Permit Application Status

PRCOM20180430


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20180430
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW COMMERCIAL
NEW 14 BAY AIRPLANE HANGAR
02/27/2018
03/30/2018
08/28/2018
09/14/2018
Locations
Contacts
B DEAN CONSTRUCTION LLC, Address:2401 SW US HIGHWAY 40 STE B, Phone:(816) 795-3733  
BRINTON ELECTRIC COMPANY INC, Address:10100 E 65TH ST STE B, Phone:(816) 356-0922  
MISSION PLUMBING, HEATING AND COOLING, Address:5725 NIEMAN RD STE C, Phone:(913) 631-6506  
CMT CRAWFORD, MILLY & TILLY, Address:211 NW EXECUTIVE WAY STE H, Phone:(816) 272-8363  
CITY OF LEES SUMMIT, Address:PO BOX 1600  
Intertek-PSI, Address:2828 S. 44th Street, Phone:(913) 310-1600  
Reviews
Review Type Outcome Est. Completion Date Completed
Final Development Plan Review Approved 05/02/2018 04/30/2018
Joe Frogge
Building Plan Review Approved with Conditions 03/22/2018 03/28/2018
Joe Frogge
Misc
Corrective Action Required
03/15/2018

This report represents both new buildings, hangars W & X. All comments apply to both buildings. Action required: Comment is for informational purposes. 3/15/18 - acknowledged in letter
Final Development Plan
Corrective Action Required
03/15/2018

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 3/15/18 - acknowledged in letter
Plan Submittal 2012 Codes
Resolved
03/19/2018

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Update all code references to those currently adopted. (2009 IBC is referenced in multiple locations) 3/15/18 - Covered on structural drawings but not on pre-engineered building set
Code analysis required
Resolved
03/19/2018

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Provide complete code analysis as noted. 3/15/18 - Covered on structural drawings but not on pre-engineered building set
Misc
Resolved
03/15/2018

2012 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf.
Misc
Resolved
03/29/2018

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Provide UL# and complete details for construction of fire rated assembly.
Misc
Resolved
03/19/2018

2012 IBC 1609.1 Applications. Buildings, structures and parts thereof shall be designed to withstand the minimum wind loads pre-scribed herein. Decreases in wind loads shall not be made for the effect of shielding by other structures. Action required: Update referenced wind loads to 115mph per IBC Figure 1609A. 3/15/18 - Covered on structural drawings but not on pre-engineered building set
Fire Plan Review Approved with Conditions 03/22/2018 03/15/2018
Joe Dir
Misc
Corrective Action Required
03/15/2018

Emergency lighting ACTION REQUIRED:(acknowledged in letter) Provide emergency lighting for all hangers and storage spaces. [B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies. [B] 1006.2 Illumination level. The means of egress illumination level shall not be less than 1 footcandle (11 lux) at the walking surface.
Address numbers required
Corrective Action Required
03/15/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Provide addressing for each hagar building, hangar space and storage space. Address shall be readable from the roadway.
Portable fire extinguishers - general
Corrective Action Required
03/15/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide one 2A-10BC fire extinguisher for each hangar and storage space. Extinguishers to be mounted on a wall close to an exit.
Misc
Corrective Action Required
03/15/2018

Diesel fuel station (north end of taxiway) ACTION REQUIRED:Make the diesel fueling station code compliant. Relocate the emergency shut off and fire extinguisher to be no close then 20 feet no farther than 100 feet from the fueling pump. 2303.2 Emergency disconnect switches. An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations
Special Inspections Review Approved 03/14/2018
Joe Frogge
Licensed Contractors Approved 02/27/2018 03/05/2018
Joe Frogge
LC - MEP Subs
Resolved
03/05/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed Plumbing Contractor.
Building Plan Review Rejected 03/13/2018 03/01/2018
Joe Frogge
Misc
Corrective Action Required
03/01/2018

This report represents both new buildings, hangars W & X. All comments apply to both buildings. Action required: Comment is for informational purposes.
Final Development Plan
Corrective Action Required
03/01/2018

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
License Tax Application
Resolved
03/05/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Resolved
03/14/2018

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Plan Submittal 2012 Codes
Corrective Action Required
03/01/2018

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Update all code references to those currently adopted. (2009 IBC is referenced in multiple locations)
Code analysis required
Corrective Action Required
03/01/2018

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Provide complete code analysis as noted.
Misc
Corrective Action Required
03/01/2018

2012 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf.
Misc
Corrective Action Required
03/01/2018

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Provide UL# and complete details for construction of fire rated assembly.
Misc
Corrective Action Required
03/01/2018

2012 IBC 1609.1 Applications. Buildings, structures and parts thereof shall be designed to withstand the minimum wind loads pre-scribed herein. Decreases in wind loads shall not be made for the effect of shielding by other structures. Action required: Update referenced wind loads to 115mph per IBC Figure 1609A.
Fire Plan Review Rejected 03/13/2018 02/28/2018
Joe Dir
Misc
Corrective Action Required
02/28/2018

