Permit Application Status

PRCOM20190589


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20190589
Building Permit - Commercial
Certificate of Occupancy
DIOCESE OF KC-ST JOE REAL ESTATE CORP
ADDITION COMMERCIAL
ADDITION OF 2ND AND 3RD FLOOR CLASSROOMS TO EXISTING CHURCH
03/15/2019
05/31/2019
09/18/2019
06/17/2020
Locations
Contacts
DIOCESE OF KC-ST JOE REAL ESTATE CORP, Address:20 W NINTH ST  
OUR LADY OF PRESENTATION CHURCH, Address:130 NW MURRAY RD  
HOLLIS & MILLER ARCHITECTS, Address:1828 Walnut, Ste. 920, Phone:(816) 442-7700  
PM CONTRACTING INC, Address:4015 E 143RD ST, Phone:(816) 318-9844  
NORTH KANSAS CITY ELECTRIC CO INC, Address:PO BOX 12442, Phone:(816) 421-2352  
PM CONTRACTING INC, Address:4015 E 143RD ST, Phone:(816) 318-9844  
LYTLE CONSTRUCTION INC, Address:18505 E 163RD ST, Phone:(816) 524-7275  
DAN JEFFRIES, Address:LYTLE CONSTRUCTION, IN, Phone:(816) 524-7275  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 06/28/2019
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
06/28/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Action Required) Call (816)969-1300 to schedule a test. Test must be conducted before a final occupancy inspection.
Misc
Corrective Action Required
06/28/2019

(Action Required) Three smoke detectors added to second floor corridor. (See additional plan sheet attached to plans.)
Sprinkler Plan Review Released for Construction 06/26/2019
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
06/26/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Action Required) Call (816)969-1300 to schedule a hydrostatic test. Have a current inspection tag on the riser.
Final Development Plan Review Approved 05/30/2019
Joe Frogge
Licensed Contractors Approved 03/28/2019 05/14/2019
Mike Weisenborn
LC - MEP Subs
Corrective Action Required
03/28/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved with Conditions 04/04/2019 03/28/2019
Joe Frogge
Final Development Plan
Resolved
05/30/2019

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Bldg - Exit access stairway construction 1009.3.1
Resolved
03/28/2019

2012 IBC 1009.3.1 - Construction. Where required, enclosures for exit access stairway shall be constructed in accordance with this section. Exit access stairway enclosures shall be constructed as fire barriers in accordance with Section 707 or horizontal assemblies in accordance with Section 711, or both. Action required: Provide 1 hour separation (1009.3.1.2) at exit access stair or provide detailed analysis wherein a lack of fire separation is explicitly excepted.
Fire Plan Review Approved with Conditions 04/04/2019 03/28/2019
Joe Frogge
Construction documents for fire alarm systems
Corrective Action Required
03/28/2019

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the Fire alarm system contractor provide shop drawings of the modifications to be done to the fire alarm system.
Tenant identification
Corrective Action Required
03/28/2019

2012 IFC 408.11.2 - Tenant identification. Each occupied tenant space provided with a secondary exit to the exterior or exit corridor shall be provided with tenant identification by business name and/or address. Letters and numbers shall be posted on the corridor side of the door, be plainly legible and shall contrast with their background. ACTION REQUIRED:(verified at inspection) Each classroom, mechanical room, storage room, electrical room shall be identified off of the corridor with proper room designation labeling.
Locks on gates or barriers
Corrective Action Required
03/28/2019

2012 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. ACTION REQUIRED:(verified at inspection) All gates obstructing any access driveway to the building(s) shall have a knox padlock if it is a swing gate or a knox key switch if it is an electric gate. both knox padlocks and knox key switches can be obtained online at knobox.com
Construction documents - Fire protection systems
Corrective Action Required
03/28/2019

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings of the modifications to be done to the fire sprinkler system. Class 1 standpipes will be required for the exit access stairways. 905.4 Location of Class I standpipe hose connections. Class I standpipe hose connections shall be provided in all of the following locations: 1. In every required stairway, a hose connection shall be provided for each floor level above or below grade. Hose connections shall be located at an intermediate floor level landing between floors, unless otherwise approved by the fire code official.
Installation acceptance testing
Corrective Action Required
03/28/2019

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(Information purposes) All field tests and acceptance testing of the fire sprinkler and fire alarm systems is required to be completed prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Portable fire extinguishers - general
Corrective Action Required
03/28/2019

