Permit Application Status

PRCOM20191458


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20191458
Building Permit - Commercial
Certificate of Occupancy
VAAP CHAPEL RIDGE LLC
CHANGE OF TENANT
TENANT FINISH FOR HAIR SALON
06/06/2019
07/01/2019
12/09/2019
08/15/2019
Locations
Contacts
DR VEERAL BHOOT, Address:3680 NE AKIN DR, Phone:(816) 721-4968  
VERITAS ARCHITECTURE & DESIGN, Address:1520 CLAY ST, SUITE AB, Phone:(816) 284-6518  
METRO HEATING & AC, Address:101 N CLAYVIEW DRIVE STE A, Phone:(816) 535-8000  
LAKE ELECTRIC LLC, Address:1917 SPRUCE ST, Phone:(913) 490-8377  
MUDLOFF CONSTRUCTION LLC, Address:1917 E SPRUCE ST, Phone:(913) 393-0737  
TRADEMARK ELECTRIC INC, Address:8200 NE US 69 HWY, Phone:(816) 442-8101  
VAAP CHAPEL RIDGE LLC, Address:5007 W 147TH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 06/21/2019 06/24/2019
Joe Frogge
LC - General Contractor
Corrective Action Required
06/18/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 6/18/19 - noted in letter to be Mudloff Construction which is not a currently licensed contractor with LS.
LC - MEP Subs
Corrective Action Required
06/18/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 6/18/19 - acknowledged in letter - to be selected by GC
Building Plan Review Approved with Conditions 06/21/2019 06/18/2019
Joe Frogge
Project cost
Resolved
06/18/2019

Two application forms have been provided with conflicting project costs. Action required: Provide contract or other written verification to clarify cost of project. First application stated $40,000 while the second application states $18,000.
Suite address
Resolved
06/18/2019

This structure has been assigned numbered addresses. When a suite is split and there is not an appropriate number to assign, the sub suites should be alphabetical. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: Numbered suite split (102) doesn't make sense in this case. Alphabetical (A, B) should be used. Clarify.
Code analysis required
Resolved
06/18/2019

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Provide code analysis.
License Tax Application
Corrective Action Required
06/14/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 6/18/19 - acknowledged in letter
Miscellaneous Correction
Resolved
06/18/2019

Large space is unidentified. Unable to complete review. Action required: Provide space use designation and show all furniture and work stations. This may result in an occupant load higher than IBC calculations given that 2 occupants will be counted per station.
Plan Submittal 2012 Codes
Resolved
06/18/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update all code references and remove any reference to IRC.
Accessibility - Dining surface height 902.4
Resolved
06/18/2019

ICC A117.1-2009 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor. Action required: Specify compliant height at break room sink.
Accessibility - Turning space 603.2.1
Resolved
06/18/2019

1103.2.2 Employee work areas. Spaces and elements within employee work areas shall only be required to comply with Sections 907.5.2.3.1, 1009 and 1104.3.1 and shall be designed and constructed so that individual with disabilities can approach, enter and exit the work area. Work areas, or portions of work areas, other than raised courtroom stations in accordance with Section 1108.4.1.4, that are less than 300 square feet in area and located 7 inches or more above or below the ground or finished floor where the change in elevation is essential to the function of the space shall be exempt from all requirements. (see code for additional exemptions) ICC A117.1-2017 Section 304.3 Size. Turning spaces shall comply with Section 304.3.1 or 304.3.2. 304.3.1 Circular Space. 304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) 304.3.1.2 Existing buildings and facilities. In existing buildings and facilities, the turning space shall be a circular space with a 60-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Provide compliant turning space in office.
Bldg - Types I and II construction allowable materials 602.2
Resolved
06/18/2019

2012 IBC 602.2 – Types I and II. Types I and II construction are those types of construction in which the building elements listed in Table 601 are of noncombustible materials, except as permitted in Section 603 and elsewhere in this code. Action required: Specify compliant wall materials. (wood studs not allowed in Type II construction which is how this building is classified)
Fire Plan Review Approved with Conditions 06/21/2019 06/17/2019
Michael Weissenbach
Misc
Resolved
06/17/2019

Plans ACTION REQUIRED: Provide a complete set of plans showing the use of the entire space and tenant finish
Misc
Resolved
06/17/2019

