Summary
PRCOM20173864
Building Permit - Commercial
Final Completion
CELTIC INVESTMENT GROUP LLC
NEW SHELL BUILDING
SHELL BUILDING FOR FUTURE OFFICE/WAREHOUSE
11/28/2017
03/20/2018
06/05/2018
07/12/2019
Locations
Contacts
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
MAYES PLUMBING INC, Address:501 S MCCLEARY RD STE A, Phone:(816) 792-5400  
CL ARCHITECTURE (CRAIG LUEBBERT), Address:396 SW WINTERGARDEN, Phone:(816) 536-3472  
TERRACON CONSULTANTS INC, Address:10841 S RIDGEVIEW ROAD, Phone:(913) 599-6886  
CELTIC INVESTMENT GROUP LLC, Address:1120 SE BROADWAY  
TPC INTERIORS INC, Address:1120 SE BROADWAY DR, Phone:(816) 406-3620  
CELTIC INVESTMENT GROUP LLC, Address:1120 SE BROADWAY DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 04/17/2019
Joe Dir
Installation acceptance testing
Corrective Action Required
04/17/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Field testing and acceptance testing of the system will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Sprinkler Plan Review Released for Construction 03/22/2019
Joe Dir
Installation acceptance testing
Corrective Action Required
03/22/2019

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) All field tests and acceptance testing of the system is required to be completed prior to the final occupancy inspection. contact the fire department to schedule testing. (816)969-1300
Fire Plan Review Approved with Conditions 12/22/2017 03/06/2019
Joe Dir
Address numbers required
Corrective Action Required
03/06/2019

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Adress shall be readable from the roadway (Kingpoint Dr)
Portable fire extinguishers - general
Corrective Action Required
03/06/2019

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide one 2A-10BC fire extinguisher for every 3,000 sq ft. mount the extinguishers so there is a maximum travel distance of 75' to an extinguisher
Misc
Corrective Action Required
03/06/2019

Door operations ACTION REQUIRED:(verified at inspection) No keyed locks on the egress side of an exit.
Misc
Resolved
03/06/2019

Development plan ACTION REQUIRED: FDP needs to be approved
Illumination required
Corrective Action Required
03/06/2019

2012 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. ACTION REQUIRED:(verified at inspection) All marked exits shall have exterior emergency lighting.
Final Development Plan Review Approved 05/02/2018 03/19/2018
Joe Frogge
Building Plan Review Approved with Conditions 12/22/2017 03/19/2018
Joe Frogge
License Tax Application
Corrective Action Required
03/19/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 12/15/17 - acknowledged in letter
Final Development Plan
Resolved
03/19/2018

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 12/15/17 - acknowledged in letter
Fire Plan Review Approved with Conditions 12/22/2017 03/19/2018
Joe Frogge
Address numbers required
Corrective Action Required
03/19/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Adress shall be readable from the roadway (Kingpoint Dr)
Portable fire extinguishers - general
Corrective Action Required
03/19/2018

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide one 2A-10BC fire extinguisher for every 3,000 sq ft. mount the extinguishers so there is a maximum travel distance of 75' to an extinguisher
Misc
Corrective Action Required
03/19/2018

Door operations ACTION REQUIRED:No keyed locks on the egress side of an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. [B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Misc
Corrective Action Required
03/19/2018

Development plan ACTION REQUIRED: FDP needs to be approved
Licensed Contractors Approved 12/15/2017 03/18/2018
Joe Frogge
LC - General Contractor
Corrective Action Required
12/15/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 12/15/17 - acknowledged in letter
LC - MEP Subs
Corrective Action Required
12/15/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 12/15/17 - acknowledged in letter
Fire Plan Review Approved with Conditions 01/03/2018 03/16/2018
Joe Dir
Address numbers required
Corrective Action Required
01/03/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Adress shall be readable from the roadway (Kingpoint Dr)
Portable fire extinguishers - general
Corrective Action Required
01/03/2018

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide one 2A-10BC fire extinguisher for every 3,000 sq ft. mount the extinguishers so there is a maximum travel distance of 75' to an extinguisher
Misc
Resolved
01/03/2018

