Permit Application Status

PRCOM20182022


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20182022
Building Permit - Commercial
Final Completion
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
ALTERATIONS TO ACCOMMODATE RELOCATING MEDICAL OFFICES FROM 1ST TO 3RD FLOOR AS WELL AS INCREASE SIZE OF MEDICAL STAFF LOUNGE ON 1ST FLOOR
06/27/2018
07/17/2018
04/21/2019
10/26/2018
Locations
Contacts
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
MCCARTHY BUILDING COMPANIES INC, Address:12851 MANCHESTER RD, Phone:(314) 646-4179  
ACI BOLAND, Address:1421 EAST 104TH ST; SUITE 100, Phone:(816) 763-9600  
RAND CONSTRUCTION COMPANY, Address:1428 W 9TH ST, Phone:(816) 421-4143  
CAPITAL ELECTRIC CONSTRUCTION INC, Address:PO BOX 410079, Phone:(913) 335-1214  
RAND CONSTRUCTION COMPANY, Address:1428 W 9TH ST, Phone:(816) 421-4143  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 07/26/2018
Joe Dir
Alarm Plan Review Released for Construction 07/23/2018
Joe Dir
Installation acceptance testing
Corrective Action Required
07/23/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the modification to the fire alarm system will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Building Plan Review Approved 07/18/2018 07/17/2018
Joe Frogge
License Tax Application
Corrective Action Required
07/11/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 7/10/18 - Acknowledged.
Bldg - Exits and exit access doorways 1015.1
Resolved
07/17/2018

2012 IBC 1015.1 – Exits or exit access doorways from spaces. Two exits or exit access doorways from any space shall be provided where one of the following conditions exists: 1. The occupant load of the space exceeds one of the values in Table 1015.1. 2. The common path of egress travel exceeds one of the limitations of Section 1014.3. 3. Where required by Section 1015.3, 1015.4, 1015.5 or 1015.6. Where a building contains mixed occupancies, each individual occupancy shall comply with the applicable requirements for that occupancy. Where applicable, cumulative occupant loads from adjacent occupancies shall be considered in accordance with the provisions of Section 1004.1. Action required: Given that occupant load in room 1A098 exceeds 50, (1 occ per 15sf - loose tables & chairs) 2 exits will be required with appropriate spacing, exit/emergency lighting, outswinging doors, etc. 7/10/18 - Exit lighting design must also be modified. (not included with submittal received.
Health Dept Review
Resolved
07/25/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes and applies to kitchen type facilities in lounge. 7/10/18 - Submittal deferred per request.
Health Dept Inspection
Corrective Action Required
07/11/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes and applies to kitchen type facilities in lounge. 7/10/18 - Acknowledged.
Misc
Resolved
07/11/2018

2012 IMC 501.3 Exhaust discharge. The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a nuisance and not less than the distances specified in Section 501.3.1. The air shall be discharged to a location from which it cannot again be readily drawn in by a ventilating system. Air shall not be exhausted into an attic or crawl space. (see code for exceptions) Action required: Restroom exhaust appears to connect to a return air duct. Modify or clarify.
Fire Plan Review Approved with Conditions 07/18/2018 07/12/2018
Joe Dir
Misc
Corrective Action Required
07/11/2018

Door operation ACTION REQUIRED:(verified at inspection) All electronically lock and access controlled doors shall unlock in the event of a power loss and or an activation of the fire alarm system.
Construction documents for fire alarm systems
Corrective Action Required
07/11/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED: (information purposes) Have the fire alarm system contractor provide shop drawings of any modifications to be done to the fire alrm system.
Construction documents - Fire protection systems
Corrective Action Required
07/11/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(informastion purposes) Have the fire sprinkler system contractor provide shop drawings of any modfications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
07/11/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing will be required prior to the final occupancy inspection for any fire alarm system devices that are disconnected, relocated or installed new. Contact the fire department to schedule testing. (816)969-1300.
Licensed Contractors Approved 07/11/2018 07/11/2018
Joe Frogge
Fire Plan Review Approved with Conditions 07/10/2018 07/03/2018
Joe Dir
Misc
Corrective Action Required
07/03/2018