Plans ACTION REQUIRED: Provide a complete set of plans showing the use of the entire space and tenant finish
Construction documents for fire alarm systems
Corrective Action Required
06/17/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Modifications to alarm system will require three sets of stamped plans.
Address numbers required
Corrective Action Required
06/17/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Action Required) Address front and back doors.
Construction documents - Fire protection systems
Corrective Action Required
06/17/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Modifications to fire sprinkler system will require three sets of stamped plans. Modifications
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/17/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Action Required) Provide one 2A10BC extinguisher
Door operations
Corrective Action Required
06/17/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Informational Purposes)
Fire Plan Review Rejected 06/12/2019
Michael Weissenbach
Misc
Corrective Action Required
06/12/2019

Plans ACTION REQUIRED: Provide a complete set of plans showing the use of the entire space and tenant finish
Misc
Corrective Action Required
06/12/2019

Plans ACTION REQUIRED: Provide a complete set of plans showing the use of the entire space and tenant finish
Fire Plan Review Rejected 06/18/2019 06/12/2019
Joe Frogge
Misc
Corrective Action Required
06/11/2019

Plans ACTION REQUIRED: Provide a complete set of plans showing the use of the entire space and tenant finish
Building Plan Review Rejected 06/18/2019 06/12/2019
Joe Frogge
Project cost
Corrective Action Required
06/12/2019

Two application forms have been provided with conflicting project costs. Action required: Provide contract or other written verification to clarify cost of project. First application stated $40,000 while the second application states $18,000.
Suite address
Corrective Action Required
06/12/2019

This structure has been assigned numbered addresses. When a suite is split and there is not an appropriate number to assign, the sub suites should be alphabetical. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: Numbered suite split (102) doesn't make sense in this case. Alphabetical (A, B) should be used. Clarify.
Code analysis required
Corrective Action Required
06/12/2019

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Provide code analysis.
License Tax Application
Corrective Action Required
06/12/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Miscellaneous Correction
Corrective Action Required
06/12/2019

Large space is unidentified. Unable to complete review. Action required: Provide space use designation and show all furniture and work stations. This may result in an occupant load higher than IBC calculations given that 2 occupants will be counted per station.
Plan Submittal 2012 Codes
Corrective Action Required
06/12/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update all code references and remove any reference to IRC.
Accessibility - Dining surface height 902.4
Corrective Action Required
06/12/2019

ICC A117.1-2009 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor. Action required: Specify compliant height at break room sink.
Accessibility - Turning space 603.2.1
Corrective Action Required
06/12/2019

1103.2.2 Employee work areas. Spaces and elements within employee work areas shall only be required to comply with Sections 907.5.2.3.1, 1009 and 1104.3.1 and shall be designed and constructed so that individual with disabilities can approach, enter and exit the work area. Work areas, or portions of work areas, other than raised courtroom stations in accordance with Section 1108.4.1.4, that are less than 300 square feet in area and located 7 inches or more above or below the ground or finished floor where the change in elevation is essential to the function of the space shall be exempt from all requirements. (see code for additional exemptions) ICC A117.1-2017 Section 304.3 Size. Turning spaces shall comply with Section 304.3.1 or 304.3.2. 304.3.1 Circular Space. 304.3.1.1 New Buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter. (see code for information regarding allowed overlapping) 304.3.1.2 Existing buildings and facilities. In existing buildings and facilities, the turning space shall be a circular space with a 60-inch minimum diameter. (see code for information regarding allowed overlapping) Action required: Provide compliant turning space in office.
Bldg - Types I and II construction allowable materials 602.2
Corrective Action Required
06/12/2019

2012 IBC 602.2 – Types I and II. Types I and II construction are those types of construction in which the building elements listed in Table 601 are of noncombustible materials, except as permitted in Section 603 and elsewhere in this code. Action required: Specify compliant wall materials. (wood studs not allowed in Type II construction which is how this building is classified)
Licensed Contractors Rejected 06/18/2019 06/11/2019
Joe Frogge
LC - General Contractor
Resolved
06/24/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
06/24/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 06/18/2019 06/10/2019
Joe Dir
Misc
Corrective Action Required
06/10/2019

