Permit Application Status

PRCOM20181486


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20181486
Building Permit - Commercial
Final Completion
LANGSFORD DEVELOPMENT INC
CHANGE OF TENANT
CHANGE OF USE FOR NEW MUSIC LESSONS BUSINESS EXPANDING FROM ADJACENT SPACE - NO CONSTRUCTION TAKING PLACE *drawing in plan review file
05/15/2018
05/21/2018
11/17/2018
05/29/2018
Locations
Contacts
SHINING LIGHT MUSIC LLC, Address:616 SW 3RD ST, Phone:(816) 347-0099  
PREMIER ELECTRIC & LIGHTING DESIGN, Address:PO BOX 1311, Phone:(816) 564-7660  
LANGSFORD DEVELOPMENT INC, Address:616 SW 3RD ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 05/25/2018 05/21/2018
Joe Frogge
Bldg - Exits and exit access doorways 1015.1
Corrective Action Required
05/21/2018

2012 IBC 1015.1 – Exits or exit access doorways from spaces. Two exits or exit access doorways from any space shall be provided where one of the following conditions exists: 1. The occupant load of the space exceeds one of the values in Table 1015.1. 2. The common path of egress travel exceeds one of the limitations of Section 1014.3. 3. Where required by Section 1015.3, 1015.4, 1015.5 or 1015.6. Where a building contains mixed occupancies, each individual occupancy shall comply with the applicable requirements for that occupancy. Where applicable, cumulative occupant loads from adjacent occupancies shall be considered in accordance with the provisions of Section 1004.1. 2012 IBC 1015.2.1 – Two exits or exit access doorways. Where two exits or exit access doorways are required from any portion of the exit access, the exit doors or exit access doorways shall be placed a distance apart equal to not less than one-half of the length of the maximum overall diagonal dimensions of the building or area to be served measured in a straight line between exit doors or exit access doorways. Interlocking or scissor stairs shall be counted as one exit stairway. (See code section for possible exceptions.) Action required: Given that the calculated occupant load exceeds 49 (57 by my conservative calculation), 2 exits are required and must be spaced adequately apart. 5/21/18 - clarification sent. 2nd exit is in the rear via stairs - exit and emergency lighting will be field verified
Fire Plan Review Approved with Conditions 05/25/2018 05/16/2018
Joe Dir
Address numbers required
Corrective Action Required
05/16/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(veriifed at inspection) Address shall be readable from the roadway
Portable fire extinguishers - general
Corrective Action Required
05/16/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) All existing fire extinguishers shall have current annual service tags posted on each extinguisher.
Misc
Corrective Action Required
05/16/2018

Exit signs/emergency lighting ACTION REQUIRED: (veriifed at inspection) All existing exit signs shall illuminate on regular house current on battery back up power when tested. All existing emergency lighting shall illuminate on battery power when tested
Misc
Corrective Action Required
05/16/2018

door operations ACTION REQUIRED: No keyed locks on the egress side of an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Licensed Contractors Approved 05/25/2018 05/15/2018
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $30.64 $30.64 Paid 05/21/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Fire Not Ready 5/23/2018 05/23/2018
Final Inspection - Commercial Failed 5/23/2018 at 2:55 PM 05/23/2018
Misc
Corrective Action Required
05/23/2018
ONE LOOSE ELECTRICAL RECEPTACLE ON MAIN FLOOR -- POINTED OUT
Misc
Corrective Action Required
05/23/2018
CAUTION REGARDING GLASS IN HAZARDOUS LOCATIONS: GLAZING AT THESE LOCATIONS MUST BE TEMPERED OR LAMINATED. - IN DOORS, SWINGING OR SLIDING - IN WALLS WITHIN 24" OF DOOR JAMBS - WITHIN 18" OF FLOOR
Misc
Corrective Action Required
05/23/2018
WATER CLOSET SEATS SHOULD BE COMMERCIAL OPEN FRONT TYPE
Misc
Corrective Action Required
05/23/2018
NEC 408.4 ELECTRICAL SERVICE INSTALLATION: ENSURE ALL CIRCUIT POSITIONS ARE PROPERLY LABELED. MUST BE LEGIBLE, COMPLETE, CURRENT, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Corrective Action Required
05/23/2018
IDENTIFICATION OF GAS SERVICE ENTRY: ENSURE ADDRESS IS IDENTIFIED WITH PERMANENT TAG TO LOAD SIDE ENTRY PIPE (NOT ON METER).
Misc
Corrective Action Required
05/23/2018
ENSURE ADDRESS LABELING OF ELECTRICAL SERVICES IS CONSISTENT WITH KCP&L RECORDS
Occupancy Inspection - Fire Passed 5/24/2018 05/24/2018
Final Inspection - Commercial Passed 5/25/2018 5/25/2018 at 10:00 AM 05/25/2018
Misc
Resolved
05/25/2018
ONE LOOSE ELECTRICAL RECEPTACLE ON MAIN FLOOR -- POINTED OUT
Misc
Resolved
05/25/2018
CAUTION REGARDING GLASS IN HAZARDOUS LOCATIONS: GLAZING AT THESE LOCATIONS MUST BE TEMPERED OR LAMINATED. - IN DOORS, SWINGING OR SLIDING - IN WALLS WITHIN 24" OF DOOR JAMBS - WITHIN 18" OF FLOOR
Misc
Resolved
05/25/2018
WATER CLOSET SEATS SHOULD BE COMMERCIAL OPEN FRONT TYPE
Misc
Resolved
05/25/2018
NEC 408.4 ELECTRICAL SERVICE INSTALLATION: ENSURE ALL CIRCUIT POSITIONS ARE PROPERLY LABELED. MUST BE LEGIBLE, COMPLETE, CURRENT, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Resolved
05/25/2018
IDENTIFICATION OF GAS SERVICE ENTRY: ENSURE ADDRESS IS IDENTIFIED WITH PERMANENT TAG TO LOAD SIDE ENTRY PIPE (NOT ON METER).
Misc
Resolved
05/25/2018
ENSURE ADDRESS LABELING OF ELECTRICAL SERVICES IS CONSISTENT WITH KCP&L RECORDS
Documents & Images
Date Uploaded File Type Document Name
05/16/2018 Letter Fire Building Plan Review
05/21/2018 Letter Codes P/R Corrections Document
05/21/2018 Letter Codes Plan Review Conditions
05/21/2018 Receipt Receipt for transaction: 2018-002871
05/21/2018 Letter Codes Building Permit
05/23/2018 Letter Inspection Summary
05/25/2018 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home