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide a minimum of one 2A-10BC fire extinguisher for every 3,000 square feet of useable space. The extinguishers are to mounted on walls or in extinguisher cabinets on a normal path of travel with an average travel distance of 75' to reach an extinguisher.
Miscellaneous Correction
Corrective Action Required
03/28/2019

Fire resistance rating ACTION REQUIRED: Exit access stairways shall be rated to a minimum of a one hour fire rating. [B] 1009.3.1.2 Fire-resistance rating. Exit access stairway enclosures shall have a fire-resistance rating of not less than 2 hours where connecting four stories or more, and not less than 1 hour where connecting less than four stories. The number of stories connected by the exit access stairway enclosures shall include any basements, but not any mezzanines. Exit access stairway enclosures shall have a fire-resistance rating not less than the floor assembly penetrated, but need not exceed 2 hours.
Miscellaneous Correction
Corrective Action Required
03/28/2019

Access controlled egress ACTION REQUIRED:(verified at inspection) All card reader access controlled egress doors shall unlock upon a fire alarm activation. [B] 1008.1.9.8 Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1 or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2, are permitted to be equipped with an approved entrance and egress access control system, listed in accordance with UL 294, which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public.
Stairway identification signs
Corrective Action Required
03/28/2019

2012 IFC (B) 1022.9 Stairway identification signs. A sign shall be provided at each floor landing in an interior exit stairway and ramp connecting more than three stories designating the floor level, the terminus of the top and bottom of the interior exit stairway and ramp and the identification of the stair or ramp. The signage shall also state the story of, and the direction to, the exit discharge and the availability of roof access from the interior exit stairway and ramp for the fire department. The sign shall be located 5 feet (1524mm) above the floor landing in a position that is readily visible when the doors are in the open an dclosed positions. In addition to the stairway identification sign, a floor-level sign in raised characters and Braille complying with the ICC A1 17.1 shall be located at each floor-level landing adjacent to the door leading from the interior exit stairway and ramp into the corridor to identify the floor level. 1022.9.1 Signage requirements. Stairway identification signs shall comply with all of the following requirements: 1. The signs shall be a minimum size of 18 inches (457 mm) by 12 inches (305 mm). 2. The letters designating the identification of the interior exit stairway and ramp shall be a minimum of 11/2 inches (38 mm) in height. 3. The number designating the floor level shall be a minimum of 5 inches (127 mm) in height and located in the center of the sign. 4. All other lettering and numbers shall be a minimum of 1 inch (25 mm) in height. 5. Characters and their background shall have a nonglare finish. Characters shall contrast with their background, with either light characters on a dark background or dark characters on a light background. 6. When signs required by Section 1022.9 are installed in the interior exit stairways and ramps of buildings subject to Section 1024, the signs shall be made of the same materials as required by Section 1024.4. ACTION REQUIRED: (verified at inspection) Provide stairway floor level signage at each floor level in the stairways.
Duct smoke detectors
Corrective Action Required
03/28/2019

2012 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. ACTION REQUIRED: Provide duct detection for AHU's producing over 2,000 CFM. Duct detection shall be monitored by the Fire alarm system.
Panic and fire exit hardware
Corrective Action Required
03/28/2019

2012 IFC 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. ACTION REQUIRED: Door schedule did not mention type of hardware for the egress doors. Provide panic hardware for all egress doors.
Illumination required
Corrective Action Required
03/28/2019

2012 IFC 1006.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. ACTION REQUIRED: Provide exterior emergency illumination at all exit discharges.
Fire Plan Review Rejected 03/29/2019 03/22/2019
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
03/22/2019

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the Fire alarm system contractor provide shop drawings of the modifications to be done to the fire alarm system.
Tenant identification
Corrective Action Required
03/22/2019

2012 IFC 408.11.2 - Tenant identification. Each occupied tenant space provided with a secondary exit to the exterior or exit corridor shall be provided with tenant identification by business name and/or address. Letters and numbers shall be posted on the corridor side of the door, be plainly legible and shall contrast with their background. ACTION REQUIRED:(verified at inspection) Each classroom, mechanical room, storage room, electrical room shall be identified off of the corridor with proper room designation labeling.
Locks on gates or barriers
Corrective Action Required
03/22/2019

2012 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. ACTION REQUIRED:(verified at inspection) All gates obstructing any access driveway to the building(s) shall have a knox padlock if it is a swing gate or a knox key switch if it is an electric gate. both knox padlocks and knox key switches can be obtained online at knobox.com
Construction documents - Fire protection systems
Corrective Action Required
03/22/2019