Access doors ACTION REQUIRED:Additional door required on the west side of the building 3206.6.1 Access doors. Where building access is required by Table 3206.2, fire department access doors shall be provided in accordance with this section. Access doors shall be accessible without the use of a ladder. 3206.6.1.1 Number of doors required. A minimum of one access door shall be provided in each 100 lineal feet (30 480 mm), or fraction thereof, of the exterior walls that face required fire apparatus access roads. The required access doors shall be distributed such that the lineal distance between adjacent access doors does not exceed 100 feet (30 480 mm). 3206.6.1.2 Door size and type. Access doors shall not be less than 3 feet (914 mm) in width and 6 feet 8 inches (2032 mm) in height. Roll-up doors shall not be used unless approved. 3206.6.1.3 Locking devices. Only approved locking devices shall be used.
Misc
Corrective Action Required
01/03/2018

Door operations ACTION REQUIRED:No keyed locks on the egress side of an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. [B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Misc
Corrective Action Required
01/03/2018

Development plan ACTION REQUIRED: FDP needs to be approved
Fire Plan Review Approved with Conditions 12/22/2017 01/03/2018
Joe Dir
Address numbers required
Corrective Action Required
01/03/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Adress shall be readable from the roadway (Kingpoint Dr)
Portable fire extinguishers - general
Corrective Action Required
01/03/2018

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide one 2A-10BC fire extinguisher for every 3,000 sq ft. mount the extinguishers so there is a maximum travel distance of 75' to an extinguisher
Misc
Corrective Action Required
01/03/2018

Access doors ACTION REQUIRED:Additional door required on the west side of the building 3206.6.1 Access doors. Where building access is required by Table 3206.2, fire department access doors shall be provided in accordance with this section. Access doors shall be accessible without the use of a ladder. 3206.6.1.1 Number of doors required. A minimum of one access door shall be provided in each 100 lineal feet (30 480 mm), or fraction thereof, of the exterior walls that face required fire apparatus access roads. The required access doors shall be distributed such that the lineal distance between adjacent access doors does not exceed 100 feet (30 480 mm). 3206.6.1.2 Door size and type. Access doors shall not be less than 3 feet (914 mm) in width and 6 feet 8 inches (2032 mm) in height. Roll-up doors shall not be used unless approved. 3206.6.1.3 Locking devices. Only approved locking devices shall be used.
Misc
Corrective Action Required
01/03/2018

Door operations ACTION REQUIRED:No keyed locks on the egress side of an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. [B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Fire Plan Review Approved with Conditions 12/22/2017 01/03/2018
Joe Dir
Address numbers required
Corrective Action Required
01/03/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Adress shall be readable from the roadway (Kingpoint Dr)
Portable fire extinguishers - general
Corrective Action Required
01/03/2018

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide one 2A-10BC fire extinguisher for every 3,000 sq ft. mount the extinguishers so there is a maximum travel distance of 75' to an extinguisher
Misc
Corrective Action Required
01/03/2018

Access doors ACTION REQUIRED:Additional door required on the west side of the building 3206.6.1 Access doors. Where building access is required by Table 3206.2, fire department access doors shall be provided in accordance with this section. Access doors shall be accessible without the use of a ladder. 3206.6.1.1 Number of doors required. A minimum of one access door shall be provided in each 100 lineal feet (30 480 mm), or fraction thereof, of the exterior walls that face required fire apparatus access roads. The required access doors shall be distributed such that the lineal distance between adjacent access doors does not exceed 100 feet (30 480 mm). 3206.6.1.2 Door size and type. Access doors shall not be less than 3 feet (914 mm) in width and 6 feet 8 inches (2032 mm) in height. Roll-up doors shall not be used unless approved. 3206.6.1.3 Locking devices. Only approved locking devices shall be used.
Misc
Corrective Action Required
01/03/2018

Door operations ACTION REQUIRED:No keyed locks on the egress side of an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. [B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Fire Plan Review Approved with Conditions 12/22/2017 12/19/2017
Joe Dir
Construction documents for fire alarm systems
Resolved
12/19/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings for approval of the fire dectection system to be installed. 3206.5 Fire detection. Where fire detection is required by Table 3206.2, an approved automatic fire detection system shall be installed throughout the high-piled storage area. The system shall be monitored and be in accordance with Section 907. Non sprinklered buildings: Refer to table 3206.2 Class 1 commodity 12,000 option 2 3206.7 Smoke and heat removal. Where smoke and heat removal are required by Table 3206.2, smoke and heat vents shall be provided in accordance with Section 910. Where draft curtains are required by Table 3206.2, they shall be provided in accordance with Section 910.3.5.
Address numbers required
Corrective Action Required
12/15/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Adress shall be readable from the roadway (Kingpoint Dr)
Knox box required
Resolved
12/19/2017

