Permit Application Status

PRCOM20182860


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20182860
Building Permit - Commercial
Certificate of Occupancy
SUMMIT NORTHRIDGE LLC
CHANGE OF TENANT
TENANT FINISH FOR A NEW RESTAURANT
08/27/2018
12/04/2018
04/29/2019
06/06/2019
Locations
Contacts
SUMMIT NORTHRIDGE LLC, Address:605 W 47TH ST STE 200  
B & A ARCHITECTURE, Address:100 W 31ST ST STE 100, Phone:(816) 753-6100  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
PAUL VIELHAUER PLUMBING INC, Address:6921 MARTINDALE RD, Phone:(913) 441-9400  
  
COMPLETE CONSTRUCTION SERVICES LLC, Address:14101 W 138TH TERR, Phone:(913) 800-7473  
MJ INTERIORS, Address:7915 HEMLOCK ST, Phone:(913) 313-6565  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 04/02/2019
Joe Dir
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
04/02/2019

2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ACTION REQUIRED:(verified at inspection) The existing fire sprinkler system riser shall be current with annual service. A current service tag shall be posted on the riser.
Fire Plan Review Approved with Conditions 11/30/2018 11/28/2018
Joe Dir
Posting of occupant load
Corrective Action Required
11/21/2018

2012 IFC 1004.3- Posting of occupant load. ACTION REQUIRED:(verified at inspection) Post the occupant load of 73 on a wall close to the main entrance.
Construction documents for fire alarm systems
Corrective Action Required
11/28/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of any modfications to be done to the existing fire alarm system. Kitchen hood supression system shall be wired into the buildings fire alarm system.
Address numbers required
Corrective Action Required
11/21/2018

2012 IFC 505.1- Address numbers. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Numeric address of 697 shall be readable from the roadway.
Construction documents - Fire protection systems
Corrective Action Required
11/21/2018

2012 IFC 901.2- Construction documents. The Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system and the Type 1 kitchen hood suppression systems contractors provide shop drawings of the modifications to be done to the fire sprinkler system and the Kitchen Hood system to be installed.
Installation acceptance testing
Corrective Action Required
11/21/2018

2012 IFC 901.5- Installation acceptance testing. ACTION REQUIRED:(information purposes) Acceptance testing of the fire alarm system modifications and Type 1 kitchen hoods will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
11/21/2018

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ACTION REQUIRED:(verified at inspection) Provide a K class fire extinguisher. The K class fire extinguisher is to be mounted under ot close to the manual pull station.
Portable fire extinguishers - general
Corrective Action Required
11/21/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide a minimum of two 2A-10BC fire extinguishers. The fire extinguishers are to be mounted on a wall close to an exit.
Misc
Corrective Action Required
11/21/2018

Solid fuel cooking ACTION REQUIRED:NFPA 96 Chapter 14 solid fuel cooking. 14.7.9 Hose protection 14.7.9.1 Solid fuel cooking appliances with fireboxes exceeding 5 cubic feet shall be provided with a fixed water pipe system with a hose in the kitchen capable of reaching the firebox. 14.7.9.1.2 The hose shall be equipped with a nozzel capable of producing a fine to medium spry or mist. ACTION REQUIRED: The Tandoor Oven fire box exceeds 5 cubic feet. Provide information about where the required water hose and nozzel will be placed in the kitchen.
Misc
Corrective Action Required
11/28/2018

Knox Box Comment plan sheet A102 fire protection notes. A Knox Box is not required for this business. The building has a Knox Box that was previously installed.
Licensed Contractors Approved 11/21/2018 11/26/2018
Joe Frogge
LC - General Contractor
Resolved
11/26/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 10/15/18 - Acknowledged in letter.
LC - MEP Subs
Resolved
11/26/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/15/18 - Acknowledged in letter.
Building Plan Review Approved with Conditions 11/30/2018 11/26/2018
Joe Frogge
License Tax Application
Corrective Action Required
11/21/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 10/30/18 - acknowledged in letter
Health Dept Inspection
Corrective Action Required
11/21/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 10/30/18 - acknowledged in letter
Misc
Resolved
11/26/2018

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide convenience power with 25' of all new rooftop equipment. 10/15/18 - Provide for makeup air unit also. 10/30/18 - Letter says to reference new M1 but we are unable to find the additional receptacle.
Misc
Resolved
11/26/2018

