Permit Application Status

PRCOM20181329


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20181329
Building Permit - Commercial
Final Completion
SNUGBEE LEES SUMMIT LLC
ALTERATION COMMERCIAL
INTERIOR REMODEL OF EXISTING STORE **invite planner to final
05/01/2018
08/08/2018
08/23/2018
Locations
Contacts
SNUGBEE LEES SUMMIT LLC, Address:7206 SILVER LODE LN  
HENTZEN CONSTRUCTION SERVICES INC, Address:3711 N HILLSIDE, Phone:(316) 267-3321  
CR ARCHITECTS, Address:750 NORTH SAINT PAUL STREET STE 450, Phone:(972) 253-4675  
KENDREK ELECTRIC INC, Address:P O BOX 9411, Phone:(316) 204-3029  
J-HAWK PLUMBING INC, Address:3615 W MAPLE ST, Phone:(316) 942-7279  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 05/11/2018 08/08/2018
Development Center
LC - General Contractor
Corrective Action Required
05/04/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
05/04/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved with Conditions 05/11/2018 05/08/2018
Joe Frogge
License Tax Application
Corrective Action Required
05/04/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Review
Resolved
05/08/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
05/04/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Department Review Approved 05/08/2018
Joe Frogge
Fire Plan Review Approved with Conditions 05/11/2018 05/03/2018
Joe Dir
Posting of occupant load
Corrective Action Required
05/03/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(verified at inspection) Post the occupant load of 32 on the interior of the sales/seating area close to the entrance.
Address numbers required
Corrective Action Required
05/03/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) The numeric address of 1130 shall be readable from the roadway on both the front and rear door.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
05/03/2018

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ACTION REQUIRED:(veriifed at inspection) The fire extinguisher shall be up to date with the annual service. A current service tag shall be posted on the fire extinguisher with the last serive date.
Misc
Corrective Action Required
05/03/2018

Health Dept ACTION REQUIRED:(information purposes) The Jackson County Health Dept will need to conduct an inspection on the business before opening up for dirve through or walk-in business.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $544.34 $544.34 Paid 08/08/2018
8331507-Sewer Connection Fee $90.00 $90.00 Paid 08/08/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 8/14/2018 at 9:15 AM 08/14/2018
Underslab Plumbing Inspection - Commercial Passed 8/14/2018 at 9:05 AM 08/14/2018
In-wall Inspection Passed 8/14/2018 8/14/2018 at 8:45 AM 08/14/2018
In-wall Inspection Passed 8/16/2018 at 12:25 PM 08/16/2018
Above Ceiling Inspection Partial 8/16/2018 at 12:05 PM 08/16/2018
Misc
Partial Correction
08/16/2018
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @: FRONT OF HOUSE NOTE: HVAC FLEX CONNECTIONS SUBJECT TO APPROVAL WHEN COMPLETED
Misc
Corrective Action Required
08/16/2018
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS: - REPLACE DOUBLE SLAMMERS WITH SINGLES WHERE ONLY ONE OPENING IS USED - CLOSE ALL BOXES - ONE UNTERMINATED MC CABLE RUN DO NOT COVER
Rough Electrical Inspection - Commercial Not Ready 8/17/2018 8/17/2018 at 7:35 AM 08/17/2018
Rough Electrical Inspection - Commercial Passed 8/17/2018 at 8:30 AM 08/17/2018
Above Ceiling Inspection Passed 8/21/2018 8/21/2018 at 9:55 AM 08/21/2018
Misc
Resolved
08/21/2018
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @: FRONT OF HOUSE NOTE: HVAC FLEX CONNECTIONS SUBJECT TO APPROVAL WHEN COMPLETED
Misc
Resolved
08/21/2018
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS: - REPLACE DOUBLE SLAMMERS WITH SINGLES WHERE ONLY ONE OPENING IS USED - CLOSE ALL BOXES - ONE UNTERMINATED MC CABLE RUN DO NOT COVER
Final Inspection - Commercial Partial 8/22/2018 8/22/2018 at 1:15 PM 08/22/2018
Misc
Corrective Action Required
08/22/2018
OBTAIN LSFD APPROVAL OF EXIT SIGNS WHICH PRESENTLY DO NOT ILLUMINATE UNDER NORMAL POWER.
Misc
Partial Correction
08/22/2018
OK TO SET UP FOR BUSINESS. FULL APPROVAL AWAITING FIRE DEPARTMENT APPROVAL OF EXIT SIGNS.
Final Inspection - Commercial Passed 8/23/2018 at 9:40 AM 08/23/2018
Misc
Resolved
08/23/2018
OBTAIN LSFD APPROVAL OF EXIT SIGNS WHICH PRESENTLY DO NOT ILLUMINATE UNDER NORMAL POWER.
Misc
Resolved
08/23/2018
OK TO SET UP FOR BUSINESS. FULL APPROVAL AWAITING FIRE DEPARTMENT APPROVAL OF EXIT SIGNS.
Occupancy Inspection - Fire Passed 08/23/2018
Documents & Images
Date Uploaded File Type Document Name
05/03/2018 Letter Fire Building Plan Review
05/08/2018 Food Establishment Remodel Plan Review - Approved FTG 0001467
08/08/2018 Letter Codes Plan Review Conditions
08/08/2018 Receipt Receipt for transaction: 2018-005584
08/08/2018 Letter Codes Building Permit
08/14/2018 Letter Inspection Summary
08/16/2018 Letter Inspection Summary
08/17/2018 Letter Inspection Summary
08/21/2018 Letter Inspection Summary
08/22/2018 Letter Inspection Summary
08/23/2018 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home