTRUCTION COMPANY INC, Address:PO BOX 45, Phone:(620) 429-1414  
SGA DESIGN GROUP PC, Address:1437 SOUTH BOULDER STE 550, Phone:(915) 587-8600  
MJ INTERIORS, Address:7915 HEMLOCK ST, Phone:(913) 313-6565  
LONG ELECTRIC LLC, Address:3301 S CARAWAY RD, Phone:(870) 206-7826  
R2 PLUMBING LLC, Address:1705 A SE COUNTY RD AA, Phone:(816) 215-8098  
  
SGA DESIGN GROUP PC, Address:1437 SOUTH BOULDER STE 550, Phone:(915) 587-8600  
KAW VALLEY ENGINEERING INC, Address:14700 W 114TH TERR, Phone:(913) 894-5150  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 02/13/2020
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
02/13/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule alarm testing.
Sprinkler Plan Review Released for Construction 02/10/2020
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
02/10/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a Hydrostatic Test and a water flow.
Miscellaneous Correction
Corrective Action Required
02/10/2020

(Action Required) FDC to be a 4 inch Storz connection with a 30 degree elbow.
Fire Plan Review Approved with Conditions 01/09/2020
Mike Weisenborn
Construction documents for fire alarm systems
Corrective Action Required
01/09/2020

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide three sets of stamped shop drawings for the fire alarm system.
Address numbers required
Corrective Action Required
01/09/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address the building readable from the roadway.
Knox box required
Corrective Action Required
01/09/2020

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. (Action Required) Order a Knox Box from knoxbox.com. Placement will be made by the FDC.
Fire protection equipment identification
Corrective Action Required
01/09/2020

2018 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. (Informational Purposes)
Construction documents - Fire protection systems
Corrective Action Required
01/09/2020

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide three sets of stamped shop drawings for the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
01/09/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
01/09/2020

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection)
Miscellaneous Correction
Corrective Action Required
01/09/2020

(Informational Purposes) The exit sign was meant for the East side. Correction noted.
Duct smoke detectors
Corrective Action Required
01/09/2020

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Informational Purposes)
Licensed Contractors Approved 07/26/2019 11/18/2019
Joe Frogge
LC - General Contractor
Resolved
11/05/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 7/26/19 - Acknowledged in letter.
LC - MEP Subs
Resolved
11/18/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 7/26/19 - Acknowledged in letter.
Final Development Plan Review Approved 11/04/2019
Joe Frogge
Fire Plan Review Approved with Conditions 08/02/2019 07/30/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
07/26/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide three sets of stamped shop drawings for the fire alarm system.
Address numbers required
Corrective Action Required
07/26/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address the building readable from the roadway.
Knox box required
Corrective Action Required
07/26/2019

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. (Action Required) Order a Knox Box from knoxbox.com. Placement will be made by the FDC.
Fire protection equipment identification
Corrective Action Required
07/26/2019

2018 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. (Informational Purposes)
Construction documents - Fire protection systems
Corrective Action Required
07/26/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide three sets of stamped shop drawings for the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
07/26/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
07/26/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection)
Miscellaneous Correction
Resolved
07/30/2019

(Action Required) Show hydrant within 100 feet of FDC. Recommendation: Place FDC at NE corner of building
Miscellaneous Correction
Resolved
07/30/2019

(Action Required) Post No Parking signage in front of building.
Miscellaneous Correction
Corrective Action Required
07/26/2019

(Informational Purposes) The exit sign was meant for the East side. Correction noted.
Duct smoke detectors
Corrective Action Required
07/26/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Informational Purposes)
Building Plan Review Approved with Conditions 08/02/2019 07/26/2019
Joe Frogge
Final Development Plan
Resolved
11/04/2019

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 7/26/19 - Acknowledged in letter.
License Tax Application
Corrective Action Required
07/26/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 7/26/19 - Acknowledged in letter.
Health Dept Inspection
Corrective Action Required
07/26/2019

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 7/26/19 - Acknowledged in letter.
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Resolved
07/26/2019

ICC A117.1-2017 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" clear at latch side of door out of cooler. 7/26/19 - meets exception
Accessibility - Turning space 603.2.1
Resolved
07/26/2019

ICC A117.1-2017 Section 304.3 Size. Turning spaces shall comply with Section 304.3.1 or 304.3.2. 304.3.1 Circular Space. 304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Turning spaces to be minimum 67".
Misc
Resolved
07/26/2019

2018 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide side rail extender at roof hatch. 7/26/19 - safety cage specified meets intent in that it provides another rung above the hatch
Misc
Resolved
07/26/2019