2012 IMC 917.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles and barbecues, shall be listed, labeled and installed in accordance with the manufacturer’s installation instructions. Commercial electric cooking appliances shall be listed and labeled in accordance with UL 197. Household electric ranges shall be listed and labeled in accordance with UL 858. Microwave cooking appliances shall be listed and labeled in accordance with UL 923. Oil burning stoves shall be listed and labeled in accordance with UL 896. Solid-fuel-fired ovens shall be listed and labeled in accordance with UL 2162. Action required: Provide verification that charcoal-fired oven will be compliant with UL 2162. 10/15/18 - Tandoor oven cut sheets provided do not show that they are compliant.
Fire Plan Review Rejected 11/01/2018 10/31/2018
Joe Dir
Posting of occupant load
Corrective Action Required
10/25/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(veriifed at inspection)
Construction documents for fire alarm systems
Corrective Action Required
10/25/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of any modfications to be done to the existing fire alarm system.
Address numbers required
Corrective Action Required
10/25/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(veriifed at inspection) Address shall be readable from the roadway
Construction documents - Fire protection systems
Corrective Action Required
10/25/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings of the modifications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
10/25/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the fire alarm system modifications and Type 1 kitchen hoods will be required prior to the final occupancy inspection. Contact the fire department to chedule testing. (816)969-1300
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
10/25/2018

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ACTION REQUIRED:(verified at inspection) Provide a K class fire extinguisher. The K class fire extinguisher is to be mounted under ot close to the manual pull station.
Portable fire extinguishers - general
Corrective Action Required
10/25/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide a minimum of two 2A-10BC fire extinguishers. The fire extinguishers are to be mounted on a wall close to an exit.
Misc
Corrective Action Required
10/25/2018

Solid fuel cooking ACTION REQUIRED: Reference the following and provide information on how the requirements will be addressed for the solid fuel cooking Tandoor oven. NFPA 96 Chapter 14 solid fuel cooking 14.3-hoods for solid fuel cooking 14.4 Exhaust for solid fuel cooking 14.6 Air movement for solid fuel cooking 14.7 Fire -extinguishing Equipment for solid fuel cooking. 14.7.9 Hose protection 14.9 Minimum Safety Requirements (all sections): Fuel storage, handling, and ash removal for solid fuel cooking
Building Plan Review Rejected 11/01/2018 10/30/2018
Joe Frogge
License Tax Application
Corrective Action Required
10/25/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 10/30/18 - acknowledged in letter
Health Dept Inspection
Corrective Action Required
10/25/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 10/30/18 - acknowledged in letter
Misc
Resolved
10/30/2018

Inadequate information to complete review. Provide the following: - - Specify hood fan locations. 10/15/18 - Exhausts are not allowed to be within 10' of intakes. (ref: 2012 IMC 501.3.1) - - Provide detailed and complete hood designs. 10/15/18 - Only 1 copy found in submittal. Provide 2 more copies.
Misc
Corrective Action Required
10/25/2018

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide convenience power with 25' of all new rooftop equipment. 10/15/18 - Provide for makeup air unit also. 10/30/18 - Letter says to reference new M1 but we are unable to find the additional receptacle.
Misc
Corrective Action Required
11/14/2018

2012 IMC 917.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles and barbecues, shall be listed, labeled and installed in accordance with the manufacturer’s installation instructions. Commercial electric cooking appliances shall be listed and labeled in accordance with UL 197. Household electric ranges shall be listed and labeled in accordance with UL 858. Microwave cooking appliances shall be listed and labeled in accordance with UL 923. Oil burning stoves shall be listed and labeled in accordance with UL 896. Solid-fuel-fired ovens shall be listed and labeled in accordance with UL 2162. Action required: Provide verification that charcoal-fired oven will be compliant with UL 2162. 10/15/18 - Tandoor oven cut sheets provided do not show that they are compliant.
Licensed Contractors Rejected 10/25/2018 10/30/2018
Joe Frogge
LC - General Contractor
Corrective Action Required
10/25/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 10/15/18 - Acknowledged in letter.
LC - MEP Subs
Corrective Action Required
10/25/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/15/18 - Acknowledged in letter.
Building Plan Review Rejected 10/16/2018 10/15/2018
Joe Frogge
License Tax Application
Corrective Action Required
10/09/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
10/09/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Misc
Resolved
10/15/2018

2012 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load imposed by new equipment. 10/15/18 - Drawings have been noted to provide engineer's report but the report has not been received.
Screening - Rooftop equipment
Resolved
10/15/2018