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings of the modifications to be done to the fire sprinkler system. Class 1 standpipes will be required for the exit access stairways. 905.4 Location of Class I standpipe hose connections. Class I standpipe hose connections shall be provided in all of the following locations: 1. In every required stairway, a hose connection shall be provided for each floor level above or below grade. Hose connections shall be located at an intermediate floor level landing between floors, unless otherwise approved by the fire code official.
Installation acceptance testing
Corrective Action Required
03/22/2019

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(Information purposes) All field tests and acceptance testing of the fire sprinkler and fire alarm systems is required to be completed prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Portable fire extinguishers - general
Corrective Action Required
03/22/2019

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide a minimum of one 2A-10BC fire extinguisher for every 3,000 square feet of useable space. The extinguishers are to mounted on walls or in extinguisher cabinets on a normal path of travel with an average travel distance of 75' to reach an extinguisher.
Miscellaneous Correction
Corrective Action Required
03/22/2019

Fire resistance rating ACTION REQUIRED: Exit access stairways shall be rated to a minimum of a one hour fire rating. [B] 1009.3.1.2 Fire-resistance rating. Exit access stairway enclosures shall have a fire-resistance rating of not less than 2 hours where connecting four stories or more, and not less than 1 hour where connecting less than four stories. The number of stories connected by the exit access stairway enclosures shall include any basements, but not any mezzanines. Exit access stairway enclosures shall have a fire-resistance rating not less than the floor assembly penetrated, but need not exceed 2 hours.
Miscellaneous Correction
Corrective Action Required
03/22/2019

Access controlled egress ACTION REQUIRED:(verified at inspection) All card reader access controlled egress doors shall unlock upon a fire alarm activation. [B] 1008.1.9.8 Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1 or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2, are permitted to be equipped with an approved entrance and egress access control system, listed in accordance with UL 294, which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public.
Stairway identification signs
Corrective Action Required
03/22/2019

2012 IFC (B) 1022.9 Stairway identification signs. A sign shall be provided at each floor landing in an interior exit stairway and ramp connecting more than three stories designating the floor level, the terminus of the top and bottom of the interior exit stairway and ramp and the identification of the stair or ramp. The signage shall also state the story of, and the direction to, the exit discharge and the availability of roof access from the interior exit stairway and ramp for the fire department. The sign shall be located 5 feet (1524mm) above the floor landing in a position that is readily visible when the doors are in the open an dclosed positions. In addition to the stairway identification sign, a floor-level sign in raised characters and Braille complying with the ICC A1 17.1 shall be located at each floor-level landing adjacent to the door leading from the interior exit stairway and ramp into the corridor to identify the floor level. 1022.9.1 Signage requirements. Stairway identification signs shall comply with all of the following requirements: 1. The signs shall be a minimum size of 18 inches (457 mm) by 12 inches (305 mm). 2. The letters designating the identification of the interior exit stairway and ramp shall be a minimum of 11/2 inches (38 mm) in height. 3. The number designating the floor level shall be a minimum of 5 inches (127 mm) in height and located in the center of the sign. 4. All other lettering and numbers shall be a minimum of 1 inch (25 mm) in height. 5. Characters and their background shall have a nonglare finish. Characters shall contrast with their background, with either light characters on a dark background or dark characters on a light background. 6. When signs required by Section 1022.9 are installed in the interior exit stairways and ramps of buildings subject to Section 1024, the signs shall be made of the same materials as required by Section 1024.4. ACTION REQUIRED: (verified at inspection) Provide stairway floor level signage at each floor level in the stairways.
Duct smoke detectors
Corrective Action Required
03/22/2019

2012 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. ACTION REQUIRED: Provide duct detection for AHU's producing over 2,000 CFM. Duct detection shall be monitored by the Fire alarm system.
Panic and fire exit hardware
Corrective Action Required
03/22/2019

2012 IFC 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. ACTION REQUIRED: Door schedule did not mention type of hardware for the egress doors. Provide panic hardware for all egress doors.
Illumination required
Corrective Action Required
03/22/2019

2012 IFC 1006.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. ACTION REQUIRED: Provide exterior emergency illumination at all exit discharges.
Building Plan Review Rejected 03/29/2019 03/22/2019
Joe Frogge
Final Development Plan
Corrective Action Required
03/20/2019

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Bldg - Exit access stairway construction 1009.3.1
Corrective Action Required
03/22/2019