Water meter must be located near property line. Action required: Remove water meter from plumbing plan and details.
Miscellaneous Correction
Corrective Action Required
08/29/2019

The City will not release this facility for any type of use until full access to Ward Rd and Donovan Rd have been completed.
Special Inspections Review Approved 07/24/2019
Joe Frogge
Health Department Review Approved 07/22/2019
Joe Frogge
Building Plan Review Rejected 07/11/2019 07/08/2019
Joe Frogge
Final Development Plan
Corrective Action Required
07/08/2019

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
License Tax Application
Corrective Action Required
07/08/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Resolved
07/24/2019

2018 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Health Dept Review
Resolved
07/22/2019

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
07/08/2019

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Corrective Action Required
07/08/2019

ICC A117.1-2017 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" clear at latch side of door out of cooler.
Accessibility - Turning space 603.2.1
Corrective Action Required
07/08/2019

ICC A117.1-2017 Section 304.3 Size. Turning spaces shall comply with Section 304.3.1 or 304.3.2. 304.3.1 Circular Space. 304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Turning spaces to be minimum 67".
Misc
Corrective Action Required
07/08/2019

2018 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide side rail extender at roof hatch.
Misc
Corrective Action Required
07/08/2019

Water meter must be located near property line. Action required: Remove water meter from plumbing plan and details.
Licensed Contractors Rejected 07/11/2019 07/08/2019
Joe Frogge
LC - General Contractor
Corrective Action Required
07/08/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
07/08/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 07/11/2019 07/01/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
07/01/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide three sets of stamped shop drawings for the fire alarm system.
Address numbers required
Corrective Action Required
07/01/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address the building readable from the roadway.
Knox box required
Corrective Action Required
07/01/2019

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. (Action Required) Order a Knox Box from knoxbox.com. Placement will be made by the FDC.
Fire protection equipment identification
Corrective Action Required
07/01/2019

2018 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. (Informational Purposes)
Construction documents - Fire protection systems
Corrective Action Required
07/01/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide three sets of stamped shop drawings for the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
07/01/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
07/01/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection)
Miscellaneous Correction
Corrective Action Required
07/01/2019

(Action Required) Show hydrant within 100 feet of FDC. Recommendation: Place FDC at NE corner of building
Miscellaneous Correction
Corrective Action Required
07/01/2019

(Action Required) Post No Parking signage in front of building.
Miscellaneous Correction
Corrective Action Required
07/01/2019

