Summary
PRCOM20170898
Building Permit - Commercial
Final Completion
DACUR INVESTMENT COMPANY INC
CHANGE OF TENANT
TENANT FINISH FOR SHIPPING/RECEIVING STORE **drawing is in plan review file
03/28/2017
04/12/2017
05/08/2017
Locations
Contacts
CATES SERVICE COMPANY, Address:14361 W 96TH TER, Phone:(913) 888-4470  
ELECTRIC SERVICE SPECIALIST , INC., Address:14612 W 71ST TERRACE, Phone:(913) 909-3858  
KEVIN GINNINGS PLUMBING SERVICE INC, Address:PO BOX 6, Phone:(816) 380-6316  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
ZIPCO CONTRACTING INC, Address:4110 N CORRINGTON AVE, Phone:(816) 471-3797  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 04/07/2017 04/12/2017
Joe Frogge
LC - General Contractor
Resolved
04/12/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
04/12/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved with Conditions 04/07/2017 03/31/2017
Joe Frogge
Project cost
Resolved
04/12/2017

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes.
Fire Plan Review Approved with Conditions 04/07/2017 03/30/2017
Joe Dir
Misc
Corrective Action Required
03/30/2017

ACTION REQUIRED: No keyed locks on the egress side of an exit [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. [B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. (verified at inspection)
Address numbers required
Corrective Action Required
03/30/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: Post the numeric address on the exterior of the front and rear doors in a color that is contrasting where posted. (verified at inspection)
Portable fire extinguishers - general
Corrective Action Required
03/30/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED: Provide at a minimum one 2A-10BC fire extinguisher to be mounted on a normal path of travel close to an exit. (verified at inspection)
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $71.73 $71.73 Paid 04/12/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 4/13/2017 04/13/2017
Misc
Corrective Action Required
04/13/2017
- uncover 5 outlet boxes in wall from box to ceiling or horizontal to next box. - remove ceiling tile for inspection of electrical going into wall.
In-wall Inspection Failed 4/14/2017 04/14/2017
Misc
Corrective Action Required
04/13/2017
- 4 outlet boxes at the center wall need equipment grounding conductors. - leave some of the ceiling tiles out for inspection of securing the MC cable to the new boxes. ok to cover the wall. if device is installed leave out for inspection of EG.
Occupancy Inspection - Fire Passed 4/26/2017 04/26/2017
In-wall Inspection Passed 4/14/2017 04/26/2017
Misc
Resolved
04/26/2017
- 4 outlet boxes at the center wall need equipment grounding conductors. - leave some of the ceiling tiles out for inspection of securing the MC cable to the new boxes. ok to cover the wall. if device is installed leave out for inspection of EG.
Above Ceiling Inspection Passed 4/26/2017 04/26/2017
Occupancy Inspection - Codes Commercial Failed 4/26/2017 4/26/2017 04/26/2017
Misc
Corrective Action Required
04/26/2017
AFFIX ACCESSIBLE RESTROOM SIGN AT DOOR
Misc
Corrective Action Required
04/26/2017
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF
Misc
Corrective Action Required
04/26/2017
ELECT RECPTS REQUIRED AT SERVICE COUNTER
Misc
Corrective Action Required
04/26/2017
EXTERIOR LIGHTED SIGN SUBJECT TO APPROVAL
Misc
Corrective Action Required
04/26/2017
OK TO SET UP FOR BUSINESS
Occupancy Inspection - Codes Commercial Temporary C of O 4/27/2017 4/27/2017 04/27/2017
Misc
Corrective Action Required
04/26/2017
AFFIX ACCESSIBLE RESTROOM SIGN AT DOOR
Misc
Corrective Action Required
04/26/2017
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF
Misc
Corrective Action Required
04/26/2017
ELECT RECPTS REQUIRED AT SERVICE COUNTER
Misc
Corrective Action Required
04/26/2017
NEC 600.4 ELECTRIC SIGN MARKINGS: SIGNS AND OUTSIDE LIGHTING SYSTEMS SHALL BE SHOP-LABELED WITH LISTING, MANUFACTURER'S NAME, TRADEMARK, OR OTHER MEANS OF IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING.
Misc
Resolved
04/27/2017
OK TO SET UP FOR BUSINESS
Final Inspection - Commercial Passed 5/5/2017 05/05/2017
Occupancy Inspection - Fire Passed 06/19/2017
Documents & Images
Date Uploaded File Type Document Name
03/30/2017 Letter Fire Building Plan Review
03/31/2017 Letter Codes P/R Corrections Document
04/12/2017 Receipt Receipt for transaction: 2017-001377
04/12/2017 Letter Codes Building Permit
04/12/2017 Letter Codes Plan Review Conditions
04/13/2017 Letter Inspection Summary
04/14/2017 Letter Inspection Summary
04/26/2017 Letter Inspection Summary
04/27/2017 Letter Codes Temporary Certificate of Occupancy
05/05/2017 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home