Permit Application Status

PRCOM20181021


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20181021
Building Permit - Commercial
Certificate of Occupancy
MIDWEST DIVISION LSH LLC
ADDITION COMMERCIAL
BUILDING ADDITION FOR NEW CT EQUIPMENT AND SUPPORT ROOMS - PERMIT INCLUDES ALTERATION OF EXISTING PHYSICIAN ROOMS INTO FAST TRACK ROOMS
04/06/2018
05/30/2018
10/10/2018
01/04/2019
Locations
Contacts
MIDWEST DIVISION LSH LLC, Address:PO BOX 80610  
ACI BOLAND, Address:1421 EAST 104TH ST; SUITE 100, Phone:(816) 763-9600  
EXCEL CONSTRUCTORS, Address:8041 W 47TH ST , Phone:(913) 261-1000  
RAND CONSTRUCTION COMPANY, Address:1428 W 9TH ST, Phone:(816) 421-4143  
HEARTLAND ELECTRIC CORPORATION, Address:947 LOCUST HILL CIR, Phone:(816) 318-8500  
RAND CONSTRUCTION COMPANY, Address:1428 W 9TH ST, Phone:(816) 421-4143  
ACI BOLAND, Address:1421 EAST 104TH ST; SUITE 100, Phone:(816) 763-9600  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 07/18/2018
Joe Dir
Installation acceptance testing
Corrective Action Required
07/18/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: The CT addition area will required field testing (hydrostaic pressure test) prior to the final occupancy inspection. Contact the fire Department to schedule testing. (816)969-1300
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
07/18/2018

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ACTION REQUIRED:(veriifed at inspection) The existing sprinkler riser shall be current with required service and maintenance. The riser shall have a current service tag posted on on the systems riser.
Licensed Contractors Approved 05/16/2018 05/23/2018
Joe Frogge
LC - General Contractor
Resolved
05/23/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
05/23/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Final Development Plan Review Approved 09/05/2018 05/23/2018
Joe Frogge
Building Plan Review Approved with Conditions 05/23/2018 05/18/2018
Joe Frogge
Final Development Plan
Resolved
05/23/2018

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
License Tax Application
Corrective Action Required
05/16/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Resolved
05/18/2018

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles. 2. Metal Boxes and enclosures containing receptacles. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system. 5/18/18 - EMT specified
Code analysis required
Resolved
05/18/2018

2012 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Listed construction type in code analysis conflicts with required fire rating information provided. Clarify.
Misc
Resolved
05/18/2018

2012 IBC 711.4 Continuity. Assemblies shall be continuous without openings, penetrations or joints except as permitted by this section and Sections 712.1, 714.4, 715, 1009.3 and 1022.1. Skylights and other penetrations through a fire-resistance-rated roof deck or slab are permitted to be unprotected, provided that the structural integrity of the fire-resistance-rated roof assembly is maintained. Unprotected skylights shall not be permitted in roof assemblies required to be fire-resistance-rated in accordance with Section 705.8.6. The supporting construction shall be protected to afford the required fire-resistance rating of the horizontal assembly supported. Action required: Provide penetration details.
Bldg - Fire partitions - Duct and air transfer openings 717.5.4
Resolved
05/18/2018

2012 IBC 717.5.4 – Fire partitions. Ducts and air transfer openings that penetrate fire partitions shall be protected with listed fire dampers installed in accordance with their listing. (See code section for possible exceptions.) Action required: Provide fire and/or smoke dampers at required locations.
Mech - Equipment and appliances on roofs or elevated structures 306.5
Resolved
05/18/2018

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. (see code section for specific construction requirements) Action required: Provide permanent access to roof.
Miscellaneous Correction
Resolved
05/18/2018

2012 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Clarify locations and types of fire partitions. Unable to determine which UL numbers to use. Type F shaft in corridor? Rated between offices? Not all UL designations detailed, etc.
Misc
Resolved
05/17/2018

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle within 25' of roof mounted exhaust fan. 5/17/18 - EE has argued that a ventilation fan does not meet letter of code.
Fire Plan Review Approved with Conditions 05/23/2018 05/18/2018
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
05/16/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings of the fire sprinkler system modifications to be done.
Construction documents - Fire protection systems
Corrective Action Required
05/16/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of the fire alarm system modifications to be done.
Installation acceptance testing
Corrective Action Required
05/16/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Field tests and acceptance testing of the SEO buttons, Duct detection, door drop off, fire sprinkler and fire alarm systems will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Misc
Corrective Action Required
05/16/2018

