Permit Application Status

PRCOM20171355


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20171355
Building Permit - Commercial
Voided
CSC INVESTMENTS II LLC
NEW TENANT FINISH
TENANT FINISH FOR OFFICE WITH SOME STORAGE **due to timing both this TF permit and the shell were approved simultaneously. This permit will be voided and all fees and any relevant plan review conditions will be moved to full building permit PRCOM20170784
05/01/2017
10/31/2017
06/13/2017
Locations
Contacts
CSC INVESTMENTS II LLC, Address:3350 NE RALPH POWELL RD  
CAPITAL CONSTRUCTION SERVICES LLC, Address:2642 NE HAGAN RD, Phone:(816) 875-0018  
DAVIDSON ARCHITECTURE & ENGINEERING, Address:4301 INDIAN CREEK PKWY, Phone:(913) 451-9390  
  
  
  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 05/24/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
03/26/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Acceptance testing of the system is required prior to the final occupancy inspection. contact the fire department to schedule testing. (816)969-1300.
Sprinkler Plan Review Released for Construction 05/24/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
12/04/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Field tests and acceptance testing will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. 816-969-1300.
Fire Plan Review Approved with Conditions 05/12/2017 05/09/2017
Joe Dir
05/09/2017

05/09/2017

Construction documents for fire alarm systems
Corrective Action Required
05/05/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED: (information purposes) have the fire alarm system contractor provide shop drawings for the fire alarm system to be installed.
Address numbers required
Corrective Action Required
05/05/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Post the numeric address on the building in a contrasting color to the background. Address shall be readable from the roadway.
Knox box required
Corrective Action Required
05/05/2017

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. ACTION REQUIRED: (information purposes) Knox boxes can be obtained online at knoxbox.com The knox box shall be mounted on the exterior of the building above the fire department connection approximately 5 to 6 feet above finish grade.
Construction documents - Fire protection systems
Corrective Action Required
05/05/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED: (information purposes) Have the fire sprinkler system contractor provide shop drawings of the fire sprinkler system to be installed.
Installation acceptance testing
Corrective Action Required
05/05/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:( information purposes) Field tests and acceptance testing of the fire sprinkler and fire alarm systems shall be required prior to the final occupancy inspection. To schedule a test contact the fire department at 816-969-1300.
Portable fire extinguishers - general
Corrective Action Required
05/05/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED: (verified at inspection) Provide 2A-10BC fire extingusihers. one fire extinguisher for every 3,000 sq feet of useable space. A maximum travel distance to a fire extinguisher shall have a maximum travel distance of 75 feet from anywhere within the structure.
Misc
Corrective Action Required
05/05/2017

Door operations ACTION REQUIRED: No keyed locks on the egress side of an exit (verified at inspection) [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Misc
Corrective Action Required
05/05/2017

controlled access doors ACTION REQUIRED:(verified at testing) [B] 1008.1.9.8  Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1 or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2, are permitted to be equipped with an approved entrance and egress access control system, listed in accordance with UL 294, which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public. [B] 1008.1.9.9 Electromagnetically locked egress doors. Doors in the means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2, and doors to tenant spaces in Group A, B, E, M, R-1 or R-2, shall be permitted to be electromagnetically locked if equipped with listed hardware that incorporates a built-in switch and meet the requirements below: 1. The listed hardware that is affixed to the door leaf has an obvious method of operation that is readily operated under all lighting conditions. 2. The listed hardware is capable of being operated with one hand. 3. Operation of the listed hardware directly interrupts the power to the electromagnetic lock and unlocks the door immediately. 4. Loss of power to the listed hardware automatically unlocks the door. 5. Where panic or fire exit hardware is required by Section 1008.1.10, operation of the listed panic or fire exit hardware also releases the electromagnetic lock.
Posting of occupant load
Corrective Action Required
05/05/2017

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED: (verified at inspection) post the occupant load in all training / conference rooms
Misc
Corrective Action Required
05/09/2017