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. ACTION REQUIRED:(information purposes) Knox box can be obtained online at knoxbox.com knox box to be mounted by the main entrance with the top of the box approx. 5'-6' off finish grade.
Installation acceptance testing
Resolved
12/19/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the fire detection system shall be required prior to the final occupancy inspection. Contact the fire department to schedule testing. 816-969-1300.
Portable fire extinguishers - general
Corrective Action Required
12/15/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide one 2A-10BC fire extinguisher for every 3,000 sq ft. mount the extinguishers so there is a maximum travel distance of 75' to an extinguisher
Misc
Resolved
12/19/2017

Aisles / plie dimension / height ACTION REQUIRED:(information purposes) 3206.9 Aisles. Aisles providing access to exits and fire department access doors shall be provided in high-piled storage areas exceeding 500 square feet (46 m2), in accordance with Sections 3206.9.1 through 3206.9.3. Aisles separating storage piles or racks shall comply with NFPA 13. Aisles shall also comply with Chapter 10. 3206.9.1.2 Nonsprinklered buildings. Aisles in nonsprinklered buildings shall be a minimum of 96 inches (2438 mm) wide. 3207.3 Pile dimension and height limitations. Pile dimensions, the maximum permissible storage height and pile volume shall be in accordance with Table 3206.2.
Misc
Corrective Action Required
12/15/2017

Access doors ACTION REQUIRED:Additional door required on the west side of the building 3206.6.1 Access doors. Where building access is required by Table 3206.2, fire department access doors shall be provided in accordance with this section. Access doors shall be accessible without the use of a ladder. 3206.6.1.1 Number of doors required. A minimum of one access door shall be provided in each 100 lineal feet (30 480 mm), or fraction thereof, of the exterior walls that face required fire apparatus access roads. The required access doors shall be distributed such that the lineal distance between adjacent access doors does not exceed 100 feet (30 480 mm). 3206.6.1.2 Door size and type. Access doors shall not be less than 3 feet (914 mm) in width and 6 feet 8 inches (2032 mm) in height. Roll-up doors shall not be used unless approved. 3206.6.1.3 Locking devices. Only approved locking devices shall be used.
Misc
Corrective Action Required
12/15/2017

Door operations ACTION REQUIRED:No keyed locks on the egress side of an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. [B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Building Plan Review Approved with Conditions 12/22/2017 12/15/2017
Joe Frogge
License Tax Application
Corrective Action Required
12/15/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 12/15/17 - acknowledged in letter
Final Development Plan
Corrective Action Required
12/15/2017

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 12/15/17 - acknowledged in letter
Project cost
Resolved
12/15/2017

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes.
Engineered truss package
Resolved
12/15/2017

Copies of the engineered building package were not provided at the time of permit application. Action required: Provide engineered building package or request deferral.
Misc
Resolved
12/15/2017

2012 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf.
Misc
Resolved
12/15/2017

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Misc
Resolved
12/15/2017

Code analysis on cover sheet describes building as non-sprinklered but utility plans show fire suppression piping. Action required: Clarify. 12/15/17 - owner will be providing the tap and stub for future
Special Inspections Review Approved 01/02/2018 12/15/2017
Joe Frogge
Building Plan Review Rejected 12/12/2017 12/07/2017
Joe Frogge
License Tax Application
Corrective Action Required
12/07/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Final Development Plan
Corrective Action Required
12/07/2017

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Project cost
Corrective Action Required
12/07/2017

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes.
Engineered truss package
Corrective Action Required
12/07/2017

Copies of the engineered building package were not provided at the time of permit application. Action required: Provide engineered building package or request deferral.
Misc
Corrective Action Required
12/07/2017

2012 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf.
Misc
Corrective Action Required
12/07/2017

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Misc
Corrective Action Required
12/07/2017

Code analysis on cover sheet describes building as non-sprinklered but utility plans show fire suppression piping. Action required: Clarify.
Licensed Contractors Rejected 12/12/2017 12/07/2017
Joe Frogge
LC - General Contractor
Corrective Action Required
12/07/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 12/15/17 - acknowledged in letter
LC - MEP Subs
Corrective Action Required
12/07/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 12/15/17 - acknowledged in letter
Fire Plan Review Rejected 12/12/2017 12/01/2017
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
12/01/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings for approval of the fire dectection system to be installed. 3206.5 Fire detection. Where fire detection is required by Table 3206.2, an approved automatic fire detection system shall be installed throughout the high-piled storage area. The system shall be monitored and be in accordance with Section 907. Non sprinklered buildings: Refer to table 3206.2 Class 1 commodity 12,000 option 2 3206.7 Smoke and heat removal. Where smoke and heat removal are required by Table 3206.2, smoke and heat vents shall be provided in accordance with Section 910. Where draft curtains are required by Table 3206.2, they shall be provided in accordance with Section 910.3.5.
Address numbers required
Corrective Action Required
12/01/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Adress shall be readable from the roadway (Kingpoint Dr)
Knox box required
Corrective Action Required
12/01/2017