Unified Development Ordinance Article 7, Section 7.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section. 10/15/18 - Per architect, existing parapets are adequate.
Code analysis required
Resolved
10/15/2018

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Revise cover sheet and A100 to show correct accessibility code which is ICC/ANSI A117.1-2009.
Bldg - Occupant load posting 1004.3
Resolved
10/15/2018

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Posting of occupant load (74) required.
Bldg - Toilet room wall finish 1210.2.2
Resolved
10/15/2018

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish materials at toilet rooms and mop sink. If paint is used it must be epoxy based.
Misc
Corrective Action Required
10/09/2018

Inadequate information to complete review. Provide the following: - - Specify hood fan locations. 10/15/18 - Exhausts are not allowed to be within 10' of intakes. (ref: 2012 IMC 501.3.1) - - Provide detailed and complete hood designs. 10/15/18 - Only 1 copy found in submittal. Provide 2 more copies.
Mech - Commercial kitchen hoods - Where required 507.2
Resolved
10/15/2018

2012 IMC 507.2 Where Required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliance under a single hood requires a Type I hood, a Type I hood shall be installed. Where a Type II hood is required, a Type I or Type II hood shall be installed. Exception: Where cooking appliances are equipped with integral down-draft exhaust systems and such appliances and exhaust systems are listed and labeled for the application in accordance with NFPA 96, a hood shall not be required at or above them. Action required: Provide Type II hood to serve dishwasher or provide verification that HVAC system has been sized to compensate the additional heat and humidity.
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Resolved
10/15/2018

2012 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Modify design of point of service counter. At least 36" of counter length to be maximum 36" high.
Misc
Corrective Action Required
10/09/2018

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide convenience power with 25' of all new rooftop equipment. 10/15/18 - Provide for makeup air unit also.
Misc
Corrective Action Required
10/09/2018

2012 IMC 917.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles and barbecues, shall be listed, labeled and installed in accordance with the manufacturer’s installation instructions. Commercial electric cooking appliances shall be listed and labeled in accordance with UL 197. Household electric ranges shall be listed and labeled in accordance with UL 858. Microwave cooking appliances shall be listed and labeled in accordance with UL 923. Oil burning stoves shall be listed and labeled in accordance with UL 896. Solid-fuel-fired ovens shall be listed and labeled in accordance with UL 2162. Action required: Provide verification that charcoal-fired oven will be compliant with UL 2162. 10/15/18 - Tandoor oven cut sheets provided do not show that they are compliant.
Licensed Contractors Rejected 10/16/2018 10/15/2018
Joe Frogge
LC - General Contractor
Corrective Action Required
10/09/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 10/15/18 - Acknowledged in letter.
LC - MEP Subs
Corrective Action Required
10/09/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/15/18 - Acknowledged in letter.
Fire Plan Review Rejected 10/16/2018 10/10/2018
Joe Dir
Posting of occupant load
Corrective Action Required
10/09/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(veriifed at inspection)
Construction documents for fire alarm systems
Corrective Action Required
10/09/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of any modfications to be done to the existing fire alarm system.
Address numbers required
Corrective Action Required
10/09/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(veriifed at inspection) Address shall be readable from the roadway
Type I hood - Where required
Resolved
10/10/2018

2012 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. ACTION REQUIRED: Have the hood suppression system contractor provide specs on the Type-1 hood suppression system to be installed.
Construction documents - Fire protection systems
Corrective Action Required
10/09/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings of the modifications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
10/09/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the fire alarm system modifications and Type 1 kitchen hoods will be required prior to the final occupancy inspection. Contact the fire department to chedule testing. (816)969-1300
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
10/09/2018

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ACTION REQUIRED:(verified at inspection) Provide a K class fire extinguisher. The K class fire extinguisher is to be mounted under ot close to the manual pull station.
Portable fire extinguishers - general
Corrective Action Required
10/09/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide a minimum of two 2A-10BC fire extinguishers. The fire extinguishers are to be mounted on a wall close to an exit.
Misc
Resolved
10/10/2018

Door operations ACTION REQUIRED: (verified at inspection) No keyed locks on the egress side of an exit
Misc
Resolved
10/10/2018

Exit signage/emergency lighting ACTION REQUIRED: Provide additional exit signage and emergency lighting at the back corridors intersection with indicators directing the egress travel to the rear exit. [B] 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit or the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Misc
Resolved
10/10/2018