(Action Required) Add exit sign in west corridor on the sales floor with arrow towards north Exit.
Duct smoke detectors
Corrective Action Required
07/01/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Informational Purposes)
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Commercial $9,000.00 $9,000.00 Paid 11/21/2019
8331507-Sewer Connection Fee $270.00 $270.00 Paid 11/21/2019
Commercial Excise Tax Fee $90,945.00 $90,945.00 Paid 05/26/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 12/26/2019 12/26/2019 at 8:45 AM 12/26/2019
Misc
Partial Correction
12/26/2019
AFTER APPROVAL BY 3RD PARTY INSPECTOR OK TO POUR WEST WALL FOOTING + ~6' RETURNS AT EACH END;
Underground Electrical Inspection - Commercial Partial 12/26/2019 12/26/2019 at 8:20 AM 12/26/2019
Misc
Partial Correction
12/26/2019
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: FROM L.P. BASE #1 TO #2 TO #3 TO #4; LEVEL TRENCH BOTTOM TO PREVENT KINKING OF CONDUIT. L.P. LOCATIONS NUMBERED ON PERMIT PRINTS SITE ELECTRICAL PLAN.
Misc
Corrective Action Required
12/26/2019
LIGHT POLE BASES NOT APPROVED TO POUR. RE-BAR CAGES MUST BE HUNG AND HAVE >=3" CLEARANCE AT BOTTOM AND >=1-1/2" AT TOP.
Underground Electrical Inspection - Commercial Partial 12/27/2019 12/27/2019 at 10:40 AM 12/27/2019
Misc
Partial Correction
12/26/2019
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: FROM L.P. BASE #1 TO #2 TO #3 TO #4; LEVEL TRENCH BOTTOM TO PREVENT KINKING OF CONDUIT. L.P. LOCATIONS NUMBERED ON PERMIT PRINTS SITE ELECTRICAL PLAN.
Misc
Partial Correction
12/27/2019
OK TO POUR WHEN READY LIGHT POLE BASES AT LOCATIONS: 1, 2, 3, 4 -- WITH G.E.C.s AND GROUND RODS IN PLACE;
Footing Inspection - Commercial Partial 12/31/2019 (11:00) 12/31/2019 at 11:30 AM 12/31/2019
Misc
Partial Correction
12/26/2019
AFTER APPROVAL BY 3RD PARTY INSPECTOR OK TO POUR WEST WALL FOOTING + ~6' RETURNS AT EACH END; A.2/4 TO A.2/2.2;
Footing Inspection - Commercial Failed 1/3/2020 (10:00) 1/3/2020 at 10:20 AM 01/03/2020
Misc
Partial Correction
12/31/2019
AFTER APPROVAL BY 3RD PARTY INSPECTOR OK TO POUR WEST WALL FOOTING + ~6' RETURNS AT EACH END; A.2/4 TO A.2/2.2;
Footing Inspection - Commercial Partial 1/3/2020 at 1:00 PM 01/03/2020
Misc
Partial Correction
01/03/2020
AFTER APPROVAL BY 3RD PARTY INSPECTOR OK TO POUR WEST WALL FOOTING + ~6' RETURNS AT EACH END; A.2/4 TO A.2/2.2; 1/A.1 TO 1/C.7;
Footing Inspection - Commercial Partial 1/8/2020 1/8/2020 at 3:00 PM 01/08/2020
Misc
Partial Correction
01/03/2020
AFTER APPROVAL BY 3RD PARTY INSPECTOR OK TO POUR WEST WALL FOOTING + ~6' RETURNS AT EACH END; A.2/4 TO A.2/2.2; 1/A.1 TO 1/C.7; 3.4/E TO 3.4/D TO D.2.5;
Foundation Inspection - Commercial Partial 1/8/2020 1/8/2020 at 2:40 PM 01/08/2020
Misc
Partial Correction
01/08/2020
CONTINGENT ON APPROVAL OF REVISED DRAWINGS OK TO POUR FOUNDATION WALL AT: WEST WALL + 3' RETURNS;
Footing Inspection - Commercial Partial 1/15/2020 (1:00) 1/15/2020 at 2:20 PM 01/15/2020
Misc
Partial Correction
01/08/2020
AFTER APPROVAL BY 3RD PARTY INSPECTOR OK TO POUR WEST WALL FOOTING + ~6' RETURNS AT EACH END; A.2/4 TO A.2/2.2; 1/A.1 TO 1/C.7; 3.4/E TO 3.4/D TO D.2.5; 5 COLUMN PADS (3) F5 LINE B 3.3 2.6 1.7 (2) F7 LINE C 2 & 3 FOOTING A 1.9 TO A 1;
Foundation Inspection - Commercial Partial 1/16/2020 1/16/2020 01/16/2020
Misc
