Permit Application Status

PRCOM20180775


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20180775
Building Permit - Commercial
Certificate of Occupancy
LS INVESTORS ONE LLC
CHANGE OF TENANT
ALTER EXISTING PIZZA RESTAURANT TO BECOME PIZZA DELIVERY *invite planner to final to verify screening
03/22/2018
05/23/2018
11/13/2018
06/18/2018
Locations
Contacts
LS INVESTORS ONE LLC, Address:1220 WASHINGTON ST PO BOX 411299  
AFFINITY CONSTRUCTION & CONTRACTING LLC, Address:32003 E FRISTOE RD, Phone:(816) 785-4090  
DIMAGGIO MECHANICAL LLC, Address:1 SE 5TH ST, Phone:(816) 246-9999  
STAR ELECTRICAL, Address:P O BOX 1755, Phone:(816) 694-0982  
A BRIGHT PLUMBING LLC, Address:18107 E 18TH TER N, Phone:(816) 215-0730  
FOARM/FIELD STUDIO, Address:415 E 60TH ST, Phone:(816) 651-7749  
MJ INTERIORS, Address:7915 HEMLOCK ST, Phone:(913) 313-6565  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 05/22/2018 05/23/2018
Development Center
LC - MEP Subs
Resolved
05/23/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 4/23/18 - added mechanical but still waiting on plumbing and electrical 5/17/18 - PC and EC still not licensed
Building Plan Review Approved with Conditions 05/22/2018 05/22/2018
Joe Frogge
Health Dept Inspection
Corrective Action Required
05/15/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 4/23/18 - acknowledged
Misc
Resolved
05/22/2018

Not enough information to complete review. Actions required: - - -
Misc
Corrective Action Required
05/15/2018

4/23/18 - This note has been added due to change in scope of work (original hood above oven was assumed to be type II) Actions required: - - Provide roof plan to show new equipment, connections, etc. 5/17/18 - Exhaust must be minimum 10' away from any intakes. (ref: makeup air unit near existing RTU. Does makeup unit really have an exhaust option?) 5/22/18 - existing intake to be field modified per updated sheet printed and attached to drawings. - Provide verification that roof structure has been evaluated for additional load at make up air unit. 5/17/18 - deferred to construction per request. - Provide screening for new roof mounted equipment. 5/17/18 - existing parapet noted to be adequate. To be field verified. (Note: new equipment is subject to this ordinance regardless of existing conditions for adjacent equipment) - Provide convenience receptacle within 25' of any new hvac equipment of roof 5/17/18 - noted. to be field verified
Fire Plan Review Approved with Conditions 05/22/2018 05/16/2018
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
05/15/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings for any modification to be done to the fire alarm system
Address numbers required
Corrective Action Required
05/15/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Numeric address of 1196 shall be readable from the roadway.
Construction documents - Fire protection systems
Corrective Action Required
05/15/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings of any modification to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
05/15/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the new type 1 hood system and any alarm system devices that had to be relocated, disconnected during the rennovation or newly installed devices will require an acceptance test prior to the final occupancy inspection. contact the fire depaertment prior to schedule testing (816)969-1300.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
05/15/2018

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ACTION REQUIRED:(verified at inspection) Provide a second K-class fire extinguisher for the second Type-1 hood system. To be mounted under or close to the manual pull station
Misc
Corrective Action Required
05/15/2018

Type-1 hood/suppression systems ACTION REQUIRED:(verified at testing) The suppression systems for the Type-1 hoods shall be monitored by the strip malls Fire Alarm Panel. Have the fire alarm system company make needed connections and programing. Testing required
Health Department Review Approved 08/08/2018 04/27/2018
Joe Frogge
Fire Plan Review Approved with Conditions 04/30/2018 04/24/2018
Joe Dir
Type I hood - Where required
Resolved
04/24/2018

2012 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors.
Construction documents for fire alarm systems
Corrective Action Required
04/23/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings for any modification to be done to the fire alarm system
Address numbers required
Corrective Action Required
04/23/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Numeric address of 1196 shall be readable from the roadway.
Construction documents - Fire protection systems
Corrective Action Required
04/23/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings of any modification to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
04/23/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the new type 1 hood system and any alarm system devices that had to be relocated, disconnected during the rennovation or newly installed devices will require an acceptance test prior to the final occupancy inspection. contact the fire depaertment prior to schedule testing (816)969-1300.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
04/23/2018