AHU/HVAC ACTION REQUIRED: Provide information about the CFM production of the AHU's. Duct detection may be required.
Misc
Resolved
10/10/2018

Tandoor Oven ACTION REQUIRED: Provide manufactures specs on the installation and ventilation of the type and model to be installed.
Misc
Corrective Action Required
10/09/2018

Solid fuel cooking ACTION REQUIRED: Reference the following and provide information on how the requirements will be addressed for the solid fuel cooking Tandoor oven. NFPA 96 Chapter 14 solid fuel cooking 14.3-hoods for solid fuel cooking 14.4 Exhaust for solid fuel cooking 14.6 Air movement for solid fuel cooking 14.7 Fire -extinguishing Equipment for solid fuel cooking. 14.7.9 Hose protection 14.9 Minimum Safety Requirements (all sections): Fuel storage, handling, and ash removal for solid fuel cooking
Health Department Review Approved 10/02/2018
Joe Frogge
Building Plan Review Rejected 09/07/2018 08/31/2018
Joe Frogge
License Tax Application
Corrective Action Required
09/05/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Review
Resolved
10/02/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
09/05/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
09/05/2018

2012 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load imposed by new equipment.
Screening - Rooftop equipment
Corrective Action Required
09/05/2018

Unified Development Ordinance Article 7, Section 7.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Code analysis required
Corrective Action Required
09/05/2018

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Revise cover sheet and A100 to show correct accessibility code which is ICC/ANSI A117.1-2009.
Bldg - Occupant load posting 1004.3
Corrective Action Required
09/05/2018

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Posting of occupant load (74) required.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
09/05/2018

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish materials at toilet rooms and mop sink. If paint is used it must be epoxy based.
Misc
Corrective Action Required
09/05/2018

Inadequate information to complete review. Provide the following: - Specify all wall construction. (designations missing) - Specify hood fan locations. - Specify NG materials. - Provide detailed and complete hood designs.
Mech - Commercial kitchen hoods - Where required 507.2
Corrective Action Required
09/05/2018

2012 IMC 507.2 Where Required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliance under a single hood requires a Type I hood, a Type I hood shall be installed. Where a Type II hood is required, a Type I or Type II hood shall be installed. Exception: Where cooking appliances are equipped with integral down-draft exhaust systems and such appliances and exhaust systems are listed and labeled for the application in accordance with NFPA 96, a hood shall not be required at or above them. Action required: Provide Type II hood to serve dishwasher or provide verification that HVAC system has been sized to compensate the additional heat and humidity.
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Corrective Action Required
09/05/2018

2012 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Modify design of point of service counter. At least 36" of counter length to be maximum 36" high.
Misc
Corrective Action Required
09/05/2018

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide convenience power with 25' of all new rooftop equipment.
Misc
Corrective Action Required
09/05/2018

2012 IMC 917.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles and barbecues, shall be listed, labeled and installed in accordance with the manufacturer’s installation instructions. Commercial electric cooking appliances shall be listed and labeled in accordance with UL 197. Household electric ranges shall be listed and labeled in accordance with UL 858. Microwave cooking appliances shall be listed and labeled in accordance with UL 923. Oil burning stoves shall be listed and labeled in accordance with UL 896. Solid-fuel-fired ovens shall be listed and labeled in accordance with UL 2162. Action required: Provide verification that charcoal-fired oven will be compliant with UL 2162.
Licensed Contractors Rejected 09/07/2018 08/31/2018
Joe Frogge
LC - General Contractor
Corrective Action Required
08/31/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
08/31/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 09/07/2018 08/28/2018
Joe Dir
Posting of occupant load
Corrective Action Required
08/28/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(veriifed at inspection) Occupant load should be posted in the dining area close to the entrance.
Construction documents for fire alarm systems
Corrective Action Required
08/28/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of any modfications to be done to the existing fire alarm system.
Address numbers required
Corrective Action Required
08/28/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(veriifed at inspection) Address shall be readable from the roadway
Type I hood - Where required
Corrective Action Required
08/28/2018

2012 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. ACTION REQUIRED: Provide manufactures specs on the Type-1 hood and suppression system to be installed. Include a drawings showing the Type 1 kitchen hood exhaust system.
Construction documents - Fire protection systems
Corrective Action Required
08/28/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings of the modifications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
08/28/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the fire alarm system modifications and Type 1 kitchen hoods will be required prior to the final occupancy inspection. Contact the fire department to schedule to schedule testing. (816)969-1300
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
08/28/2018