Partial Correction
01/08/2020
CONTINGENT ON APPROVAL OF REVISED DRAWINGS OK TO POUR FOUNDATION WALL AT: WEST WALL + 3' RETURNS; OK to pour south foundation wall A.2 3.3 to 1.9 OK to pour east foundation wall B to B.8
Foundation Inspection - Commercial Failed 1/27/2020 (10:00) 1/27/2020 at 10:20 AM 01/27/2020
Misc
Partial Correction
01/16/2020
CONTINGENT ON APPROVAL OF REVISED DRAWINGS OK TO POUR FOUNDATION WALL AT: WEST WALL + 3' RETURNS; OK to pour south foundation wall A.2 3.3 to 1.9 OK to pour east foundation wall B to B.8
Misc
Corrective Action Required
01/27/2020
RE-BAR NOT PER APPROVED DRAWINGS
Foundation Inspection - Commercial Partial 1/27/2020 1/27/2020 at 12:05 PM 01/27/2020
Misc
Partial Correction
01/27/2020
CONTINGENT ON APPROVAL OF REVISED DRAWINGS OK TO POUR FOUNDATION WALL AT: WEST WALL + 3' RETURNS; OK to pour south foundation wall A.2 3.3 to 1.9 OK to pour east foundation wall B to B.8; A.3/1 TO A/1 TO A/2.4;
Misc
Resolved
01/27/2020
RE-BAR NOT PER APPROVED DRAWINGS
Foundation Inspection - Commercial Failed 1/29/2020 (2:30) 1/29/2020 at 2:55 PM 01/29/2020
Misc
Partial Correction
01/27/2020
OK TO POUR FOUNDATION WALL AT: WEST WALL + 3' RETURNS; south foundation wall A.2 3.3 to 1.9 ; east foundation wall B to B.8; A.3/1 TO A/1 TO A/2.4; WALL SEGMENT D/3.4 TO D/2.8 NOT APPROVED DUE TO UNDER-SIZED VERTICAL RE-BAR
Foundation Inspection - Commercial Partial 1/30/2020 1/30/2020 at 9:05 AM 01/30/2020
Misc
Partial Correction
01/29/2020
OK TO POUR FOUNDATION WALL AT: WEST WALL + 3' RETURNS; south foundation wall A.2 3.3 to 1.9 ; east foundation wall B to B.8; A.3/1 TO A/1 TO A/2.4; TRUCK DOCK WALL D/3.4 TO D/2.8;
Foundation Inspection - Commercial Partial 1/30/2020 1/30/2020 at 2:35 PM 01/30/2020
Misc
Partial Correction
01/30/2020
OK TO POUR FOUNDATION WALL AT: WEST WALL + 3' RETURNS; south foundation wall A.2 3.3 to 1.9 ; east foundation wall B to B.8; A.3/1 TO A/1 TO A/2.4; TRUCK DOCK WALL D/3.4 TO D/2.8; D/3.4 TO E/3.4;
Foundation Inspection - Commercial Partial 2/5/2020 (9:00) 2/5/2020 at 8:20 AM 02/05/2020
Misc
Partial Correction
01/30/2020
OK TO POUR FOUNDATION WALL AT: WEST WALL + 3' RETURNS; south foundation wall A.2 3.3 to 1.9 ; east foundation wall B to B.8; A.3/1 TO A/1 TO A/2.4; TRUCK DOCK WALL D/3.4 TO D/2.8; D/3.4 TO E/3.4; FROM E/3.4 TO E/4;
Footing Inspection - Commercial Partial 2/11/2020 2/11/2020 at 2:20 PM 02/11/2020
Misc
Partial Correction
01/15/2020
AFTER APPROVAL BY 3RD PARTY INSPECTOR OK TO POUR WEST WALL FOOTING + ~6' RETURNS AT EACH END; A.2/4 TO A.2/2.2; 1/A.1 TO 1/C.7; 3.4/E TO 3.4/D TO D/2.5; D/2.5 EAST TO D/2; 5 COLUMN PADS (3) F5 LINE B 3.3 2.6 1.7 (2) F7 LINE C 2 & 3 FOOTING A 1.9 TO A 1;
Footing Inspection - Commercial Partial 2/12/2020 (1:00) 2/12/2020 at 1:00 PM 02/12/2020
Misc
Partial Correction
02/11/2020
AFTER APPROVAL BY 3RD PARTY INSPECTOR OK TO POUR WEST WALL FOOTING + ~6' RETURNS AT EACH END; A.2/4 TO A.2/2.2; 1/A.1 TO 1/C.7; 3.4/E TO 3.4/D TO D/2.5; D/2.5 EAST TO D/2; D/2 TO D/1.2 TO 1.2/C.7 TO COMPLETE WALL FOOTING 5 COLUMN PADS (3) F5 LINE B 3.3 2.6 1.7 (2) F7 LINE C 2 & 3 FOOTING A 1.9 TO A 1;
Foundation Inspection - Commercial Partial 2/14/2020 (1:30) 2/18/2020 at 7:15 AM 02/18/2020
Misc
Partial Correction
02/05/2020