There were alot of comments made to the effect refer to the shell building drawings. These plans are not for a shell building they are for a tenant finish. Any conditions that were listed for the tenant finish should have been transfered from the shell drawings to the tenant finish, to prevent alot of cross referencing of plans.
Building Plan Review Approved with Conditions 05/12/2017 05/08/2017
Joe Frogge
Misc
Corrective Action Required
05/05/2017

This tenant finish project is tied to a shell permit. Action required: Occupancy will not be granted until shell building has been closed. Comment is for informational purposes. 5/8/17 - acknowledged
Project cost
Corrective Action Required
05/05/2017

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes. 5/8/17 - acknowledged
License Tax Application
Corrective Action Required
05/05/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 5/8/17 - acknowledged
Misc
Resolved
05/08/2017

2012 IBC 1021.2 Exits from stories. Two exits, or exit access stairways or ramps providing access to exist, from any story or occupied roof shall be provided where one of the following conditions exist: 1. The occupant load or number of dwelling units exceeds one of the values in Table 1021.2(1) or 1021.2(2). 2. The exit access travel distance exceeds that specified in Table 1021.2(1) or 1021.2(2) as determined in accordance with the provisions of Section 1016.1. 3. Helistop landing areas located on buildings or structures shall be provided with two exits, or exit access stairways or ramps providing access to exits. (see code section for exceptions) Action required: Due to occupant load in excess of 50, each training room requires an additional exit. 5/8/17 -recalculated as educational rooms
Bldg - Door swing 1008.1.2
Resolved
05/08/2017

2012 IBC 1008.1.2 – Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for possible exceptions.) Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. Action required: Sliding doors are not allowed as exit access components. (this applies to the barn door, the file room doors meet an exemption) 5/8/17 - to be used as movable partition, not a door
Mech - Materials within plenums 602.2.1
Resolved
05/08/2017

2012 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action required: PVC is not allowed in plenums. Clarify locations of use. 5/8/17 - clarified
Misc
Resolved
05/08/2017

Additional information required. Provide the following information: - Sizes of Grounding Electrode Conductors. - Generator cut sheets. (2 copies) - Pier/foundation details for fence posts and trash enclosure.
Licensed Contractors Rejected 05/05/2017 05/08/2017
Joe Frogge
LC - MEP Subs
Corrective Action Required
05/05/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 5/8/17 - acknowledged
Fire Plan Review Rejected 05/11/2017 05/03/2017
Joe Dir
Misc
Corrective Action Required
05/03/2017

fire hydrant ACTION REQUIRED: provide a civil plan sheet to show the location of a fire hydrant in correlation to the fire department connection 903.3.7 Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch storz fitting and located within 100 feet of a fire hydrant, or as approved by the code official.
Construction documents for fire alarm systems
Corrective Action Required
05/03/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED: (information purposes) have the fire alarm system contractor provide shop drawings for the fire alarm system to be installed.
Address numbers required
Corrective Action Required
05/03/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Post the numeric address on the building in a contrasting color to the background. Address shall be readable from the roadway.
Knox box required
Corrective Action Required
05/03/2017

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. ACTION REQUIRED: (information purposes) Knox boxes can be obtained online at knoxbox.com The knox box shall be mounted on the exterior of the building above the fire department connection approximately 5 to 6 feet above finish grade.
Construction documents - Fire protection systems
Corrective Action Required
05/03/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED: (information purposes) Have the fire sprinkler system contractor provide shop drawings of the fire sprinkler system to be installed.
Installation acceptance testing
Corrective Action Required
05/03/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:( information purposes) Field tests and acceptance testing of the fire sprinkler and fire alarm systems shall be required prior to the final occupancy inspection. To schedule a test contact the fire department at 816-969-1300.
Portable fire extinguishers - general
Corrective Action Required
05/03/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED: (verified at inspection) Provide 2A-10BC fire extingusihers. one fire extinguisher for every 3,000 sq feet of useable space. A maximum travel distance to a fire extinguisher shall have a maximum travel distance of 75 feet from anywhere within the structure.
Misc
Corrective Action Required
05/03/2017