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ACTION REQUIRED:(veriifed at inspection) Provide a K class fire extinguisher. The K class fire extinguisher is to be mounted under ot close to the manual pull station.
Portable fire extinguishers - general
Corrective Action Required
08/28/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide a minimum of two 2A-10BC fire extinguishers. The fire extinguishers are to be mounted on a wall close to an exit.
Misc
Corrective Action Required
08/28/2018

Door operations ACTION REQUIRED: No keyed locks on the egress side of an exit [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort Exit Door Hardware ACTION REQUIRED: [B] 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware.
Misc
Corrective Action Required
08/28/2018

Exit signage/emergency lighting ACTION REQUIRED: Provide additional exit signage and emergency lighting at the back corridors intersection with indicators directing the egress travel to the rear exit. [B] 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit or the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Misc
Corrective Action Required
08/28/2018

AHU/HVAC ACTION REQUIRED: Provide information about the CFM production of the AHU's. Duct detection may be required.
Misc
Corrective Action Required
08/28/2018

Tandoor Oven ACTION REQUIRED: Provide manufactures specs on the installation and ventilation of the type and model to be installed.
Misc
Corrective Action Required
08/28/2018

Solid fuel cooking ACTION REQUIRED: Reference the following and provide information on how the requirements will be addressed for the solid fuel cooking Tandoor oven. NFPA 96 Chapter 14 solid fuel cooking 14.3-hoods for solid fuel cooking 14.4 Exhaust for solid fuel cooking 14.6 Air movement for solid fuel cooking 14.7 Fire -extinguishing Equipment for solid fuel cooking. 14.7.9 Hose protection 14.9 Minimum Safety Requirements (all sections): Fuel storage, handling, and ash removal for solid fuel cooking
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $480.00 $480.00 Paid 12/04/2018
8331507-Sewer Connection Fee $270.00 $270.00 Paid 12/04/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 1/14/2019 1/14/2019 at 7:45 AM 01/14/2019
Misc
Corrective Action Required
01/14/2019
CONFIGURATION HAS BEEN MODIFIED. SUBMIT REVISION TO LS PLAN REVIEW.
Misc
Corrective Action Required
01/14/2019
CHECK & REPAIR CUT UNDER-SLAB ELECTRICAL CONDUIT (AND CABLE?).
Misc
Corrective Action Required
01/14/2019
EXPOSE SANITARY CONNECTION TO BUILDING DRAIN
Underslab Plumbing Inspection - Commercial Passed 1/15/2019 at 10:15 AM 01/15/2019
Misc
Resolved
01/15/2019
CONFIGURATION HAS BEEN MODIFIED. SUBMIT REVISION TO LS PLAN REVIEW.
Misc
Resolved
01/15/2019
CHECK & REPAIR CUT UNDER-SLAB ELECTRICAL CONDUIT (AND CABLE?).
Misc
Resolved
01/15/2019
EXPOSE SANITARY CONNECTION TO BUILDING DRAIN
In-wall Inspection Passed 3/21/2019 3/21/2019 at 8:50 AM 03/21/2019
Above Ceiling Inspection Partial 3/21/2019 at 9:20 AM 03/21/2019
Misc
Partial Correction
03/21/2019
OK TO COVER WHEN READY GWB BULKHEAD FRAMING & SYSTEMS TO BE ENCLOSED
Hood/Duct Inspection Partial 4/3/2019 4/3/2019 at 1:00 PM 04/03/2019
Hood/Duct Inspection Partial 4/3/2019 at 2:30 PM 04/03/2019
Misc
Partial Correction
04/03/2019
TWO SS GREASE DUCTS INSTALLED FROM HOOD TO ROOF. 1ST LAYER FIRE WRAP APPLIED TO NORTH DUCT -- OK TO APPLY 2ND LAYER.