Duct detection monitored ACTION REQUIRED:(verified at testing) 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble
Misc
Corrective Action Required
05/16/2018

Pipe and valve labeling ACTION REQUIRED:(verified at inspection) All med gas lines and valves shall be labeled according to (NFPA 99) 5.3.11.1 - 5.3.11.3
Misc
Corrective Action Required
05/16/2018

door operations ACTION REQUIRED:(verified at testing) B] 1008.1.9.8 Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1 or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2, are permitted to be equipped with an approved entrance and egress access control system, listed in accordance with UL 294, which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public
Fire Plan Review Approved with Conditions 04/25/2018
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
04/25/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings of the fire sprinkler system modifications to be done.
Construction documents - Fire protection systems
Corrective Action Required
04/25/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of the fire alarm system modifications to be done.
Installation acceptance testing
Corrective Action Required
04/25/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Field tests and acceptance testing of the SEO buttons, Duct detection, door drop off, fire sprinkler and fire alarm systems will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Misc
Corrective Action Required
04/25/2018

Duct detection monitored ACTION REQUIRED:(verified at testing) 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble
Misc
Corrective Action Required
04/25/2018

Pipe and valve labeling ACTION REQUIRED:(verified at inspection) All med gas lines and valves shall be labeled according to (NFPA 99) 5.3.11.1 - 5.3.11.3
Misc
Corrective Action Required
04/25/2018

door operations ACTION REQUIRED:(verified at testing) B] 1008.1.9.8 Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1 or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2, are permitted to be equipped with an approved entrance and egress access control system, listed in accordance with UL 294, which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public
Fire Plan Review Approved with Conditions 04/20/2018 04/25/2018
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
04/13/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings of the fire sprinkler system modifications to be done.
Construction documents - Fire protection systems
Corrective Action Required
04/13/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of the fire alarm system modifications to be done.
Installation acceptance testing
Corrective Action Required
04/13/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Field tests and acceptance testing of the SEO buttons, Duct detection, door drop off, fire sprinkler and fire alarm systems will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Misc
Corrective Action Required
04/13/2018

Duct detection monitored ACTION REQUIRED:(verified at testing) 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble
Misc
Corrective Action Required
04/13/2018

Pipe and valve labeling ACTION REQUIRED:(verified at inspection) All med gas lines and valves shall be labeled according to (NFPA 99) 5.3.11.1 - 5.3.11.3
Misc
Corrective Action Required
04/13/2018

door operations ACTION REQUIRED:(verified at testing) B] 1008.1.9.8 Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1 or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2, are permitted to be equipped with an approved entrance and egress access control system, listed in accordance with UL 294, which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public
Building Plan Review Rejected 04/20/2018 04/13/2018
Joe Frogge
Final Development Plan
Corrective Action Required
04/13/2018

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
License Tax Application
Corrective Action Required
04/13/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
04/13/2018

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles. 2. Metal Boxes and enclosures containing receptacles. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system.
Code analysis required
Corrective Action Required
04/13/2018

2012 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Listed construction type in code analysis conflicts with required fire rating information provided. Clarify.
Misc
Corrective Action Required
04/13/2018

2012 IBC 711.4 Continuity. Assemblies shall be continuous without openings, penetrations or joints except as permitted by this section and Sections 712.1, 714.4, 715, 1009.3 and 1022.1. Skylights and other penetrations through a fire-resistance-rated roof deck or slab are permitted to be unprotected, provided that the structural integrity of the fire-resistance-rated roof assembly is maintained. Unprotected skylights shall not be permitted in roof assemblies required to be fire-resistance-rated in accordance with Section 705.8.6. The supporting construction shall be protected to afford the required fire-resistance rating of the horizontal assembly supported. Action required: Provide penetration details.
Bldg - Fire partitions - Duct and air transfer openings 717.5.4
Corrective Action Required
04/13/2018

2012 IBC 717.5.4 – Fire partitions. Ducts and air transfer openings that penetrate fire partitions shall be protected with listed fire dampers installed in accordance with their listing. (See code section for possible exceptions.) Action required: Provide fire and/or smoke dampers at required locations.
Mech - Equipment and appliances on roofs or elevated structures 306.5
Corrective Action Required
04/13/2018

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. (see code section for specific construction requirements) Action required: Provide permanent access to roof.
Miscellaneous Correction
Corrective Action Required
04/13/2018