OK TO POUR FOUNDATION WALL AT: WEST WALL + 3' RETURNS; south foundation wall A.2 3.3 to 1.9 ; east foundation wall B to B.8; A.3/1 TO A/1 TO A/2.4; TRUCK DOCK WALL D/3.4 TO D/2.8; D/3.4 TO E/3.4; FROM E/3.4 TO E/4; 1.2/D TO 1.2/B.8;
Foundation Inspection - Commercial Partial 2/18/2020 (1:00) 2/18/2020 at 11:50 AM 02/18/2020
Misc
Partial Correction
02/18/2020
OK TO POUR FOUNDATION WALL AT: WEST WALL + 3' RETURNS; south foundation wall A.2 3.3 to 1.9 ; east foundation wall B to B.8; A.3/1 TO A/1 TO A/2.4; TRUCK DOCK WALL D/3.4 TO D/2.8; D/3.4 TO E/3.4; FROM E/3.4 TO E/4; 1.2/D TO 1.2/B.8; D/1.3 TO D/2.1;
Footing Inspection - Commercial Partial 2/21/2020 (2:30) 2/21/2020 at 2:20 PM 02/21/2020
Misc
Partial Correction
02/12/2020
AFTER APPROVAL BY 3RD PARTY INSPECTOR OK TO POUR WEST WALL FOOTING + ~6' RETURNS AT EACH END; A.2/4 TO A.2/2.2; 1/A.1 TO 1/C.7; 3.4/E TO 3.4/D TO D/2.5; D/2.5 EAST TO D/2; D/2 TO D/1.2 TO 1.2/C.7; E/2 TO E/3.4 5 COLUMN PADS (3) F5 LINE B 3.3 2.6 1.7 (2) F7 LINE C 2 & 3 FOOTING A 1.9 TO A 1;
Footing Inspection - Commercial Partial 2/24/2020 (1:00) 2/24/2020 at 12:05 PM 02/24/2020
Misc
Partial Correction
02/21/2020
AFTER APPROVAL BY 3RD PARTY INSPECTOR OK TO POUR WEST WALL FOOTING + ~6' RETURNS AT EACH END; A.2/4 TO A.2/2.2; 1/A.1 TO 1/C.7; 3.4/E TO 3.4/D TO D/2.5; D/2.5 EAST TO D/2; D/2 TO D/1.2 TO 1.2/C.7; E/2 TO E/3.4; SOUTH CART CORRAL; 5 COLUMN PADS (3) F5 LINE B 3.3 2.6 1.7 (2) F7 LINE C 2 & 3 FOOTING A 1.9 TO A 1;
Foundation Inspection - Commercial Partial 2/25/2020 (2:00) 2/25/2020 at 1:35 PM 02/25/2020
Misc
Partial Correction
02/18/2020
OK TO POUR FOUNDATION WALL AT: WEST WALL + 3' RETURNS; south foundation wall A.2 3.3 to 1.9 ; east foundation wall B to B.8; A.3/1 TO A/1 TO A/2.4; TRUCK DOCK WALL D/3.4 TO D/2.8; D/3.4 TO E/3.4; FROM E/3.4 TO E/4; 1.2/D TO 1.2/B.8; D/1.3 TO D/2.1; NORTH WALL OF TRUCK WELL;
Underslab Plumbing Inspection - Commercial Passed 2/27/2020 2/27/2020 at 2:05 PM 02/27/2020
Footing Inspection - Commercial Passed 3/4/2020 3/4/2020 at 9:50 AM 03/04/2020
Misc
Resolved
03/04/2020
AFTER APPROVAL BY 3RD PARTY INSPECTOR OK TO POUR WEST WALL FOOTING + ~6' RETURNS AT EACH END; A.2/4 TO A.2/2.2; 1/A.1 TO 1/C.7; 3.4/E TO 3.4/D TO D/2.5; D/2.5 EAST TO D/2; D/2 TO D/1.2 TO 1.2/C.7; E/2 TO E/3.4; SOUTH CART CORRAL; EAST CART CORRAL; STAIR IN TRUCK WELL 5 COLUMN PADS (3) F5 LINE B 3.3 2.6 1.7 (2) F7 LINE C 2 & 3 FOOTING A 1.9 TO A 1
Foundation Inspection - Commercial Partial 3/4/2020 3/4/2020 at 10:25 AM 03/04/2020
Misc
Partial Correction
02/25/2020
OK TO POUR FOUNDATION WALL AT: WEST WALL + 3' RETURNS; south foundation wall A.2 3.3 to 1.9 ; east foundation wall B to B.8; A.3/1 TO A/1 TO A/2.4; TRUCK DOCK WALL D/3.4 TO D/2.8; D/3.4 TO E/3.4; FROM E/3.4 TO E/4; 1.2/D TO 1.2/B.8; D/1.3 TO D/2.1; NORTH WALL OF TRUCK WELL; SOUTH CART CORRAL; 5 COLUMN PADS (3) F5 LINE B 3.3 2.6 1.7 (2) F7 LINE C 2 & 3 FOOTING A 1.9 TO A 1
Foundation Inspection - Commercial Passed 3/13/2020 3/13/2020 03/13/2020
Misc
Resolved
03/13/2020
OK TO POUR FOUNDATION WALL AT: WEST WALL + 3' RETURNS; south foundation wall A.2 3.3 to 1.9 ; east foundation wall B to B.8; A.3/1 TO A/1 TO A/2.4; TRUCK DOCK WALL D/3.4 TO D/2.8; D/3.4 TO E/3.4; FROM E/3.4 TO E/4; 1.2/D TO 1.2/B.8; D/1.3 TO D/2.1; NORTH WALL OF TRUCK WELL; SOUTH CART CORRAL; 5 COLUMN PADS (3) F5 LINE B 3.3 2.6 1.7 (2) F7 LINE C 2 & 3 FOOTING A 1.9 TO A 1