Door operation ACTION REQUIRED:(verified at inspection) All electronically lock and access controlled doors shall unlock in the event of a power loss and or an activation of the fire alarm system.
Construction documents for fire alarm systems
Corrective Action Required
07/03/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED: (information purposes) Have the fire alarm system contractor provide shop drawings of any modifications to be done to the fire alrm system.
Construction documents - Fire protection systems
Corrective Action Required
07/03/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(informastion purposes) Have the fire sprinkler system contractor provide shop drawings of any modfications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
07/03/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing will be required prior to the final occupancy inspection for any fire alarm system devices that are disconnected, relocated or installed new. Contact the fire department to schedule testing. (816)969-1300.
Building Plan Review Rejected 07/10/2018 07/02/2018
Joe Frogge
License Tax Application
Corrective Action Required
07/02/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Bldg - Exits and exit access doorways 1015.1
Corrective Action Required
07/02/2018

2012 IBC 1015.1 – Exits or exit access doorways from spaces. Two exits or exit access doorways from any space shall be provided where one of the following conditions exists: 1. The occupant load of the space exceeds one of the values in Table 1015.1. 2. The common path of egress travel exceeds one of the limitations of Section 1014.3. 3. Where required by Section 1015.3, 1015.4, 1015.5 or 1015.6. Where a building contains mixed occupancies, each individual occupancy shall comply with the applicable requirements for that occupancy. Where applicable, cumulative occupant loads from adjacent occupancies shall be considered in accordance with the provisions of Section 1004.1. Action required: Given that occupant load in room 1A098 exceeds 50, (1 occ per 15sf - loose tables & chairs) 2 exits will be required with appropriate spacing, exit/emergency lighting, outswinging doors, etc.
Health Dept Review
Corrective Action Required
07/02/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes and applies to kitchen type facilities in lounge.
Health Dept Inspection
Corrective Action Required
07/02/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes and applies to kitchen type facilities in lounge.
Misc
Corrective Action Required
07/02/2018