Hood/Duct Inspection Partial 4/4/2019 at 9:00 AM 04/04/2019
Misc
Partial Correction
04/03/2019
TWO SS GREASE DUCTS INSTALLED FROM HOOD TO ROOF. 1ST LAYER FIRE WRAP APPLIED TO NORTH DUCT -- OK TO APPLY 2ND LAYER; 2ND LAYER APPROVED
Misc
Corrective Action Required
04/04/2019
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Gas Piping Inspection - Commercial Failed 5/7/2019 5/7/2019 at 10:20 AM 05/07/2019
Gas Piping Inspection - Commercial Passed 5/7/2019 at 11:25 AM 05/07/2019
Above Ceiling Inspection Partial 5/9/2019 5/9/2019 at 11:00 AM 05/09/2019
Misc
Partial Correction
03/21/2019
OK TO COVER WHEN READY GWB BULKHEAD FRAMING & SYSTEMS TO BE ENCLOSED ALL APPROVED TO DROP EXCEPT RESTROOM. INSTALL COPPER TUBING FOR PRESSURE RELIEF VALVE TO EXTEND TO WITHIN 6" OF FLOOR OR PAN SURFACE.
Above Ceiling Inspection Partial 5/10/2019 5/10/2019 at 8:45 AM 05/10/2019
Misc
Partial Correction
05/09/2019
OK TO COVER WHEN READY GWB BULKHEAD FRAMING & SYSTEMS TO BE ENCLOSED ALL APPROVED TO DROP EXCEPT RESTROOM. INSTALL COPPER TUBING FOR PRESSURE RELIEF VALVE TO EXTEND TO WITHIN 6" OF FLOOR OR PAN SURFACE.
Above Ceiling Inspection Partial 5/13/2019 at 8:20 AM 05/13/2019
Misc
Partial Correction
05/10/2019
OK TO COVER WHEN READY GWB BULKHEAD FRAMING & SYSTEMS TO BE ENCLOSED ALL APPROVED TO DROP EXCEPT RESTROOM. INSTALL COPPER TUBING FOR PRESSURE RELIEF VALVE TO EXTEND TO WITHIN 6" OF FLOOR OR PAN SURFACE.
Above Ceiling Inspection Passed 5/14/2019 5/14/2019 at 7:10 AM 05/14/2019
Misc
Resolved
05/14/2019
OK TO COVER WHEN READY GWB BULKHEAD FRAMING & SYSTEMS TO BE ENCLOSED ALL APPROVED TO DROP EXCEPT RESTROOM. INSTALL COPPER TUBING FOR PRESSURE RELIEF VALVE TO EXTEND TO WITHIN 6" OF FLOOR OR PAN SURFACE.
Miscellaneous Inspection Partial 5/15/2019 05/15/2019
Miscellaneous Inspection Partial 5/17/2019 at 1:15 PM 05/17/2019
Alarm Test Passed 5/21/2019 05/21/2019
Alternate Protection Systems Inspection Passed 5/21/2019 05/21/2019
Hood/Duct Inspection Partial 5/22/2019 at 8:15 AM 05/22/2019
Misc
Partial Correction
04/04/2019
TWO SS GREASE DUCTS INSTALLED FROM HOOD TO ROOF. 1ST LAYER FIRE WRAP APPLIED TO NORTH DUCT -- OK TO APPLY 2ND LAYER; 2ND LAYER APPROVED
Misc
Corrective Action Required
04/04/2019
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Miscellaneous Inspection Passed 05/22/2019
Occupancy Inspection - Codes Commercial Failed 5/22/2019 5/22/2019 at 1:25 PM 05/22/2019
Misc
Corrective Action Required
05/22/2019
NEC 600.3 UL LISTING OF EXTERIOR LIGHTED SIGNS / DECORATIVE ELEMENTS: IF INTERNALLY LIGHTED, MUST BE UL SHOP-LABELED AS INDICATION OF LISTING. NEC 600.4 ELECTRIC SIGN MARKINGS: SIGNS AND OUTSIDE LIGHTING SYSTEMS SHALL BE SHOP-LABELED WITH LISTING, MANUFACTURER'S NAME, TRADEMARK, OR OTHER MEANS OF IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING.
Misc
Corrective Action Required
05/22/2019
18" VERTICAL GRAB BAR AT WOMENS' RESTROOM MOUNTED LOWER THAN 39"-41" AFF TO BOTTOM
Misc
Corrective Action Required
05/22/2019
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF
Misc
Corrective Action Required
05/22/2019
SEAL BOTTOM OF WATER CLOSETS TO FLOOR.
Misc
Corrective Action Required
05/22/2019
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. STAFFING, TRAINING, FIXTURING, STOCKING OK. NO PUBLIC OR CUSTOMERS PRIOR TO APPROVAL.