Gas Piping Inspection - Commercial Failed 3/16/2020 3/16/2020 03/16/2020
Misc
Corrective Action Required
03/16/2020
PARTIAL- INCOMPLETE GAS LINE AT WEST END, 2 LOCATIONS NOT EXTENED THROUGH ROOF HOLD 15 PSI. RETEST WHEN GAS IS COMPLETE WITHIN 6FT OF UNIT.
Rough Electrical Inspection - Commercial Partial 3/18/2020 3/18/2020 03/18/2020
Misc
Informational
03/18/2020
South exterior wall electrical ok to spray foam West exterior wall electrical ok to spray foam
Rough Mechanical Inspection - Commercial Partial 3/18/2020 03/18/2020
Misc
Informational
03/18/2020
West exterior wall refrigeration lines OK to spray foam
All Rough Inspection - Commercial Partial 3/18/2020 3/18/2020 03/18/2020
Misc
Informational
03/18/2020
Metal stud framing exterior walls south , west, north, east
Gas Piping Inspection - Commercial Passed 3/19/2020 3/18/2020 03/18/2020
Misc
Resolved
03/18/2020
PARTIAL- INCOMPLETE GAS LINE AT WEST END, 2 LOCATIONS NOT EXTENED THROUGH ROOF HOLD 15 PSI. RETEST WHEN GAS IS COMPLETE WITHIN 6FT OF UNIT. Units inside building not on roof
Underground Electrical Inspection - Commercial Partial 12/27/2019 3/20/2020 at 1:20 PM 03/20/2020
Misc
Partial Correction
12/26/2019
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: FROM L.P. BASE #1 TO #2 TO #3 TO #4; LEVEL TRENCH BOTTOM TO PREVENT KINKING OF CONDUIT. L.P. LOCATIONS NUMBERED ON PERMIT PRINTS SITE ELECTRICAL PLAN.
Misc
Partial Correction
12/27/2019
OK TO POUR WHEN READY LIGHT POLE BASES AT LOCATIONS: 1, 2, 3, 4 -- WITH G.E.C.s AND GROUND RODS IN PLACE;
Misc
Partial Correction
03/20/2020
UNDERGROUND ELECTRICAL OK BELOW: -LOW VOLTAGE RACEWAY AND SECONDARY ELECTRICAL RACEWAYS FROM TRANSFORMER PAD TO BUILDING SERVICE LOCATION **DUE TO ROCKS, THE ELECTRICIAN WAS GIVEN OK TO BURY THE GROUNDING RODS, INSTEAD OF DRIVING THEM STRAIGHT DOWN OR AT 45 DEG ANGLE.
All Rough Inspection - Commercial Partial 3/23/2020 3/23/2020 03/23/2020
Misc
Informational
03/18/2020
Metal stud framing exterior walls south , west, north, east PARAPET WALLS; NORTH;EAST,SOUTH.
In-wall Inspection Partial 3/25/2020 3/25/2020 at 9:20 AM 03/25/2020
Misc
Partial Correction
03/25/2020
WALLS APPROVED TO COVER: -WALL ABOVE COOLER WINDOW, RM 107
In-wall Inspection Failed 3/27/2020 3/27/2020 at 10:20 AM 03/27/2020
Misc
Partial Correction
03/25/2020
WALLS APPROVED TO COVER: -WALL ABOVE COOLER WINDOW, RM 107 **IN-WALL PLUMBING NOT READY
In-wall Inspection Partial 3/31/2020 3/31/2020 03/31/2020
Misc
Partial Correction
03/27/2020
WALLS APPROVED TO COVER: -WALL ABOVE COOLER WINDOW, RM 107; INSTALL PLUMBING SUPPORTS MID STORY ON DWV AT BATHS AND OFFICE, BREAK ROOM RECALL. E COMMERCE ROOM NEEDS CORNER COMPLETE W/ELECT. EXTERIOR STRUCTURAL FRAMING OK TO INSULATE: SOUTH , EAST 1/2 WALL.
In-wall Inspection Partial 4/1/2020 4/1/2020 04/01/2020
Misc
Partial Correction
03/31/2020
WALLS APPROVED TO COVER: -WALL ABOVE COOLER WINDOW, RM 107; E COMMERCE, BATHROOMS, OFFICE AND REAKROOM. EXTERIOR STRUCTURAL FRAMING COMPLETE.
In-wall Inspection Partial 4/6/2020 4/6/2020 04/06/2020
Misc
Partial Correction
04/01/2020
WALLS APPROVED TO COVER: -WALL ABOVE COOLER WINDOW, RM 107; E COMMERCE, BATHROOMS, OFFICE AND REAKROOM. BEHIND COOLER AREA 2 WALLS. EXTERIOR STRUCTURAL FRAMING COMPLETE.
Sprinkler - Hydrostatic Test Passed 4/10/2020 04/10/2020