2012 IMC 501.3 Exhaust discharge. The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a nuisance and not less than the distances specified in Section 501.3.1. The air shall be discharged to a location from which it cannot again be readily drawn in by a ventilating system. Air shall not be exhausted into an attic or crawl space. (see code for exceptions) Action required: Restroom exhaust appears to connect to a return air duct. Modify or clarify.
Licensed Contractors Approved 07/10/2018 07/02/2018
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $1,908.89 $1,908.89 Paid 07/17/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 7/18/2018 7/18/2018 at 10:00 AM 07/18/2018
Misc
Partial Correction
07/18/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: NEW SPACES AT 3RD FLOOR;
In-wall Inspection Partial 7/20/2018 7/20/2018 at 10:05 AM 07/20/2018
Misc
Partial Correction
07/18/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F063; 3F063A; 3F064; 3F065; CORRIDOR CROSSWALL @ DOOR 3F062;
Above Ceiling Inspection Partial 7/20/2018 at 10:25 AM 07/20/2018
Misc
Partial Correction
07/20/2018
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFIT AT 3F063 EAST;
Above Ceiling Inspection Partial 8/8/2018 8/8/2018 at 10:00 AM 08/08/2018
Misc
Partial Correction
07/20/2018
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFIT AT 3F063 EAST;
Misc
Partial Correction
08/08/2018
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 3F063; 3F063A; 3F0F64; 3F065;
Alarm Test Passed 8/16/2018 08/16/2018
Final Inspection - Commercial Partial 8/21/2018 8/21/2018 at 8:50 AM 08/21/2018
Misc
Partial Correction
08/21/2018
PHASE 1 AREA AT 3RD FLOOR OK FOR USE & OCCUPANCY WITH LSFD TO RESOLVE QUESTION REGARDING EMERGENCY SYSTEM AT CORRIDOR DOORS;
Occupancy Inspection - Fire Partial 08/21/2018
Underslab Plumbing Inspection - Commercial Partial 9/4/2018 9/4/2018 at 9:20 AM 09/04/2018
Misc
Partial Correction
09/04/2018
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT EXISTING DOCTORS' LOUNGE. ENSURE PRESSURE-TESTING OF PIPING SYSTEM.IS PERFORMED PER IPC 312 / IRC P2503.5.1 REQUIREMENT.
In-wall Inspection Partial 9/13/2018 9/13/2018 at 11:10 AM 09/13/2018
Misc
Partial Correction
07/20/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F063; 3F063A; 3F064; 3F065; CORRIDOR CROSSWALL @ DOOR 3F062; [1A098; 1A098A; 1A098B;
Above Ceiling Inspection Partial 10/8/2018 10/8/2018 at 9:35 AM 10/08/2018
Misc
Partial Correction
08/08/2018
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFIT AT 3F063 EAST;
Misc
Partial Correction
08/08/2018
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 3F063; 3F063A; 3F064; 3F065; [1A098; 1A098A; 1A098B; 1A100; 1A100A; 1A100B;
Alarm Test Passed 10/19/2018 10/19/2018
Above Ceiling Inspection Passed 10/8/2018 10/19/2018
Misc
Resolved
10/19/2018
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SOFFIT AT 3F063 EAST;
Misc
Resolved
10/19/2018
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 3F063; 3F063A; 3F064; 3F065; [1A098; 1A098A; 1A098B; 1A100; 1A100A; 1A100B;
Underslab Plumbing Inspection - Commercial Passed 9/4/2018 10/19/2018
Misc
Resolved
10/19/2018
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT EXISTING DOCTORS' LOUNGE. ENSURE PRESSURE-TESTING OF PIPING SYSTEM.IS PERFORMED PER IPC 312 / IRC P2503.5.1 REQUIREMENT.
In-wall Inspection Passed 9/13/2018 10/19/2018
Misc
Resolved
10/19/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F063; 3F063A; 3F064; 3F065; CORRIDOR CROSSWALL @ DOOR 3F062; [1A098; 1A098A; 1A098B;
Final Inspection - Commercial Passed 10/26/2018 10/26/2018 at 8:00 AM 10/26/2018
Misc
Resolved
10/26/2018
PHASE 1 AREA AT 3RD FLOOR OK FOR USE & OCCUPANCY WITH LSFD TO RESOLVE QUESTION REGARDING EMERGENCY SYSTEM AT CORRIDOR DOORS;
Occupancy Inspection - Fire Passed 10/26/2018 10/26/2018
Documents & Images
Date Uploaded File Type Document Name
07/03/2018 Letter Fire Building Plan Review
07/05/2018 Letter Codes P/R Corrections Document
07/12/2018 Letter Fire Building Plan Review
07/16/2018 Letter Codes P/R Corrections Document
07/17/2018 Letter Codes Plan Review Conditions
07/17/2018 Receipt Receipt for transaction: 2018-004939
07/17/2018 Letter Codes Building Permit
07/18/2018 Letter Inspection Summary
07/20/2018 Letter Inspection Summary
07/23/2018 Letter Fire (Alarm) Plan Review Notice
07/25/2018 Food Establishment Remodel Plan Review - Approved FTG 0001354
07/26/2018 Letter Fire (Sprinkler) Plan Review
08/08/2018 Letter Inspection Summary
08/21/2018 Letter Inspection Summary
09/04/2018 Letter Inspection Summary
09/13/2018 Letter Inspection Summary
10/08/2018 Letter Inspection Summary
10/26/2018 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home