Occupancy Inspection - Fire Passed 5/22/2019 05/22/2019
Hood/Duct Inspection Passed 5/24/2019 at 7:30 AM 05/24/2019
Misc
Resolved
05/24/2019
TWO SS GREASE DUCTS INSTALLED FROM HOOD TO ROOF. 1ST LAYER FIRE WRAP APPLIED TO NORTH DUCT -- OK TO APPLY 2ND LAYER; 2ND LAYER APPROVED
Misc
Resolved
05/24/2019
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Occupancy Inspection - Codes Commercial Partial 5/24/2019 at 7:40 AM 05/24/2019
Misc
Corrective Action Required
05/22/2019
NEC 600.3 UL LISTING OF EXTERIOR LIGHTED SIGNS / DECORATIVE ELEMENTS: IF INTERNALLY LIGHTED, MUST BE UL SHOP-LABELED AS INDICATION OF LISTING. NEC 600.4 ELECTRIC SIGN MARKINGS: SIGNS AND OUTSIDE LIGHTING SYSTEMS SHALL BE SHOP-LABELED WITH LISTING, MANUFACTURER'S NAME, TRADEMARK, OR OTHER MEANS OF IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING.
Misc
Resolved
05/24/2019
18" VERTICAL GRAB BAR AT WOMENS' RESTROOM MOUNTED LOWER THAN 39"-41" AFF TO BOTTOM
Misc
Resolved
05/24/2019
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF
Misc
Resolved
05/24/2019
SEAL BOTTOM OF WATER CLOSETS TO FLOOR.
Misc
Corrective Action Required
05/22/2019
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. STAFFING, TRAINING, FIXTURING, STOCKING OK. NO PUBLIC OR CUSTOMERS PRIOR TO APPROVAL.
Occupancy Inspection - Codes Commercial Temporary C of O 5/24/2019 at 3:10 PM 05/24/2019
Misc
Corrective Action Required
05/24/2019
NEC 600.4 ELECTRIC SIGN MARKINGS: SIGNS AND OUTSIDE LIGHTING SYSTEMS SHALL BE SHOP-LABELED WITH LISTING, MANUFACTURER'S NAME, TRADEMARK, OR OTHER MEANS OF IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING.
Misc
Resolved
05/24/2019
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. STAFFING, TRAINING, FIXTURING, STOCKING OK. NO PUBLIC OR CUSTOMERS PRIOR TO APPROVAL.
Occupancy Inspection - Codes Commercial Full C of O 6/6/2019 at 11:00 AM 06/06/2019
Misc
Resolved
06/06/2019
NEC 600.4 ELECTRIC SIGN MARKINGS: SIGNS AND OUTSIDE LIGHTING SYSTEMS SHALL BE SHOP-LABELED WITH LISTING, MANUFACTURER'S NAME, TRADEMARK, OR OTHER MEANS OF IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING.
Documents & Images
Date Uploaded File Type Document Name
08/29/2018 Letter Fire Building Plan Review
09/05/2018 Letter Codes P/R Corrections Document
10/02/2018 New Food Establishment Plan Review - Approved FTG 0001478
10/10/2018 Letter Fire Building Plan Review
10/15/2018 Letter Codes P/R Corrections Document
10/31/2018 Letter Fire Building Plan Review
10/31/2018 Letter Codes P/R Corrections Document
11/28/2018 Letter Fire Building Plan Review
11/28/2018 Letter Codes Plan Review Conditions
12/04/2018 Receipt Receipt for transaction: 2018-007435
12/04/2018 Letter Codes Building Permit
01/14/2019 Letter INSPECTION SUMMARY
01/15/2019 Letter INSPECTION SUMMARY
01/24/2019 2
03/21/2019 Letter INSPECTION SUMMARY
03/21/2019 Letter INSPECTION SUMMARY
04/02/2019 Letter Fire (Sprinkler) Plan Review
04/03/2019 Letter INSPECTION SUMMARY
04/04/2019 Letter INSPECTION SUMMARY
05/07/2019 Letter INSPECTION SUMMARY
05/09/2019 Letter INSPECTION SUMMARY
05/14/2019 Letter INSPECTION SUMMARY
05/22/2019 Letter INSPECTION SUMMARY
05/24/2019 Letter INSPECTION SUMMARY
05/24/2019 Letter INSPECTION SUMMARY
05/24/2019 Letter Codes Temporary Certificate of Occupancy
06/06/2019 Letter Field Certificate of Occupancy
06/14/2019 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home