Plans ACTION REQUIRED: Provide a complete set of plans showing the use of the entire space and tenant finish
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $96.00 $96.00 Paid 06/24/2019
8331507-Sewer Connection Fee $180.00 $180.00 Paid 06/24/2019
7232302-Commercial Excise Tax Fee $1,245.00 $1,245.00 Paid 07/01/2019
$1,245.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 7/9/2019 at 1:00 PM 07/09/2019
In-wall Inspection Failed 7/12/2019 7/12/2019 at 10:50 AM 07/12/2019
Misc
Corrective Action Required
07/12/2019
-RESTROOM NOT READY. COMPLETE FRAMING AND INSTALL BLOCKINGS FOR GRAB BARS
In-wall Inspection Passed 7/15/2019 at 10:40 AM 07/15/2019
Misc
Resolved
07/15/2019
-RESTROOM NOT READY. COMPLETE FRAMING AND INSTALL BLOCKINGS FOR GRAB BARS
Above Ceiling Inspection Failed 7/30/2019 7/30/2019 at 3:30 PM 07/30/2019
Misc
Corrective Action Required
07/30/2019
NOT READY FORABOVE CEILING INSPECTION @ RESTROOM
Electrical Service Inspection Passed 7/30/2019 7/30/2019 at 3:35 PM 07/30/2019
Above Ceiling Inspection Passed 8/6/2019 8/6/2019 at 11:05 AM 08/06/2019
Misc
Resolved
08/06/2019
NOT READY FOR ABOVE CEILING INSPECTION @ RESTROOM
Occupancy Inspection - Codes Commercial Failed 8/9/2019 8/9/2019 at 9:45 AM 08/09/2019
Misc
Corrective Action Required
08/09/2019
-FIRE DEPT APPROVAL REQUIRED -INSTALL NO SMOKING SIGNAGE AT FRONT -INSTALL SPARK RINGS FOR ALL ELECTRICAL BOXES RECESSED MORE THAN 1/4" BEHIND NON-COMBUSTIBLE WALL SURFACE -RECEPTACLES AT HAIR WASH SINKS MUST BE GFCI-PROTECTED -RECEPTACLE IN LAUNDRY RM LOCATED WITHIN SIX FT OF THE SINK MUST BE GFCI-PROTECTED -INSTALL ROOF FLASHING FOR THE 3" PLUMBING VENT PER CODE. CANNOT SIMPLY CAULK AROUND IT -INSTALL MIN CIRCUIT AMPACITY FOR THE RTU PER LABEL **OK TO STOCK ITEMS
Occupancy Inspection - Fire Passed 8/9/2019 8/9/2019 08/09/2019
Occupancy Inspection - Codes Commercial Temporary C of O 8/12/2019 8/12/2019 at 2:35 PM 08/12/2019
Misc
Corrective Action Required
08/09/2019
-INSTALL ROOF FLASHING FOR THE 3" PLUMBING VENT PER CODE. CANNOT SIMPLY CAULK AROUND IT
Occupancy Inspection - Codes Commercial Full C of O 8/15/2019 08/15/2019
Misc
Resolved
08/15/2019
-INSTALL ROOF FLASHING FOR THE 3" PLUMBING VENT PER CODE. CANNOT SIMPLY CAULK AROUND IT
Documents & Images
Date Uploaded File Type Document Name
06/10/2019 Letter Fire Building Plan Review
06/12/2019 Letter DS P/R Corrections Document
06/12/2019 Letter Fire Building Plan Review
06/17/2019 Letter Fire Building Plan Review
06/24/2019 Receipt Receipt for transaction: 2019-004039
06/24/2019 Letter Codes Plan Review Conditions
07/01/2019 Letter Codes Building Permit
07/01/2019 Letter License Tax Bill
07/09/2019 Letter INSPECTION SUMMARY
07/12/2019 Letter INSPECTION SUMMARY
07/15/2019 Letter INSPECTION SUMMARY
08/06/2019 Letter INSPECTION SUMMARY
08/09/2019 Letter INSPECTION SUMMARY
08/12/2019 Letter Codes Temporary Certificate of Occupancy
08/15/2019 Letter Codes Final Certificate of Occupancy
08/15/2019 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home