2012 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Clarify locations and types of fire partitions. Unable to determine which UL numbers to use. Type F shaft in corridor? Rated between offices? Not all UL designations detailed, etc.
Misc
Corrective Action Required
04/13/2018

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle within 25' of roof mounted exhaust fan.
Licensed Contractors Rejected 04/20/2018 04/13/2018
Joe Frogge
LC - General Contractor
Corrective Action Required
04/13/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
04/13/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Addition to Commercial $5,030.12 $5,030.12 Paid 05/30/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underground Plumbing Inspection - Commercial Partial 7/12/2018 7/12/2018 at 1:45 PM 07/12/2018
Sewer Service Inspection Passed 7/13/2018 7/13/2018 at 3:45 PM 07/13/2018
Informational
07/13/2018
John DiMauro 07/13/2018 3:39 PM The storm line appears to be installed according to the site plans.
Piers/Caissons Inspection - Commercial Partial 7/24/2018 (9:30) 7/24/2018 at 2:30 PM 07/24/2018
Misc
Corrective Action Required
07/24/2018
7 OF 14 PIERS ON WEST SIDE OF PROJECT READY TO POUR
Piers/Caissons Inspection - Commercial Passed 7/25/2018 7/25/2018 at 3:00 PM 07/25/2018
Misc
Corrective Action Required
07/24/2018
7 OF 14 PIERS ON WEST SIDE OF PROJECT READY TO POUR
Misc
Corrective Action Required
07/25/2018
7 piers ok to pour
Footing Inspection - Commercial Partial 8/6/2018 8/6/2018 08/06/2018
Misc
Partial Correction
08/06/2018
-SOUTH ELEVEATION APPROVED -20 FEET EAST ELEVATION (TO THE SOUTH) APPROVED -WEST ELEVATION APPROVED -20 FEET NORTH (TO THE WEST) APPROVED
Rated Assembly Inspection Passed 8/7/2018 8/6/2018 at 3:00 PM 08/06/2018
Underground Electrical Inspection - Commercial Passed 8/6/2018 at 3:10 PM 08/06/2018
Footing Inspection - Commercial Passed 8/6/2018 at 3:20 PM 08/06/2018
Misc
Partial Correction
08/06/2018
Underslab Electrical Inspection - Commercial Partial 8/7/2018 8/7/2018 08/07/2018
Misc
Partial Correction
08/07/2018
UNDERSLAB ELECTRICAL OK: -NE CORNER CT&CONTROL RM
In-wall Inspection Partial 9/24/2018 9/24/2018 09/24/2018
Misc
Partial Correction
09/24/2018
existing remodel area where combining three rooms area approved
Rated Assembly Inspection Partial 9/27/2018 9/27/2018 09/27/2018
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
09/27/2018
-EXTERIOR SIDE OF STEEL AT PARAPET AREA SPRAY APPLIED FIRE PROOFING JAPPROVED
Rated Assembly Inspection Partial 10/2/2018 10/2/2018 10/02/2018
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
10/02/2018
SPRAY APPLIED FIRE PROOFING TO SUPER STRUCTURAL STEEL APPROVED
Rated Assembly Inspection Partial 10/12/2018
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
10/02/2018
-EXTERIOR SIDE OF STEEL AT PARAPET AREA SPRAY APPLIED FIRE PROOFING JAPPROVED -1ST LAYER SHAFT WALL APPROVED
In-wall Inspection Partial 10/12/2018 10/12/2018 10/12/2018
Misc
Partial Correction
09/24/2018
existing remodel area where combining three rooms area approved
Misc
Partial Correction
10/12/2018
ADDITIOIN AREA: 6 A 7.1; 7 A 7.1; NORTH CORRIDOR WALL APPROVED
Rated Assembly Inspection Partial 10/16/2018 10/16/2018
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
10/12/2018
-EXTERIOR SIDE OF STEEL AT PARAPET AREA SPRAY APPLIED FIRE PROOFING JAPPROVED -1ST LAYER SHAFT WALL APPROVED -1ST LAYER GYP APPROVED NORTH SIDE OF SOUTH WALL.
Rated Assembly Inspection Partial 10/22/2018 10/22/2018 10/22/2018
