Permit Application Status

PRCOM20172531


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20172531
Building Permit - Commercial
Certificate of Occupancy
PARROT PROPERTIES INC
NEW MULTI-FAMILY
MERIDIAN AT VIEW HIGH - BUILDING #15NEW 2 STORY APARTMENT BUILDING WITH PARKING GARAGE BENEATH FOUNDATION PERMIT - PRCOM20181910
07/24/2017
12/06/2019
09/21/2020
Locations
Contacts
CITYSCAPE CONSTRUCTION VIEW HIGH LLC, Address:10 W CARMEL DR STE 200, Phone:(317) 574-1600 Ext:100  
STANDARD HEATING & COOLING TOO LLC, Address:2006 E PRAIRIE CIRCLE , Phone:(913) 782-5409  
STANDARD ELECTRIC COMPANY INC, Address:2006 E PRAIRIE CIRCLE, Phone:(913) 782-5409  
GARRISON PLUMBING, Address:15430 S MAHAFFIE ST STE 102, Phone:(913) 768-1311  
SGN+A ARCHITECTS, Address:315 W PONCE DE LEON AVE #755, Phone:(404) 373-7370  
LATIMER SOMMERS & ASSOCIATES PA, Address:3639 SW SUMMERFIELD DR STE A, Phone:(785) 233-3232  
PARROT PROPERTIES INC, Address:11303 VIEW HIGH DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 07/25/2018 06/19/2018
Joe Frogge
Final Development Plan Review Approved 08/07/2018 02/16/2018
Joe Frogge
Building Plan Review Approved 08/07/2018 02/16/2018
Joe Frogge
Special Inspections Review Approved 08/24/2017
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Multi-Family $8,160.59 $8,160.59 Paid 12/06/2019
$8,160.83
8331507-Sewer Connection Fee $3,000.00 $3,000.00 Paid 12/06/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 12/9/2019 12/9/2019 12/09/2019
Misc
Corrective Action Required
12/09/2019
UPPER PERIMETER FOOTING UFER ON SOUTH END
Footing Inspection - Commercial Partial 1/2/2020 1/2/2020 01/02/2020
Misc
Resolved
01/02/2020
Interior footings on west side of building 13 are ok to pour
Footing Inspection - Commercial Passed 1/8/2020 1/8/2020 01/08/2020
Sprinkler - Hydrostatic Test Failed 4/24/2020 04/24/2020
Sprinkler - Hydrostatic Test Failed 4/27/2020 04/27/2020
All Rough Inspection - Commercial Failed 4/27/2020 4/27/2020 04/27/2020
THIRD FLOOR
Corrective Action Required
04/27/2020
SOUTH END - - 308 BOCA PLATE MECHANICAL ROOM DECK - - 306 FIRE COLLAR TUB DEAD SPACE - - 305 FIRE CAULK DEAD SPACE KITCHEN ISLAND BOTTOM PLATE -
SECOND FLOOR
Corrective Action Required
04/27/2020
SOUTH END -G12 TUB TRAB ABOVE DOORWAY-
FIRST FLOOR
Corrective Action Required
04/27/2020
SOUTH END - - 106 FIRE COLLARS TUB DEAD SPACE - - 108 FIRE COLLARS TUB DEAD SPACE - - TERRACE ENTRY JOIST HANGERS -
All Rough Inspection - Commercial Failed 4/28/2020 4/28/2020 04/28/2020
THIRD FLOOR
Corrective Action Required
04/27/2020
SOUTH END - - 308 BOCA PLATE MECHANICAL ROOM DECK - - 306 FIRE COLLAR TUB DEAD SPACE - - 305 FIRE CAULK DEAD SPACE KITCHEN ISLAND BOTTOM PLATE - NORTH END -G1 STRAP & FIRE CAULK TOP PLATE - - 304 MECH ROOM HOLE IN FLOOR, FIRE CAULK DEAD SPACE - - 301 PLUMBING NAIL GUARD LAUNDRY -
SECOND FLOOR
Corrective Action Required
04/27/2020
SOUTH END -G12 TUB TRAB ABOVE DOORWAY-
FIRST FLOOR
Corrective Action Required
04/27/2020
SOUTH END - - 106 FIRE COLLARS TUB DEAD SPACE - - 108 FIRE COLLARS TUB DEAD SPACE - - TERRACE ENTRY JOIST HANGERS -
All Rough Inspection - Commercial Passed 5/6/2020 05/06/2020
THIRD FLOOR
Resolved
05/06/2020
SECOND FLOOR
Resolved
05/06/2020
FIRST FLOOR
Resolved
05/06/2020
Rated Assembly Inspection Passed 5/6/2020 5/6/2020 05/06/2020
Sprinkler - Hydrostatic Test Failed 5/8/2020 05/08/2020
Rated Assembly Inspection Failed 5/20/2020 5/20/2020 05/20/2020
SECOND FLOOR
Corrective Action Required
05/20/2020
NORTH END - 301 REMOVE TYPE X CEILING ABOVE ENTRY DOOR - - 303 COMPLETE SCREW PATTERN BEDROOM CEILING - - SOUTH END NOT READY
FIRST FLOOR
Corrective Action Required
05/20/2020
NORTH END - G1 , G2 , G3 ROCK NOT COMPLETE - G5 FULL OF TRASH - - 204 REMOVE TYPE X CEILING REPLACE WITH TYPE X , COMPLETE SCREW PATTERN BOTTOM PLATE - - 202 REMOVE TYPE X CEILING BED CLOSET & ENTRY DOOR, COMPLETE SCREW PATTERN REAR BATH - - SOUTH END NOT READY -
