Permit Application Status

PRCOM20173278


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20173278
Building Permit - Commercial
Voided
JOHN KNOX VILLAGE
ALTERATION COMMERCIAL
ALTER BUILDING FROM SENIOR APARTMENTS TO ASSISTED CARE - INCLUDES NEW STAIRWAYS
10/02/2017
04/07/2018
04/09/2018
Locations
Contacts
PARIC CORPORATION , Address:77 WESTORT PLAZA STE 250, Phone:(636) 561-9795  
  
  
  
SFCS ARCHITECTS, Address:1927 SOUTH TRYON ST, SUITE 207, Phone:(704) 372-7327  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Rejected 11/06/2017 11/08/2017
Joe Frogge
LC - MEP Subs
Corrective Action Required
11/06/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved 11/13/2017 11/08/2017
Joe Frogge
Gen - Submittal documents 7-137
Resolved
11/08/2017

Missouri Board for Architects, Professional Engineers, Professional Land Surveyors and Professional Landscape Architects – Board Rules, Division 2030 – Chapter 3, 20 CSR 2030-3.060 Licensees Seal Documents must bear design professionals original seal with signature and date. (relevant portion paraphrased – reference original document for additional information) Action required: Provide at least one copy of plan set with original seals/signatures or provide letters from design professionals attesting to the fact that these copies represent their digital seal.
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Resolved
11/08/2017

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide at least 18" clearance at latch side of 2nd floor door into stair #1.
Misc
Resolved
11/08/2017

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Add fire ratings to door schedule and provide verification that existing doors and frames have appropriate ratings.
Misc
Resolved
11/08/2017

ICC A117.1-2009 Section 1004.11.1 Grab Bar and Shower Seat Reinforcement. Reinforcement shall be provided for the future installation of grab bars and shower seats at water closets, bathtubs, and shower compartments. Where walls are located to permit the installation of grab bars and seats complying with Section 604.5 at water closets; grab bars complying with Section 607.4 at bathtubs; and for grab bars and shower seats complying with Sections, 608.3, 608.2.1.3, 608.2.2.3 and 608.2.3.2 at shower compartments; reinforcement shall be provided for the future installation of grab bars and seats complying with those requirements. (see code for exceptions) Action required: Provide reinforcement for future grab bar installation at all required locations.
Misc
Resolved
11/08/2017

2012 IBC 1809.5 Frost protection. Except where otherwise protected from frost, foundations and other permanent supports of buildings and structures shall be protected from frost by one or more of the following methods: 1. Extending below the frost line of the locality; 2. Constructing in accordance with ASCE 32; or 3. Erecting on solid rock. (see code section for exceptions) Shallow foundations shall not bear on frozen soil unless such frozen condition is of a permanent character. Action required: Modify footing details to show that all will be installed below minimum frost depth of 36".
Fire Plan Review Approved with Conditions 11/13/2017 11/08/2017
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
11/06/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings for approval of any modifications to be done to the fire alarm system.
Construction documents - Fire protection systems
Corrective Action Required
11/06/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings for approval of any modifications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
11/06/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) If any fire alarm system devices are added, moved, relocated or replaced in the residences or corridors during the renovation process an ecceptance test will be required prior to the final occupancy inspection. Contact the fire department to schedule testing (816)969-1300.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Resolved
11/08/2017

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ACTION REQUIRED:(veriifed at inspection) The existing fire sprinkler system shall be current with all required service and maintenance. A current service tag shall be posted on the systems riser.
Misc
Resolved
11/08/2017

Restrooms ACTION REQUIRED:(information purposes) If fire sprinklers are not already existing in the bathrooms to be renovated, the new square footage puts them at 55 square feet which NFPA 13R requires them to have sprinklers installed.
Misc
Resolved
11/08/2017

Emergency lighting ACTION REQUIRED:(information purposes) Maintain all emergency lighting throughout the corridors and stairways during all construction phases.
Misc
Resolved
11/08/2017