Piers/Caissons Inspection - Commercial Passed 4/22/2020 4/22/2020 04/22/2020
Misc
Informational
04/22/2020
- (1) LIGHT POLE BASE REAR DRIVE APPROACH AT STREET DRIVEN GROUND ROD IN PLACE OK TO POUR -
Rough Electrical Inspection - Commercial Passed 5/5/2020 5/5/2020 05/05/2020
Misc
Informational
03/18/2020
South exterior wall electrical ok to spray foam West exterior wall electrical ok to spray foam . entry canopy lighting OK POLE LIGHTS GROUNDING INSPECTED MARK HARDING 05/18/2020 8:50 AM
Alarm Test Not Ready 5/11/2020 05/11/2020
Sprinkler - Flow Test Not Ready 5/11/2020 05/11/2020
Electrical Service Inspection Passed 5/12/2020 5/12/2020 05/12/2020
Above Ceiling Inspection Failed 5/11/2020 5/12/2020 05/12/2020
Misc
Corrective Action Required
05/12/2020
support all MC cable, install 2 support wires per light fixture throughout. support all DWV 48"o.c.and condensate line to front office. reset for wednesday 5/13
All Rough Inspection - Commercial Passed 05/12/2020
Misc
Informational
03/23/2020
Metal stud framing exterior walls south , west, north, east PARAPET WALLS; NORTH;EAST,SOUTH.
Above Ceiling Inspection Passed 5/13/2020 05/13/2020
Misc
Resolved
05/13/2020
support all MC cable, install 2 support wires per light fixture throughout. support all DWV 48"o.c.and condensate line to front office. reset for wednesday 5/13
In-wall Inspection Passed 5/13/2020 05/13/2020
Misc
Resolved
05/13/2020
WALLS APPROVED TO COVER: -WALL ABOVE COOLER WINDOW, RM 107; E COMMERCE, BATHROOMS, OFFICE AND REAKROOM. BEHIND COOLER AREA 2 WALLS. EXTERIOR STRUCTURAL FRAMING COMPLETE.
Underground Electrical Inspection - Commercial Passed 05/13/2020
Misc
Resolved
05/13/2020
OK TO COVER WHEN READY BURIED CONDUIT FOR SITE ELECTRICAL SYSTEM AT FOLLOWING LOCATIONS: FROM L.P. BASE #1 TO #2 TO #3 TO #4; LEVEL TRENCH BOTTOM TO PREVENT KINKING OF CONDUIT. L.P. LOCATIONS NUMBERED ON PERMIT PRINTS SITE ELECTRICAL PLAN.
Misc
Resolved
05/13/2020
OK TO POUR WHEN READY LIGHT POLE BASES AT LOCATIONS: 1, 2, 3, 4 -- WITH G.E.C.s AND GROUND RODS IN PLACE;
Misc
Resolved
05/13/2020
UNDERGROUND ELECTRICAL OK BELOW: -LOW VOLTAGE RACEWAY AND SECONDARY ELECTRICAL RACEWAYS FROM TRANSFORMER PAD TO BUILDING SERVICE LOCATION **DUE TO ROCKS, THE ELECTRICIAN WAS GIVEN OK TO BURY THE GROUNDING RODS, INSTEAD OF DRIVING THEM STRAIGHT DOWN OR AT 45 DEG ANGLE.
Gas Service Inspection - Commercial Passed 5/13/2020 05/13/2020
Alarm Test Passed 5/28/2020 05/28/2020
Sprinkler - Flow Test Passed 5/28/2020 05/28/2020
Occupancy Inspection - Engineering Temporary C of O 5/28/2020 05/28/2020
Occupancy Inspection - Codes Commercial Temporary C of O 5/28/2020 5/28/2020 05/28/2020
Misc
Corrective Action Required
05/28/2020
BUILDING INSPECTIONS LIST- OK FOR TCO-2WEEKS TO COMPLETE THE FOLLOWING: - ACCESS TO ROOF TOP FOR INSPECTION(WEATHER RELATED) -GUARD RAIL OPENING AT LOADING DOCK OVER 4" NEXT TO BUILDING -GFCI NEED WITHIN 6' OF MOP SINK. -SUPPORTING OF DWV PIPE 48"O.C. OVER REAR COOLERS. - JACKSON COUNTY HEALTH DEPT APPROVED 5/28 OTHER DEPARTMENTS ON SEPARATE LETTER. ALL APPROVED FOR TCO.
Occupancy Inspection - Planning Temporary C of O 5/28/2020 05/28/2020
Corrective Action Required
05/28/2020
Complete landscaping per the approved landscape plan.
Occupancy Inspection - Water Utilities Passed 5/28/2020 06/01/2020