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
10/16/2018
-EXTERIOR SIDE OF STEEL AT PARAPET AREA SPRAY APPLIED FIRE PROOFING JAPPROVED -1ST LAYER SHAFT WALL APPROVED -1ST LAYER GYP APPROVED NORTH SIDE OF SOUTH WALL. -2nd layer 2 hour shaft wall approved
Rated Assembly Inspection Partial 10/29/2018 10/29/2018 at 8:40 AM 10/29/2018
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
10/22/2018
-EXTERIOR SIDE OF STEEL AT PARAPET AREA SPRAY APPLIED FIRE PROOFING JAPPROVED -1ST LAYER SHAFT WALL APPROVED -1ST LAYER GYP APPROVED NORTH SIDE OF SOUTH WALL. -2nd layer 2 hour shaft wall approved; LINER BOARD AT WALL, BULKHEAD, AND LID AT BREAKTHRU OPENING 1-1458;
In-wall Inspection Partial 10/22/2018 10/29/2018 at 8:55 AM 10/29/2018
Misc
Partial Correction
10/12/2018
existing remodel area where combining three rooms area approved
Misc
Partial Correction
10/12/2018
ADDITIOIN AREA: 6 A 7.1; 7 A 7.1; NORTH CORRIDOR WALL APPROVED; NEW AND MODIFIED WALLS AT 1-B01431 + CORRIDOR WALLS JUST OUTSIDE CASED OPENING UNDER CONSTRUCTION;
Above Ceiling Inspection Partial 11/15/2018 11/15/2018 11/15/2018
Misc
Partial Correction
11/15/2018
All approved excellent West ct scan room
Sprinkler - Hydrostatic Test Passed 11/15/2018 11/15/2018
Above Ceiling Inspection Passed 11/19/2018 11/19/2018 11/19/2018
Misc
Resolved
11/19/2018
All approved excellent West ct scan room
Alarm Test Passed 11/29/2018 11/29/2018
Occupancy Inspection - Planning Passed 11/30/2018
Occupancy Inspection - Fire Temporary C of O 11/30/2018 11/30/2018
Occupancy Inspection - Codes Commercial Failed 11/30/2018 12/3/2018 12/03/2018
Misc
Corrective Action Required
12/03/2018
-complete exterior means of egress east exit -complete all exterior items -Obtain Fire approval
Occupancy Inspection - Water Utilities Passed 12/04/2018
Occupancy Inspection - Codes Commercial Temporary C of O 12/5/2018 12/5/2018 12/05/2018
Misc
Corrective Action Required
12/03/2018
EXTERIOR, NORTH OF ADDITION, COMPLETE GRADING AND STABLEIZATION OF GRADE.
Occupancy Inspection - Fire Passed 12/5/2018 12/05/2018
Occupancy Inspection - Codes Commercial Full C of O 1/4/2019 1/4/2019 01/04/2019
Misc
Resolved
01/04/2019
EXTERIOR, NORTH OF ADDITION, COMPLETE GRADING AND STABLEIZATION OF GRADE.
Documents & Images
Date Uploaded File Type Document Name
04/06/2018 Plans 3-15242 LSMC CT Addition
04/06/2018 Plans Supplemental Info
04/13/2018 Letter Fire Building Plan Review
04/13/2018 Letter Codes P/R Corrections Document
04/25/2018 Letter Fire Building Plan Review
05/18/2018 Letter Fire Building Plan Review
05/23/2018 Letter Codes Plan Review Conditions
05/30/2018 Receipt Receipt for transaction: 2018-003256
05/30/2018 Letter Codes Building Permit
07/12/2018 Letter Inspection Summary
07/13/2018 Letter DE-Daily Inspection Summary
07/18/2018 Letter Fire (Sprinkler) Plan Review
07/24/2018 Letter Inspection Summary
07/25/2018 Letter Inspection Summary
08/06/2018 Letter Inspection Summary
08/06/2018 Letter Inspection Summary
08/07/2018 Letter Inspection Summary
10/02/2018 Letter Inspection Summary
10/12/2018 Letter Inspection Summary
10/16/2018 Letter Inspection Summary
10/22/2018 Letter Inspection Summary
10/29/2018 Letter Inspection Summary
10/29/2018 Inspection Summary_20181029091008
11/15/2018 Letter INSPECTION SUMMARY
11/19/2018 Letter INSPECTION SUMMARY
12/03/2018 Letter INSPECTION SUMMARY
12/05/2018 Letter Codes Temporary Certificate of Occupancy
01/04/2019 Letter Field Certificate of Occupancy
01/14/2019 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home