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. ACTION REQUIRED:(information purposes) Knox box can be obtained online at knoxbox.com knox box to be mounted by the main entrance with the top of the box approx. 5'-6' off finish grade.
Installation acceptance testing
Corrective Action Required
12/01/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the fire detection system shall be required prior to the final occupancy inspection. Contact the fire department to schedule testing. 816-969-1300.
Portable fire extinguishers - general
Corrective Action Required
12/01/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) Provide one 2A-10BC fire extinguisher for every 3,000 sq ft. mount the extinguishers so there is a maximum travel distance of 75' to an extinguisher
Misc
Corrective Action Required
12/01/2017

Aisles / plie dimension / height ACTION REQUIRED:(information purposes) 3206.9 Aisles. Aisles providing access to exits and fire department access doors shall be provided in high-piled storage areas exceeding 500 square feet (46 m2), in accordance with Sections 3206.9.1 through 3206.9.3. Aisles separating storage piles or racks shall comply with NFPA 13. Aisles shall also comply with Chapter 10. 3206.9.1.2 Nonsprinklered buildings. Aisles in nonsprinklered buildings shall be a minimum of 96 inches (2438 mm) wide. 3207.3 Pile dimension and height limitations. Pile dimensions, the maximum permissible storage height and pile volume shall be in accordance with Table 3206.2.
Misc
Corrective Action Required
12/01/2017

