Summary
PRCOM20191115
Building Permit - Commercial
Final Completion
LAKEWOOD RANCH LLC
REPAIR REPLACE UPGRADE
ELECTRICAL SERVICE UPGRADE TO 200 AMP SERVICE--AND-- this is a NEW change of service with new meter can, 200amp 3 phase knife switch and new sub panel in the unit. After hours inspection with John Borns and MH. 10/28 pm for 4 hrs of time worked.
05/01/2019
05/01/2019
06/05/2020
Locations
Contacts
LAKEWOOD RANCH LLC, Address:605 W 47TH ST # 200  
LAKE ELECTRIC LLC, Address:1917 SPRUCE ST, Phone:(913) 490-8377  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 05/01/2019 05/01/2019
Development Center
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Repair/Replace/Upgrade $30.00 $30.00 Paid Not payable online 05/01/2019
Outstanding Fees Amount Paid Owing Date Paid
9110079-After Hours Inspection (Building Codes)(Per Hour) $200.00 $0.00 $200.00 Not Paid


$200.00    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Failed 10/28/2019 at 3:30 PM 10/28/2019
Misc
Corrective Action Required
10/28/2019
-SUBMIT ENGINEER PLAN TO CITY FOR THE UPGRADED SERVICE TO INCLUDE THE 200 AMP SERVICE DISCONNECT -COMPLETE SERVICE INSTALLATION (SUBPANEL, CONDUCTORS, ETC) -SHALL GROUND THE NEW 200 AMP SERVICE DISCONNECT WITH #4 COPPER GROUNDING ELECTRODE CONDUCTOR -THE 600 AMP SERVICE IS CURRENTLY NOT GROUNDED TO THE WATER SERVICE LINE -SHALL NOT GROUND THE SUBPANEL ON THE LOAD SIDE OF THE SERVICE DISCONNECT. ALL GROUNDING ELECTRODE CONDUCTORS SHALL GO TO AND GROUND THE MAIN SERVICE DISCONNECT
Electrical Service Inspection Partial 10/28/2019 at 7:00 AM 10/28/2019
Misc
Corrective Action Required
10/28/2019
-SUBMIT ENGINEER PLAN TO CITY FOR THE UPGRADED SERVICE TO INCLUDE THE 200 AMP SERVICE DISCONNECT -SHALL GROUND THE NEW 200 AMP SERVICE DISCONNECT WITH #4 COPPER GROUNDING ELECTRODE CONDUCTOR -THE 600 AMP SERVICE IS CURRENTLY NOT GROUNDED TO THE WATER SERVICE LINE -SHALL NOT GROUND THE SUBPANEL ON THE LOAD SIDE OF THE SERVICE DISCONNECT. ALL GROUNDING ELECTRODE CONDUCTORS SHALL GO TO AND GROUND THE MAIN SERVICE DISCONNECT
Misc
Partial Correction
10/28/2019
AS EMERGENCY MEASURE TO PRESERVE STORED FOOD NEW 200A SERVICE IS RELEASED FOR TEMPORARY ACTIVATION PENDING CONFORMING GROUNDING BEING ESTABLISHED AT MAIN DISCONNECT. THEN GROUNDING AT NEW SUB-PANEL IS TO BE REMOVED AND EXTENDED TO 200A DISCONNECT.
Miscellaneous Inspection Partial 10/28/2019 at 7:00 AM 10/29/2019
Misc
Corrective Action Required
10/29/2019
My phone contact with them began at 5:35 P.M. with Mike; then 5:55 and 6:56 with Dusty. I arrived there at 7:40 at their request but they were nowhere near done -- I waited on site for them to be ready for inspection. When you arrived after 8:00 they were marginally ready as you observed. After we inspected I got home about 9:45.