Door operations ACTION REQUIRED: No keyed locks on the egress side of an exit (verified at inspection) [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Misc
Corrective Action Required
05/03/2017

Panic hardware ACTION REQUIRED: [B] 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware.
Misc
Corrective Action Required
05/03/2017

controlled access doors ACTION REQUIRED: [B] 1008.1.9.8  Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1 or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2, are permitted to be equipped with an approved entrance and egress access control system, listed in accordance with UL 294, which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public. [B] 1008.1.9.9 Electromagnetically locked egress doors. Doors in the means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2, and doors to tenant spaces in Group A, B, E, M, R-1 or R-2, shall be permitted to be electromagnetically locked if equipped with listed hardware that incorporates a built-in switch and meet the requirements below: 1. The listed hardware that is affixed to the door leaf has an obvious method of operation that is readily operated under all lighting conditions. 2. The listed hardware is capable of being operated with one hand. 3. Operation of the listed hardware directly interrupts the power to the electromagnetic lock and unlocks the door immediately. 4. Loss of power to the listed hardware automatically unlocks the door. 5. Where panic or fire exit hardware is required by Section 1008.1.10, operation of the listed panic or fire exit hardware also releases the electromagnetic lock.
Posting of occupant load
Corrective Action Required
05/03/2017

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED: (verified at inspection) post the occupant load in all training / conference rooms
Building Plan Review Rejected 05/11/2017 05/02/2017
Joe Frogge
Misc
Corrective Action Required
05/02/2017

This tenant finish project is tied to a shell permit. Action required: Occupancy will not be granted until shell building has been closed. Comment is for informational purposes.
Project cost
Corrective Action Required
05/02/2017

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes.
License Tax Application
Corrective Action Required
05/02/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
05/02/2017

2012 IBC 1021.2 Exits from stories. Two exits, or exit access stairways or ramps providing access to exist, from any story or occupied roof shall be provided where one of the following conditions exist: 1. The occupant load or number of dwelling units exceeds one of the values in Table 1021.2(1) or 1021.2(2). 2. The exit access travel distance exceeds that specified in Table 1021.2(1) or 1021.2(2) as determined in accordance with the provisions of Section 1016.1. 3. Helistop landing areas located on buildings or structures shall be provided with two exits, or exit access stairways or ramps providing access to exits. (see code section for exceptions) Action required: Due to occupant load in excess of 50, each training room requires an additional exit.
Bldg - Door swing 1008.1.2
Corrective Action Required
05/02/2017

2012 IBC 1008.1.2 – Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for possible exceptions.) Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. Action required: Sliding doors are not allowed as exit access components. (this applies to the barn door, the file room doors meet an exemption)
Mech - Materials within plenums 602.2.1
Corrective Action Required
05/02/2017

2012 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action required: PVC is not allowed in plenums. Clarify locations of use.
Misc
Corrective Action Required
05/02/2017

Additional information required. Provide the following information: - Sizes of Grounding Electrode Conductors. - Generator cut sheets. (2 copies) - Pier/foundation details for fence posts and trash enclosure.
Licensed Contractors Rejected 05/11/2017 05/02/2017
Joe Frogge
LC - MEP Subs
Corrective Action Required
05/02/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Alarm Test Partial 7/27/2018 07/27/2018
Documents & Images
Date Uploaded File Type Document Name
05/03/2017 Letter Fire Building Plan Review
05/04/2017 Letter Codes P/R Corrections Document
05/09/2017 Letter Fire Building Plan Review
12/04/2017 Letter Fire (Sprinkler) Plan Review
03/26/2018 Letter Fire (Alarm) Plan Review Notice
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home