Door operations ACTION REQUIRED:No keyed locks on the egress side of an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. [B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Shell Building $2,449.30 $2,449.30 Paid 03/15/2018
8331401-Water Tap Fee $3,343.00 $3,343.00 Paid 03/15/2018
8350015-Water Meter Fee $431.83 $431.83 Paid 03/15/2018
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 03/15/2018
8331507-Sewer Connection Fee $180.00 $180.00 Paid 03/21/2019
9110078-Valuation Fee for New Shell Building $550.70 $550.70 Paid 03/21/2019
$3,000.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Passed 7/2/2018 7/3/2018 at 11:40 AM 07/03/2018
Underslab Plumbing Inspection - Commercial Passed 7/13/2018 at 1:10 PM 07/13/2018
Foundation Inspection - Commercial Passed 7/18/2018 (2:30) 7/18/2018 at 2:30 PM 07/18/2018
Water Service Inspection Partial 9/21/2018 9/21/2018 at 8:30 AM 09/21/2018
Misc
Partial Correction
09/21/2018
APPROVED TO METER SET UP
Underslab Plumbing Inspection - Commercial Passed 5/15/2019 9/26/2018 at 3:00 PM 09/27/2018
Misc
Partial Correction
09/21/2018
APPROVED TO METER SET UP
Informational
09/27/2018
John DiMauro 09/27/2018 7:20 AM Approved at the meter and main.
Gas Piping Inspection - Commercial Passed 11/30/2018 11/30/2018
Gas Service Inspection - Commercial Passed 11/30/2018 11/30/2018
Underground Electrical Inspection - Commercial Partial 12/11/2018 12/12/2018 12/12/2018
Misc
Partial Correction
12/12/2018
LIGHT POLE BASE NW CORNER BY BUILDING APPROVED
Electrical Service Inspection Failed 12/14/2018 at 9:15 AM 12/14/2018
Misc
Corrective Action Required
12/14/2018
SECONDARY CABLES JUST NOW BEING PULLED. NOT READY FOR INSPECTION.
Electrical Service Inspection Passed 12/14/2018 at 10:15 AM 12/14/2018
Misc
Resolved
12/14/2018
SECONDARY CABLES JUST NOW BEING PULLED. NOT READY FOR INSPECTION.
Underslab Plumbing Inspection - Commercial Passed 4/4/2019 4/4/2019 at 11:30 AM 04/04/2019
All Rough Inspection - Commercial Passed 4/11/2019 4/11/2019 04/11/2019
Above Ceiling Inspection Passed 5/8/2019 5/8/2019 at 9:00 AM 05/08/2019
Underground Electrical Inspection - Commercial Partial 05/15/2019
Misc
Partial Correction
12/12/2018
LIGHT POLE BASE NW CORNER BY BUILDING APPROVED from sign to vault for sump pump for the backflow pit
Sprinkler - Hydrostatic Test Passed 6/4/2019 06/04/2019
Alarm Test Passed 6/5/2019 06/05/2019
Sprinkler - Flow Test Passed 6/5/2019 06/05/2019
Occupancy Inspection - Fire Temporary C of O 6/5/2019 06/05/2019
Sidewalk Inspection Partial 6/6/2019 6/6/2019 06/06/2019
Misc
Informational
06/06/2019
PRE-POUR INSPECTION SMALL SECTION OF SIDEWALK THAT WAS TORN OUT FOR WATER TIE IN. At time of inspection, Sidewalk appears to meet ADA and Lee Summit spec. Sidewalk has proper amount of gravel and is compacted
Occupancy Inspection - Planning Temporary C of O 6/10/2019 06/10/2019
Corrective Action Required
06/10/2019
Complete installation of sod per the approved landscape plan.
Occupancy Inspection - Fire Passed 6/10/2019 06/10/2019
Final Inspection - Commercial Failed 6/10/2019 at 10:00 AM 06/10/2019
Misc
Corrective Action Required
06/10/2019
-SUBMIT AS GRADED SURVEY FOR DETENTION BASIN -WATER METER NEEDS TO BE SET FLUSH WITH THE ELEVATION OF THE SIDEWALK -WATER METER NEEDS TO BE 14"-18" FROM THE METER WELL LID -NORTH MAN HOLE NEEDS TO BE FLUSH WITH GRADE -OBTAIN PLANNING APPROVAL
Occupancy Inspection - Water Utilities Passed 6/10/2019 06/13/2019
Occupancy Inspection - Planning Passed 06/14/2019
Occupancy Inspection - Engineering Temporary C of O 6/10/2019 06/20/2019
Misc
Corrective Action Required
06/10/2019
Need As- Graded for detention basin before substantial completion can be given.
Occupancy Inspection - Codes Commercial Temporary C of O 6/10/2019 06/20/2019
Misc
Corrective Action Required
06/20/2019
OBTAIN FINAL ENGINEERING APPROVAL
Final Inspection - Commercial Passed 6/13/2019 07/12/2019
Misc
Corrective Action Required
06/10/2019
-SUBMIT AS GRADED SURVEY FOR DETENTION BASIN -WATER METER NEEDS TO BE SET FLUSH WITH THE ELEVATION OF THE SIDEWALK -WATER METER NEEDS TO BE 14"-18" FROM THE METER WELL LID -NORTH MAN HOLE NEEDS TO BE FLUSH WITH GRADE -OBTAIN PLANNING APPROVAL
Documents & Images
Date Uploaded File Type Document Name
12/01/2017 Letter Fire Building Plan Review
12/07/2017 Letter Codes P/R Corrections Document
12/19/2017 Letter Fire Building Plan Review
12/20/2017 Spec Insp
03/15/2018 Receipt Receipt for transaction: 2018-000974
03/19/2018 Letter Codes Plan Review Conditions
03/20/2018 Letter Codes Building Permit
07/03/2018 Letter Inspection Summary
07/13/2018 Letter Inspection Summary
09/21/2018 Letter Inspection Summary
09/27/2018 Letter DE-Daily Inspection Summary
11/30/2018 Letter INSPECTION SUMMARY
11/30/2018 Letter INSPECTION SUMMARY
12/12/2018 Letter INSPECTION SUMMARY
12/14/2018 Letter INSPECTION SUMMARY
03/06/2019 Letter Fire Building Plan Review
03/13/2019 City Letter_2019-3-13
03/13/2019 Wall Finish @ Mop Sinks
03/21/2019 Receipt Receipt for transaction: 2019-000980
03/22/2019 Letter Fire (Sprinkler) Plan Review
04/04/2019 Letter INSPECTION SUMMARY
04/11/2019 Letter INSPECTION SUMMARY
04/17/2019 Letter Fire (Alarm) Plan Review Notice
05/08/2019 Letter INSPECTION SUMMARY
06/06/2019 Sidewalk section pre-pour
06/06/2019 Letter INSPECTION SUMMARY
06/10/2019 Letter DE-Daily Inspection Summary
06/10/2019 Letter INSPECTION SUMMARY
06/20/2019 Letter INSPECTION SUMMARY
06/20/2019 Letter Codes Temporary Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home