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ACTION REQUIRED:(verified at inspection) Provide a second K-class fire extinguisher for the second Type-1 hood system. To be mounted under or close to the manual pull station
Misc
Resolved
04/24/2018

Type-1 Hood/suppression system ACTION REQUIRED: Provide specifications for the new Type-hood/suppression system.
Misc
Corrective Action Required
04/23/2018

Type-1 hood/suppression systems ACTION REQUIRED:(verified at testing) The suppression systems for the Type-1 hoods shall be monitored by the strip malls Fire Alarm Panel. Have the fire alarm system company make needed connections and programing. Testing required
Building Plan Review Rejected 04/30/2018 04/23/2018
Joe Frogge
Health Dept Review
Resolved
04/27/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 4/23/18 - acknowledged
Health Dept Inspection
Corrective Action Required
04/23/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 4/23/18 - acknowledged
Code analysis required
Resolved
04/23/2018

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Actions required: - Modify drawings to reflect actual construction type which is 5B. - Update code analysis to show occupant load.
Plan Submittal 2012 Codes
Resolved
04/23/2018

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Modify drawings to reflect actual ICC/ANSI year which is 2009.
Misc
Corrective Action Required
04/23/2018

Not enough information to complete review. Actions required: - - Provide complete MEP designs as applicable. 4/23/18 - not provided. - Provide complete design for new hood above oven. 4/23/18 - specify duct construction and fire rated wrap
Misc
Resolved
04/23/2018

2012 IBC 1210.4 Toilet room location. Toilet rooms shall not open directly into a room used for the preparation of food for service to the public. Action required: Modify design to demonstrate compliance.
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Resolved
04/23/2018

2012 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Specify compliant maximum height of countertop. (not relevant if not open to public - clarify)
Misc
Resolved
04/27/2018

2012 IMC 507.2.2 Type II hoods. Type II hoods shall be installed above dishwashers and appliances that produce heat or moisture and do not produce grease or smoke as a result of the cooking process, except where the heat and moisture loads from such appliances are incorporated into the HVAC system design or into the design of a separate removal system. (see code section for more specific requirements) Action required: Provide hood over new dishwasher or provide verification that exemptions are met. 4/23/18 - deferred to construction 4/27/18 - dishwasher removed from project
Misc
Corrective Action Required
04/23/2018

4/23/18 - This note has been added due to change in scope of work (original hood above oven was assumed to be type II) Actions required: - Provide verification that wall behind type I hood is non-combustible, i.e. metal studs - Provide roof plan to show new equipment, connections, etc. - Provide verification that roof structure has been evaluated for additional load at make up air unit. - Provide screening for new roof mounted equipment. - Provide convenience receptacle within 25' of any new hvac equipment of roof
Licensed Contractors Rejected 04/23/2018 04/23/2018
Joe Frogge
LC - General Contractor
Resolved
04/23/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
04/23/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 4/23/18 - added mechanical but still waiting on plumbing and electrical
Fire Plan Review Rejected 04/03/2018 03/27/2018
Joe Dir
Type I hood - Where required
Corrective Action Required
03/27/2018

2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors.
Construction documents for fire alarm systems
Corrective Action Required
03/27/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED: Have the fire alarm system contractor provide shop drawings for any modification to be done to the fire alarm system
Address numbers required
Corrective Action Required
03/27/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Numeric address of 1196 shall be readable from the roadway.
Construction documents - Fire protection systems
Corrective Action Required
03/27/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED: Have the fire sprinkler system contractor provide shop drawings of any modification to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
03/27/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Acceptance testing of the new type 1 hood system and any alarm system devices that had to be relocated, disconnected during the rennovation or newly installed devices will require an acceptance test prior to the final occupancy inspection. contact the fire depaertment prior to schedule testing (816)969-1300.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
03/27/2018

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ACTION REQUIRED: Provide a second K-class fire extinguisher for the second Type-1 hood system. To be mounted under or close to the manual pull station
Misc
Corrective Action Required
03/27/2018