Fire extinguishers ACTION REQUIRED:(information purposes) Maintain fire extinguishers in the corridors. If moved during construction they shall be replaced prior to ther final occupancy inspection.
Building Plan Review Rejected 10/12/2017 10/09/2017
Joe Frogge
Gen - Submittal documents 7-137
Corrective Action Required
10/09/2017

Missouri Board for Architects, Professional Engineers, Professional Land Surveyors and Professional Landscape Architects – Board Rules, Division 2030 – Chapter 3, 20 CSR 2030-3.060 Licensees Seal Documents must bear design professionals original seal with signature and date. (relevant portion paraphrased – reference original document for additional information) Action required: Provide at least one copy of plan set with original seals/signatures or provide letters from design professionals attesting to the fact that these copies represent their digital seal.
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Corrective Action Required
10/09/2017

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide at least 18" clearance at latch side of 2nd floor door into stair #1.
Misc
Corrective Action Required
10/09/2017

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Add fire ratings to door schedule and provide verification that existing doors and frames have appropriate ratings.
Misc
Corrective Action Required
10/09/2017

ICC A117.1-2009 Section 1004.11.1 Grab Bar and Shower Seat Reinforcement. Reinforcement shall be provided for the future installation of grab bars and shower seats at water closets, bathtubs, and shower compartments. Where walls are located to permit the installation of grab bars and seats complying with Section 604.5 at water closets; grab bars complying with Section 607.4 at bathtubs; and for grab bars and shower seats complying with Sections, 608.3, 608.2.1.3, 608.2.2.3 and 608.2.3.2 at shower compartments; reinforcement shall be provided for the future installation of grab bars and seats complying with those requirements. (see code for exceptions) Action required: Provide reinforcement for future grab bar installation at all required locations.
Misc
Corrective Action Required
10/09/2017

2012 IBC 1809.5 Frost protection. Except where otherwise protected from frost, foundations and other permanent supports of buildings and structures shall be protected from frost by one or more of the following methods: 1. Extending below the frost line of the locality; 2. Constructing in accordance with ASCE 32; or 3. Erecting on solid rock. (see code section for exceptions) Shallow foundations shall not bear on frozen soil unless such frozen condition is of a permanent character. Action required: Modify footing details to show that all will be installed below minimum frost depth of 36".
Licensed Contractors Rejected 10/02/2017 10/09/2017
Joe Frogge
LC - MEP Subs
Corrective Action Required
10/09/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 10/12/2017 10/04/2017
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
10/04/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings for approval of any modifications to be done to the fire alarm system.
Construction documents - Fire protection systems
Corrective Action Required
10/04/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings for approval of any modifications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
10/04/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) If any fire alarm system devices are added, moved, relocated or replaced in the residences or corridors during the renovation process an ecceptance test will be required prior to the final occupancy inspection. Contact the fire department to schedule testing (816)969-1300.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
10/04/2017

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ACTION REQUIRED:(veriifed at inspection) The existing fire sprinkler system shall be current with all required service and maintenance. A current service tag shall be posted on the systems riser.
Misc
Corrective Action Required
10/04/2017

Restrooms ACTION REQUIRED:(information purposes) If fire sprinklers are not already existing in the bathrooms to be renovated, the new square footage puts them at 55 square feet which NFPA 13R requires them to have sprinklers installed.
Misc
Corrective Action Required
10/04/2017

Emergency lighting ACTION REQUIRED:(information purposes) Maintain all emergency lighting throughout the corridors and stairways during all construction phases.
Misc
Corrective Action Required
10/04/2017

Fire extinguishers ACTION REQUIRED:(information purposes) Maintain fire extinguishers in the corridors. If moved during construction they shall be replaced prior to ther final occupancy inspection.
Inspections

There are no inspections for this permit application.

Documents & Images
Date Uploaded File Type Document Name
10/04/2017 Letter Fire Building Plan Review
10/09/2017 Astoria Building Code Analysis
10/09/2017 Letter Codes P/R Corrections Document
11/08/2017 Letter Fire Building Plan Review
04/09/2018 RE Astoria
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home