2012 IBC 1009.3.1 - Construction. Where required, enclosures for exit access stairway shall be constructed in accordance with this section. Exit access stairway enclosures shall be constructed as fire barriers in accordance with Section 707 or horizontal assemblies in accordance with Section 711, or both. Action required: Provide 1 hour separation (1009.3.1.2) at exit access stair or provide detailed analysis wherein a lack of fire separation is explicitly excepted.
Licensed Contractors Rejected 03/29/2019 03/20/2019
Joe Frogge
LC - MEP Subs
Corrective Action Required
03/20/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Addition to Commercial $8,106.00 $8,106.00 Paid 05/23/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Above Ceiling Inspection Partial 8/12/2019 8/12/2019 at 7:15 AM 08/12/2019
Misc
Partial Correction
08/12/2019
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1ST FLOOR SPACES EXCEPT [124] & S ENTRANCE CORRIDOR; INSTALL NO CEILING TILE BEFORE ABOVE-CEILING INSPECTION EXCEPT THOSE FEW REQUIRED FOR MOUNTING OF DEVICES.
In-wall Inspection Failed 8/21/2019 at 8:05 AM 08/21/2019
Misc
Corrective Action Required
08/21/2019
2ND FLOOR: 3RD PARTY INSPECTION REPORT REQUIRED CERTIFYING ALL HOLD-DOWNS HAVE BEEN CHECKED AND APPROVED
Above Ceiling Inspection Partial 8/26/2019 8/26/2019 at 7:30 AM 08/26/2019
Misc
Partial Correction
08/12/2019
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1ST FLOOR SPACES INCLUDING CORRIDORS BUT EXCLUDING [124] ; INSTALL NO CEILING TILE BEFORE ABOVE-CEILING INSPECTION EXCEPT THOSE FEW REQUIRED FOR MOUNTING OF DEVICES.
In-wall Inspection Partial 8/30/2019 8/30/2019 at 7:20 AM 08/30/2019
Misc
Partial Correction
08/30/2019
OK TO COVER WHEN READY WALL FRAMING & SYSTEMS TO BE CONCEALED IN WALL CAVITIES AT: WEST STAIRWELL; 2ND FLOOR EXTERIOR WALLS ONLY; SPOT CHECK OF HOLD-DOWNS FOUND SOME NUTS NOT TIGHTENED. G.C. WAS INFORMED.
In-wall Inspection Partial 9/9/2019 9/9/2019 at 8:15 AM 09/09/2019
Misc
Partial Correction
08/30/2019
OK TO COVER WHEN READY WALL FRAMING & SYSTEMS TO BE CONCEALED IN WALL CAVITIES AT: WEST STAIRWELL; 2ND FLOOR EXTERIOR WALLS ONLY; 3RD FLOOR INTERIOR WALLS; SPOT CHECK OF HOLD-DOWNS FOUND SOME NUTS NOT TIGHTENED. G.C. WAS INFORMED.
Rated Assembly Inspection Partial 9/11/2019 9/11/2019 at 1:40 PM 09/11/2019
Misc
Partial Correction
09/11/2019
OK TO COVER WHEN READY COMPONENTS OF RATED ASSEMBLY AT: RETURN AIR CHASE AT CORRIDOR A201: 1ST LAYER 5/8" GWB; RETURN AIR CHASE AT CORRIDOR A301: 1ST LAYER 5/8" GWB;
Above Ceiling Inspection Partial 9/13/2019 9/13/2019 at 7:30 AM 09/13/2019
Misc
Partial Correction
08/26/2019
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1ST FLOOR SPACES INCLUDING CORRIDORS BUT EXCLUDING [124] ; INSTALL NO CEILING TILE BEFORE ABOVE-CEILING INSPECTION EXCEPT THOSE FEW REQUIRED FOR MOUNTING OF DEVICES.
Misc
Partial Correction
09/13/2019
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: CEILINGS AT WEST STAIRWELL @: 1ST FLOOR; 2ND FLOOR;
Rated Assembly Inspection Partial 9/18/2019 9/18/2019 at 8:20 AM 09/18/2019
Misc
Partial Correction
09/11/2019
OK TO COVER WHEN READY COMPONENTS OF RATED ASSEMBLY AT: RETURN AIR CHASE AT CORRIDOR A201: 1ST LAYER 5/8" GWB; 2ND LAYER 5/8" GWB; RETURN AIR CHASE AT CORRIDOR A301: 1ST LAYER 5/8" GWB; 2ND LAYER 5/8" GWB;
Above Ceiling Inspection Failed 10/23/2019 10/23/2019 at 8:15 AM 10/23/2019
Misc
Partial Correction
09/13/2019