Type-1 Hood/suppression system ACTION REQUIRED: Provide specifications for the new Type-hood/suppression system.
Misc
Corrective Action Required
03/27/2018

Type-1 hood/suppression systems ACTION REQUIRED: The suppression systems for the Type-1 hoods shall be monitored by the strip malls Fire Alarm Panel. Have the fire alarm system company make needed connections and programing. Testing required
Building Plan Review Rejected 04/03/2018 03/26/2018
Joe Frogge
Health Dept Review
Corrective Action Required
03/26/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
03/26/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Code analysis required
Corrective Action Required
03/26/2018

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Actions required: - Modify drawings to reflect actual construction type which is 5B. - Update code analysis to show occupant load.
Plan Submittal 2012 Codes
Corrective Action Required
03/26/2018

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Modify drawings to reflect actual ICC/ANSI year which is 2009.
Misc
Corrective Action Required
03/26/2018

Not enough information to complete review. Actions required: - Label use of all spaces. - Provide complete MEP designs as applicable. - Provide complete design for new hood above oven.
Misc
Corrective Action Required
03/26/2018

2012 IBC 1210.4 Toilet room location. Toilet rooms shall not open directly into a room used for the preparation of food for service to the public. Action required: Modify design to demonstrate compliance.
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Corrective Action Required
03/26/2018

2012 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Specify compliant maximum height of countertop. (not relevant if not open to public - clarify)
Misc
Corrective Action Required
03/26/2018