LOWER LEVEL
Corrective Action Required
05/20/2020
NORTH END ELECTRICAL ROOM NO ROCK HUNG UNITS OK TO TAPE SOUTH END NOT READY
Sprinkler - Hydrostatic Test Failed 5/22/2020 05/22/2020
Rated Assembly Inspection Partial 5/27/2020 5/27/2020 05/27/2020
Misc
Corrective Action Required
05/27/2020
- G2 replace type X on ceiling with type C - - G3 replace type X on ceiling with type C - - G7 complete screw pattern at bottom plate - - south corridor replace type X on ceiling with type C - - G12 no rock at meter bank -
Rated Assembly Inspection Partial 5/29/2020 5/29/2020 05/29/2020
FIRST FLOOR
Resolved
05/29/2020
LOWER LEVEL
Corrective Action Required
05/29/2020
SOUTH END NO ROCK ELECTRICAL ROOM
SECOND FLOOR
Resolved
05/29/2020
Sprinkler - Hydrostatic Test Passed 6/18/2020 06/18/2020
Electrical Service Inspection Passed 6/24/2020 6/24/2020 06/24/2020
Misc
Informational
06/24/2020
- BLDG # 15 - - 16 UNITS, 1 HOUSE METER -
Underslab Electrical Inspection - Commercial Passed 9/1/2020 9/1/2020 09/01/2020
Misc
Informational
09/01/2020
- LIGHT POLE BASES BLDG 15 & 16 -
Piers/Caissons Inspection - Commercial Passed 9/1/2020 09/01/2020
Misc
Informational
09/01/2020
- LIGHT POLE BASES BLDG # 15 & 16 -
Underground Electrical Inspection - Commercial Passed 9/1/2020 09/01/2020
Misc
Informational
09/01/2020
- UNDERGROUND FOR LIGHT POLES BLDG # 15 & 16 -
Alarm Test Passed 9/1/2020 09/01/2020
Sprinkler - Flow Test Passed 9/1/2020 09/01/2020
Occupancy Inspection - Water Utilities Passed 9/8/2020 09/02/2020
Occupancy Inspection - Engineering Passed 9/8/2020 09/08/2020
Corrective Action Required
09/08/2020
Parking areas shall be striped.
Occupancy Inspection - Fire Failed 9/8/2020 09/08/2020
Occupancy Inspection - Planning Failed 9/8/2020 09/08/2020
Occupancy Inspection - Codes Commercial Failed 9/8/2020 9/8/2020 09/08/2020
Misc
Corrective Action Required
09/08/2020
- TOP COAT & STRIPPING PARKING LOT - - PROVIDE HAMMER ARRESTORS DISHWASHERS - - 301 GFCI AT RANGE, TIGHTEN SELF CLOSING HINGES ENTERY DOOR - - 302 BROKEN WINDOW BATHROOM, TIGHTEN SELF CLOSING HINGE ENTRY DOOR - - 202 GFCI NEXT TO REFRIGERATOR - - 204 ADA INSULATE PIPES UNDER SINK - - 2-6 ADA INSULATE PIPES UNDER SINK - - 208 NAIL JOIST HANGER DECK - - 104 NAIL JOIST HANGER DECK - - FIRE ALARM PANEL ROOM FIRE CAULK CEILING - - SPRINKLER ROOM FIRE CAULK CEILING - - GUARDRAILS AT NORTH & SOUTH A/C CONDENSORS - - PROVIDE TAMPER PROOF CAPS A/C CONDENSORS - - G-2 GUARDRAIL SHALL BE 42" - - G-3 GUARDRAIL SHALL BE 42", 36" CLEARANCE - - G-4 GUARDRAIL SHALL BE 42" - - G-8 " " - - G-10 " "
Rated Assembly Inspection Passed 9/8/2020 09/08/2020
LOWER LEVEL
Corrective Action Required
05/29/2020
SOUTH END NO ROCK ELECTRICAL ROOM
Occupancy Inspection - Fire Passed 9/21/2020 09/21/2020
Occupancy Inspection - Planning Passed 11/05/2020
Occupancy Inspection - Codes Commercial Full C of O 9/21/2020 9/21/2020 11/06/2020
Misc
Resolved
11/06/2020
- PROVIDE TAMPER PROOF CAPS A/C
Documents & Images
Date Uploaded File Type Document Name
10/16/2017 Meridian Site Map
12/06/2019 Letter DS Building Permit
12/09/2019 Letter INSPECTION SUMMARY
01/02/2020 Letter INSPECTION SUMMARY
01/08/2020 Letter INSPECTION SUMMARY
04/27/2020 Letter INSPECTION SUMMARY
04/28/2020 Letter INSPECTION SUMMARY
05/06/2020 Letter INSPECTION SUMMARY
05/06/2020 Letter INSPECTION SUMMARY
05/20/2020 Letter INSPECTION SUMMARY
05/27/2020 Letter INSPECTION SUMMARY
05/29/2020 Letter INSPECTION SUMMARY
06/24/2020 Letter INSPECTION SUMMARY
09/01/2020 Letter INSPECTION SUMMARY
09/01/2020 Letter INSPECTION SUMMARY
09/01/2020 Letter INSPECTION SUMMARY
09/08/2020 Letter INSPECTION SUMMARY
09/21/2020 Letter Codes Temporary Certificate of Occupancy
09/21/2020 Letter INSPECTION SUMMARY
11/06/2020 Letter Field Certificate of Occupancy
11/06/2020 Letter Codes Final Certificate of Occupancy
11/06/2020 Letter Codes Temporary Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home