Occupancy Inspection - Fire Temporary C of O 5/28/2020 06/04/2020
Occupancy Inspection - Fire Passed 6/4/2020 06/04/2020
Occupancy Inspection - Planning Passed 6/4/2020 06/04/2020
Occupancy Inspection - Engineering Passed 6/4/2020 06/04/2020
Misc
Informational
06/04/2020
All items have been completed and we have passed occupancy.
Occupancy Inspection - Codes Commercial Full C of O 6/4/2020 6/4/2020 06/04/2020
Misc
Resolved
06/04/2020
Documents & Images
Date Uploaded File Type Document Name
07/01/2019 Letter Fire Building Plan Review
07/08/2019 Letter DS P/R Corrections Document
07/22/2019 Letter New Food Establishment Plan Review - Approved FTG 0001498
07/24/2019 Letter sp insp letter
07/30/2019 Letter Fire Building Plan Review
11/08/2019 Letter License Tax Bill
11/21/2019 Receipt Receipt for transaction: 2019-007429
11/21/2019 Letter DS Building Permit
11/21/2019 Letter DS Building Permit
12/26/2019 Letter INSPECTION SUMMARY
12/26/2019 Letter INSPECTION SUMMARY
12/27/2019 Letter INSPECTION SUMMARY
12/31/2019 Letter INSPECTION SUMMARY
01/03/2020 Letter INSPECTION SUMMARY
01/08/2020 Letter INSPECTION SUMMARY
01/08/2020 Letter INSPECTION SUMMARY
01/15/2020 Letter INSPECTION SUMMARY
01/16/2020 Letter INSPECTION SUMMARY
01/27/2020 Letter INSPECTION SUMMARY
01/29/2020 Letter INSPECTION SUMMARY
01/30/2020 Letter INSPECTION SUMMARY
01/30/2020 Letter INSPECTION SUMMARY
02/05/2020 Letter INSPECTION SUMMARY
02/10/2020 Letter Fire (Sprinkler) Plan Review
02/11/2020 Letter INSPECTION SUMMARY
02/12/2020 Letter INSPECTION SUMMARY
02/13/2020 Letter Fire (Alarm) Plan Review Notice
02/18/2020 Letter INSPECTION SUMMARY
02/18/2020 Letter INSPECTION SUMMARY
02/18/2020 Letter INSPECTION SUMMARY
02/21/2020 Letter INSPECTION SUMMARY
02/24/2020 Letter INSPECTION SUMMARY
02/25/2020 Letter INSPECTION SUMMARY
02/27/2020 Letter INSPECTION SUMMARY
03/04/2020 Letter INSPECTION SUMMARY
03/04/2020 Letter INSPECTION SUMMARY
03/13/2020 Letter INSPECTION SUMMARY
03/16/2020 Letter INSPECTION SUMMARY
03/18/2020 Letter INSPECTION SUMMARY
03/18/2020 Letter INSPECTION SUMMARY
03/18/2020 Letter INSPECTION SUMMARY
03/18/2020 Letter INSPECTION SUMMARY
03/20/2020 Letter INSPECTION SUMMARY
03/23/2020 Letter INSPECTION SUMMARY
03/25/2020 Letter INSPECTION SUMMARY
03/27/2020 Letter INSPECTION SUMMARY
03/31/2020 Letter INSPECTION SUMMARY
04/01/2020 Letter INSPECTION SUMMARY
04/01/2020 Specifications Lee's Summit, MO 06_Current Permit Spec
04/01/2020 Plans ALDI - Lee's Summit MO 06 - combined set for city
04/01/2020 Approved drawings - ALDI - Lee's Summit MO 06 - combined set for city
04/01/2020 Approved spec - Lee's Summit, MO 06_Current Permit Spec
04/06/2020 Letter INSPECTION SUMMARY
04/22/2020 Letter INSPECTION SUMMARY
05/05/2020 Letter INSPECTION SUMMARY
05/12/2020 Letter INSPECTION SUMMARY
05/12/2020 Letter INSPECTION SUMMARY
05/13/2020 Letter INSPECTION SUMMARY
05/13/2020 INSPECTION SUMMARY_20200513094017
05/13/2020 Letter INSPECTION SUMMARY
05/13/2020 Letter INSPECTION SUMMARY
05/20/2020 Aldi #6, Permit # 20191681 - Backflow Reports
05/26/2020 Receipt Receipt for transaction: 2020-002380
05/28/2020 Letter Codes Temporary Certificate of Occupancy
06/04/2020 Letter Codes Final Certificate of Occupancy
06/04/2020 Letter DE-Daily Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home