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1ST FLOOR SPACES INCLUDING CORRIDORS BUT EXCLUDING [124] ; 2ND FLOOR: NOT READY FOR INSPECTION -- RUN LOW-VOLTAGE WIRING MINIMUM 18" ABOVE GRID BEFORE REQUESTING INSPECTION. INSTALL NO CEILING TILE BEFORE ABOVE-CEILING INSPECTION EXCEPT THOSE FEW REQUIRED FOR MOUNTING OF DEVICES.
Misc
Partial Correction
09/13/2019
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: CEILINGS AT WEST STAIRWELL @: 1ST FLOOR; 2ND FLOOR;
Above Ceiling Inspection Partial 10/25/2019 10/25/2019 at 2:55 PM 10/25/2019
Misc
Partial Correction
10/23/2019
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1ST FLOOR SPACES INCLUDING CORRIDORS BUT EXCLUDING [124] ; 2ND FLOOR COMPLETE; 3RD FLOOR EXCEPT STAIRWELL CEILING;
Misc
Partial Correction
10/23/2019
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: CEILINGS AT WEST STAIRWELL @: 1ST FLOOR; 2ND FLOOR;
In-wall Inspection Passed 11/6/2019 at 7:40 AM 11/06/2019
Misc
Resolved
11/06/2019
OK TO COVER WHEN READY WALL FRAMING & SYSTEMS TO BE CONCEALED IN WALL CAVITIES AT: WEST STAIRWELL; 2ND FLOOR EXTERIOR WALLS ONLY; 3RD FLOOR INTERIOR WALLS; SPOT CHECK OF HOLD-DOWNS FOUND SOME NUTS NOT TIGHTENED. G.C. WAS INFORMED.
Rated Assembly Inspection Passed 11/6/2019 at 7:25 AM 11/06/2019
Misc
Resolved
11/06/2019
OK TO COVER WHEN READY COMPONENTS OF RATED ASSEMBLY AT: RETURN AIR CHASE AT CORRIDOR A201: 1ST LAYER 5/8" GWB; 2ND LAYER 5/8" GWB; RETURN AIR CHASE AT CORRIDOR A301: 1ST LAYER 5/8" GWB; 2ND LAYER 5/8" GWB;
Miscellaneous Inspection Partial 11/6/2019 at 10:10 AM 11/06/2019
Miscellaneous Inspection Partial 11/8/2019 at 11:00 AM 11/08/2019
Above Ceiling Inspection Passed 11/13/2019 11/13/2019 at 7:35 AM 11/13/2019
Misc
Resolved
11/13/2019
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 1ST FLOOR SPACES INCLUDING CORRIDORS BUT EXCLUDING [124] ; 2ND FLOOR COMPLETE; 3RD FLOOR EXCEPT STAIRWELL CEILING;
Misc
Resolved
11/13/2019
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: CEILINGS AT WEST STAIRWELL @: 1ST FLOOR; 2ND FLOOR;
Miscellaneous Inspection Partial 11/18/2019 at 3:05 PM 11/18/2019
Sprinkler - Hydrostatic Test Passed 9/10/2019 12/16/2019
Alarm Test Passed 12/16/2019 12/16/2019
Occupancy Inspection - Fire Passed 12/16/2019 12/16/2019
Miscellaneous Inspection Passed 12/18/2019 at 7:10 AM 12/18/2019
Final Inspection - Commercial Partial 12/17/2019 12/18/2019 at 2:55 PM 12/18/2019
Misc
Corrective Action Required
12/18/2019
RESOLVE SITE CIVIL ISSUES.
Misc
Partial Correction
12/18/2019
OCCUPANCY STATUS: OK FOR USE AND OCCUPANCY THROUGH 12/31/2019 WHEREUPON RETAINING WALLS ARE TO BE COMPLETED AND APPROVED.
Occupancy Inspection - Planning Passed 12/18/2019 12/19/2019
Occupancy Inspection - Planning Passed 12/19/2019
Occupancy Inspection - Engineering Temporary C of O 12/18/2019 12/20/2019
Misc
Informational
12/20/2019
Still need to install the retaining wall. Everything else is complete. RP 12-18-19
Occupancy Inspection - Engineering Passed 05/14/2020
Misc
Informational
12/20/2019
Still need to install the retaining wall. Everything else is complete. RP 12-18-19
Occupancy Inspection - Codes Commercial Full C of O 05/14/2020
Misc
Corrective Action Required
12/18/2019
RESOLVE SITE CIVIL ISSUES.
Misc
Partial Correction
12/18/2019
OCCUPANCY STATUS: OK FOR USE AND OCCUPANCY THROUGH 12/31/2019 WHEREUPON RETAINING WALLS ARE TO BE COMPLETED AND APPROVED.
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home