Final Electrical Inspection - Commercial Failed 10/29/2019 10/29/2019
Misc
Corrective Action Required
10/28/2019
**NOTE FOR EXISTING NON-COMPLIANCE: THE 600 AMP SERVICE HAS ONLY ONE SET OF 500 KCMIL AL SERVICE CONDUCTORS. IT WAS NOT PROPERLY GROUNDED. THE ELECTRICIAN INSTALLED A #4 CU GEC TO THE ROD LOCATED AT SOUTH SIDE OF THE BUILDING, ONE #4 CU GEC TO WATER LINE LOCATED IN THE RESTROOM, AND ONE #4 CU BONDING JUMPER TO BOND THE BUILDING COPPER WATER LINES -IN ORDER FOR THE 600 AMP SERVICE GROUNDING TO BE COMPLIANT WITH CODE, THE FOLLOWINGS MUST BE DONE: 1) INSTALL A 1/0 CU GEC TO THE WATER, BASED ON THE SIZE OF THE 500 KCMIL SERVICE CONDUCTORS (SEE EXISTING NON-COMPLIANCE ABOVE) 2)INSTALL A 1/0 CU BONDING JUMPER FROM THE TOP RIGHT BUS BAR WHERE THE NEW GECs ARE CONNECTED TO, TO THE BAR WHERE THE SERVICE GROUNDED CONDUCTOR IS CONNECTED TO.
Electrical Service Inspection Passed 10/29/2019
Misc
Resolved
10/29/2019
Misc
Resolved
10/29/2019
AS EMERGENCY MEASURE TO PRESERVE STORED FOOD NEW 200A SERVICE IS RELEASED FOR TEMPORARY ACTIVATION PENDING CONFORMING GROUNDING BEING ESTABLISHED AT MAIN DISCONNECT. THEN GROUNDING AT NEW SUB-PANEL IS TO BE REMOVED AND EXTENDED TO 200A DISCONNECT.
Miscellaneous Inspection Passed 1/15/2020 01/15/2020
Misc
Resolved
01/15/2020
My phone contact with them began at 5:35 P.M. with Mike; then 5:55 and 6:56 with Dusty. I arrived there at 7:40 at their request but they were nowhere near done -- I waited on site for them to be ready for inspection. When you arrived after 8:00 they were marginally ready as you observed. After we inspected I got home about 9:45.
Final Electrical Inspection - Commercial Passed 06/05/2020
Misc
Informational
06/05/2020
**THE OWNER SHOULD HAVE THE BELOW EXISTING NON-COMPLIANT DEFICIENCY BROUGHT UP TO CODE. WORK SHALL BE ON SEPARATE PERMIT **NOTE FOR EXISTING NON-COMPLIANCE: THE 600 AMP SERVICE HAS ONLY ONE SET OF 500 KCMIL AL SERVICE CONDUCTORS. IT WAS NOT PROPERLY GROUNDED. THE ELECTRICIAN INSTALLED A #4 CU GEC TO THE ROD LOCATED AT SOUTH SIDE OF THE BUILDING, ONE #4 CU GEC TO WATER LINE LOCATED IN THE RESTROOM, AND ONE #4 CU BONDING JUMPER TO BOND THE BUILDING COPPER WATER LINES IN ORDER FOR THE 600 AMP SERVICE GROUNDING TO BE COMPLIANT WITH CODE, THE FOLLOWINGS MUST BE DONE: 1) INSTALL A 1/0 CU GEC TO THE WATER, BASED ON THE SIZE OF THE 500 KCMIL SERVICE CONDUCTORS (SEE EXISTING NON-COMPLIANCE ABOVE) 2)INSTALL A 1/0 CU BONDING JUMPER FROM THE TOP RIGHT BUS BAR WHERE THE NEW GECs ARE CONNECTED TO, TO THE BAR WHERE THE SERVICE GROUNDED CONDUCTOR IS CONNECTED TO.
Documents & Images
Date Uploaded File Type Document Name
05/01/2019 Receipt Receipt for transaction: 2019-001702
05/01/2019 Letter Codes Building Permit
05/02/2019 Scope of Work DOC050219-05022019112308
10/18/2019 Letter Codes 140 Day Letter
10/28/2019 Letter INSPECTION SUMMARY
10/28/2019 Letter INSPECTION SUMMARY
10/29/2019 Letter INSPECTION SUMMARY
10/29/2019 Letter INSPECTION SUMMARY
06/05/2020 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home