2012 IMC 507.2.2 Type II hoods. Type II hoods shall be installed above dishwashers and appliances that produce heat or moisture and do not produce grease or smoke as a result of the cooking process, except where the heat and moisture loads from such appliances are incorporated into the HVAC system design or into the design of a separate removal system. (see code section for more specific requirements) Action required: Provide hood over new dishwasher or provide verification that exemptions are met.
Licensed Contractors Rejected 04/03/2018 03/26/2018
Joe Frogge
LC - General Contractor
Corrective Action Required
03/26/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
03/26/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $122.55 $122.55 Paid 05/23/2018
8331507-Sewer Connection Fee $30.00 $30.00 Paid 05/23/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Hood/Duct Inspection Not Ready 5/25/2018 5/25/2018 at 8:10 AM 05/25/2018
Misc
Corrective Action Required
05/25/2018
IBC 109.1, 109.5; IRC R109.3 INSPECTION ACCESS: PROPERTY LOCKED; INTERIOR NOT ACCESSIBLE. CALL FOR INSPECTION ON DAY WHEN JOBSITE IS ACCESSIBLE. PER IMC PROVIDE LIGHT AND ACCESS FOR GREASE DUCT LIGHT TEST.
Hood/Duct Inspection Partial 5/29/2018 at 9:55 AM 05/29/2018
Misc
Resolved
05/29/2018
IBC 109.1, 109.5; IRC R109.3 INSPECTION ACCESS: PROPERTY LOCKED; INTERIOR NOT ACCESSIBLE. CALL FOR INSPECTION ON DAY WHEN JOBSITE IS ACCESSIBLE.
Misc
Partial Correction
05/29/2018
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: GREASE DUCT INSTALLED WITHOUT LIGHT TEST OF SEAMS. TEST PERFORMED ON JOINTS AND SEAMS NOW ACCESSIBLE. THOSE ABOVE ROOF LINE NOT ACCESSIBLE. HOLES MARKED FOR SPOT-WELDING. OK TO APPLY 1ST WRAP WHEN READY. CALL FOR INSPECTION BEFORE 2ND LAYER.
Hood/Duct Inspection Not Ready 5/30/2018 5/30/2018 at 7:05 AM 05/30/2018
Misc
Partial Correction
05/29/2018
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: GREASE DUCT INSTALLED WITHOUT LIGHT TEST OF SEAMS. TEST PERFORMED ON JOINTS AND SEAMS NOW ACCESSIBLE. THOSE ABOVE ROOF LINE NOT ACCESSIBLE. HOLES MARKED FOR SPOT-WELDING. OK TO APPLY 1ST WRAP WHEN READY. CALL FOR INSPECTION BEFORE 2ND LAYER.
Hood/Duct Inspection Partial 5/30/2018 at 8:15 AM 05/30/2018
Misc
Partial Correction
05/30/2018
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: GREASE DUCT INSTALLED WITHOUT LIGHT TEST OF SEAMS. TEST PERFORMED ON JOINTS AND SEAMS NOW ACCESSIBLE. THOSE ABOVE ROOF LINE NOT ACCESSIBLE. HOLES MARKED FOR SPOT-WELDING. OK TO APPLY 1ST WRAP WHEN READY. CALL FOR INSPECTION BEFORE 2ND LAYER.
Above Ceiling Inspection Passed 6/7/2018 6/7/2018 at 10:10 AM 06/07/2018
In-wall Inspection Passed 6/7/2018 6/7/2018 at 9:55 AM 06/07/2018
Gas Piping Inspection - Commercial Partial 6/8/2018 6/8/2018 at 10:40 AM 06/08/2018
Misc
Partial Correction
06/08/2018
GAS PIPING PRESSURE TEST HELD STEADY AT >= 20 PSI FOR >=10 MIN..
Misc
Corrective Action Required
06/08/2018
PROPERLY CLAMP PIPE AT WEST GRILL
Misc
Corrective Action Required
06/08/2018
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. PAINT 100% OF STEEL PIPE INCLUDING AT SUPPORTS.
Miscellaneous Inspection Partial 6/12/2018 at 1:15 PM 06/12/2018
Miscellaneous Inspection Partial 6/13/2018 at 8:25 AM 06/13/2018
Miscellaneous Inspection Passed 6/13/2018 at 1:15 PM 06/13/2018
Gas Piping Inspection - Commercial Passed 6/14/2018 at 9:45 AM 06/14/2018
Misc
Resolved
06/14/2018
GAS PIPING PRESSURE TEST HELD STEADY AT >= 20 PSI FOR >=10 MIN..
Misc
Resolved
06/14/2018
PROPERLY CLAMP PIPE AT WEST GRILL
Misc
Resolved
06/14/2018
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. PAINT 100% OF STEEL PIPE INCLUDING AT SUPPORTS.
Occupancy Inspection - Codes Commercial Not Ready 6/14/2018 6/14/2018 at 9:55 AM 06/14/2018
Alarm Test Passed 6/14/2018 06/14/2018
Alternate Protection Systems Inspection Failed 6/14/2018 06/14/2018
Occupancy Inspection - Fire Not Ready 6/14/2018 06/14/2018
Hood/Duct Inspection Passed 6/18/2018 at 8:55 AM 06/18/2018
Misc
Resolved
06/18/2018
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: GREASE DUCT INSTALLED WITHOUT LIGHT TEST OF SEAMS. TEST PERFORMED ON JOINTS AND SEAMS NOW ACCESSIBLE. THOSE ABOVE ROOF LINE NOT ACCESSIBLE. HOLES MARKED FOR SPOT-WELDING. OK TO APPLY 1ST WRAP WHEN READY. CALL FOR INSPECTION BEFORE 2ND LAYER.
Occupancy Inspection - Codes Commercial Full C of O 6/18/2018 at 9:05 AM 06/18/2018
Alternate Protection Systems Inspection Passed 6/18/2018 06/18/2018
Occupancy Inspection - Fire Passed 6/18/2018 06/18/2018
Occupancy Inspection - Water Utilities Passed 06/19/2018
Documents & Images
Date Uploaded File Type Document Name
03/27/2018 Letter Fire Building Plan Review
03/28/2018 Letter Codes P/R Corrections Document
04/24/2018 Letter Fire Building Plan Review
04/25/2018 Letter Codes P/R Corrections Document
04/27/2018 New Food Establishment Plan Review - Approved FTG 0001325
05/16/2018 Letter Fire Building Plan Review
05/17/2018 Letter Codes P/R Corrections Document
05/22/2018 Re Main Slice 2
05/23/2018 Letter Codes Plan Review Conditions
05/23/2018 Receipt Receipt for transaction: 2018-002984
05/23/2018 Letter Codes Building Permit
05/25/2018 Letter Inspection Summary
05/29/2018 Letter Inspection Summary
05/30/2018 Letter Inspection Summary
06/07/2018 Letter Inspection Summary
06/08/2018 Letter Inspection Summary
06/18/2018 Letter Field Certificate of Occupancy
06/19/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home