Emergency lighting ACTION REQUIRED: Provide emergency lighting for all hangers and storage spaces. [B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies. [B] 1006.2 Illumination level. The means of egress illumination level shall not be less than 1 footcandle (11 lux) at the walking surface.
Address numbers required
Corrective Action Required
02/28/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Provide addressing for each hagar building, hangar space and storage space. Address shall be readable from the roadway.
Portable fire extinguishers - general
Corrective Action Required
02/28/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide one 2A-10BC fire extinguisher for each hangar and storage space. Extinguishers to be mounted on a wall close to an exit.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $2,445.02 $2,445.02 Paid 03/30/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 4/11/2018 4/11/2018 at 11:05 AM 04/11/2018
Misc
Partial Correction
04/11/2018
-INTERIOR COLUMN PIERS OK
Footing Inspection - Commercial Partial 4/12/2018 at 11:00 AM 04/12/2018
Misc
Partial Correction
04/11/2018
-INTERIOR COLUMN PIERS OK -EXTERIOR GB OK, EXCEPT 20 FT SECTION AT SE CORNER
Underground Electrical Inspection - Commercial Partial 4/12/2018 at 2:20 PM 04/12/2018
Misc
Partial Correction
04/12/2018
-UFER GROUNDING CONNECTION INSPECTED-OK
Footing Inspection - Commercial Passed 4/13/2018 (10:00) 4/13/2018 at 10:35 AM 04/13/2018
Misc
Resolved
04/13/2018
-INTERIOR COLUMN PIERS OK -EXTERIOR GB OK, EXCEPT 20 FT SECTION AT SE CORNER
Underslab Plumbing Inspection - Commercial Partial 4/18/2018 4/18/2018 at 10:25 AM 04/18/2018
Misc
Partial Correction
04/18/2018
-RESTROOM OK
Underslab Electrical Inspection - Commercial Passed 4/23/2018 4/23/2018 at 2:10 PM 04/23/2018
Electrical Service Inspection Failed 6/28/2018 6/28/2018 at 11:15 AM 06/28/2018
Misc
Corrective Action Required
06/28/2018
-CONNECT GEC TO SERVICE GROUNDED CONDUCTOR PER 250.24
Electrical Service Inspection Passed 6/28/2018 at 1:05 PM 06/28/2018
Misc
Resolved
06/28/2018
-CONNECT GEC TO SERVICE GROUNDED CONDUCTOR PER 250.24
Rough Framing Inspection - Commercial Passed 7/2/2018 7/2/2018 at 10:10 AM 07/02/2018
Rated Assembly Inspection Failed 7/10/2018 7/10/2018 at 2:05 PM 07/10/2018
Rated Assembly Inspection Partial 7/11/2018 7/11/2018 at 8:40 AM 07/11/2018
Misc
Partial Correction
07/11/2018
3/4" GWB BOTH FACES AT RATED WALL: OK TO COVER WHEN READY 1ST LAYER;
Electrical Service Inspection Passed 7/11/2018 at 9:05 AM 07/11/2018
Rated Assembly Inspection Passed 7/13/2018 at 1:15 PM 07/13/2018
Misc
Resolved
07/13/2018
3/4" GWB BOTH FACES AT RATED WALL: OK TO COVER WHEN READY 1ST LAYER;
Rated Assembly Inspection Passed 7/18/2018 7/18/2018 at 2:45 PM 07/18/2018
Underground Electrical Inspection - Commercial Passed 07/27/2018
Misc
Resolved
07/27/2018
-UFER GROUNDING CONNECTION INSPECTED-OK
Underslab Plumbing Inspection - Commercial Passed 07/27/2018
Misc
Resolved
07/27/2018
-RESTROOM OK
Occupancy Inspection - Fire Passed 07/27/2018
Occupancy Inspection - Codes Commercial Temporary C of O 7/27/2018 7/27/2018 at 10:45 AM 07/27/2018
Misc
Corrective Action Required
07/27/2018
-GET APPROVAL FROM FIRE AND PLANNING DEPT -PROTECT OUTSIDE ELECTRICAL EQUIPMENTS **OK TO USE THE BUILDING
Occupancy Inspection - Planning Passed 07/30/2018
Occupancy Inspection - Codes Commercial Full C of O 9/14/2018 9/14/2018 at 2:50 PM 09/14/2018
Misc
Resolved
09/14/2018
-GET APPROVAL FROM FIRE AND PLANNING DEPT -PROTECT OUTSIDE ELECTRICAL EQUIPMENTS **OK TO USE THE BUILDING
Documents & Images
Date Uploaded File Type Document Name
02/28/2018 Letter Fire Building Plan Review
03/01/2018 Letter Codes P/R Corrections Document
03/14/2018 Lee's Summit Airport Hangars
03/15/2018 Letter Fire Building Plan Review
03/28/2018 Letter Codes Plan Review Conditions
03/30/2018 Receipt Receipt for transaction: 2018-001183
03/30/2018 Letter Codes Building Permit
04/11/2018 Letter Inspection Summary
04/12/2018 Letter Inspection Summary
04/13/2018 Letter Inspection Summary
04/18/2018 Letter Inspection Summary
04/23/2018 Letter Inspection Summary
06/28/2018 Letter Inspection Summary
06/28/2018 Letter Inspection Summary
07/02/2018 Letter Inspection Summary
07/11/2018 Letter Inspection Summary
07/13/2018 Letter Inspection Summary
07/18/2018 Letter Inspection Summary
07/27/2018 Letter Inspection Summary
09/14/2018 Letter Field Certificate of Occupancy
09/17/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home