Summary
PRCOM20170889
Building Permit - Commercial
Final Completion
HOKE JAKE
ALTERATION COMMERCIAL
HYVEE DONUT FRYER AND HOOD **drawings are in plan review file
03/28/2017
04/10/2017
09/27/2017
05/31/2017
Locations
Contacts
HOKE JAKE, Address:PO BOX 388  
THE WALDINGER CORPORATION, Address:1800 LEVEE ROAD, Phone:(515) 323-8786  
WESTHUES ELECTRIC INC, Address:PO BOX 18220, Phone:(816) 356-5223  
HY VEE FOOD STORES INC, Address:5820 WESTOWN PKWY  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 03/28/2017 02/12/2018
Joe Frogge
Building Plan Review Approved 04/11/2017 04/10/2017
Joe Frogge
Misc
Resolved
04/10/2017

2012 IBC 603.1 Allowable Materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3: (see code for specific examples and exceptions) Action required: Wood nailers not allowed at roof curb assembly. Specify compliant materials.
Miscellaneous Correction
Resolved
04/10/2017

2012 IMC 505.2 Makeup air required. Exhaust hood systems capable of exhausting in excess of 400 cfm shall be provided with makeup air at a rate approximately equal to the exhaust air rate. Such makeup air systems shall be equipped with a means of closure and shall be automatically controlled to start and operate simultaneously with the exhaust system. Action required: Provide makeup air.
Miscellaneous Correction
Resolved
04/10/2017

2012 IMC 506.3.1 Grease Duct materials. Grease ducts serving Type I hoods shall be constructed of steel having a minimum thickness of 0.0575 inch (No. 16 gage) or stainless steel not less than 0.0450 inch (No. 18 gage) in thickness. Exception: Factory-built commercial kitchen grease ducts listed and labeled in accordance with UL 1978 and installed in accordance with Section 304.1. Action required: Specify compliant ductwork.
Licensed Contractors Approved 04/04/2017 04/10/2017
Joe Frogge
Fire Plan Review Approved with Conditions 04/11/2017 04/06/2017
Joe Dir
Misc
Corrective Action Required
04/04/2017

ACTION REQUIRED: Suppression system for the Type-1 hood shall be wired in the the buildings fire alarm system.
Installation acceptance testing
Corrective Action Required
04/04/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Acceptance testing of the type-1 hood suppression system shall be required prior to use of the hood and fryer. To schedule a test contact the fire department at 816-969-1300.
Building Plan Review Rejected 04/07/2017 03/31/2017
Joe Frogge
Misc
Corrective Action Required
03/31/2017

2012 IBC 603.1 Allowable Materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3: (see code for specific examples and exceptions) Action required: Wood nailers not allowed at roof curb assembly. Specify compliant materials.
Miscellaneous Correction
Corrective Action Required
03/31/2017

2012 IMC 505.2 Makeup air required. Exhaust hood systems capable of exhausting in excess of 400 cfm shall be provided with makeup air at a rate approximately equal to the exhaust air rate. Such makeup air systems shall be equipped with a means of closure and shall be automatically controlled to start and operate simultaneously with the exhaust system. Action required: Provide makeup air.
Miscellaneous Correction
Corrective Action Required
03/31/2017

2012 IMC 506.3.1 Grease Duct materials. Grease ducts serving Type I hoods shall be constructed of steel having a minimum thickness of 0.0575 inch (No. 16 gage) or stainless steel not less than 0.0450 inch (No. 18 gage) in thickness. Exception: Factory-built commercial kitchen grease ducts listed and labeled in accordance with UL 1978 and installed in accordance with Section 304.1. Action required: Specify compliant ductwork.
Licensed Contractors Rejected 03/28/2017 03/31/2017
Joe Frogge
LC - MEP Subs
Corrective Action Required
03/31/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed electrical contractor.
Fire Plan Review Approved with Conditions 04/07/2017 03/30/2017
Joe Dir
Misc
Corrective Action Required
03/30/2017

ACTION REQUIRED: Suppression system for the Type-1 hood shall be wired in the the buildings fire alarm system.
Installation acceptance testing
Corrective Action Required
03/30/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Acceptance testing of the type-1 hood suppression system shall be required prior to use of the hood and fryer. To schedule a test contact the fire department at 816-969-1300.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $56.08 $56.08 Paid 04/10/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Failed 5/4/2017 5/4/2017 05/04/2017
Misc
Corrective Action Required
05/04/2017
- re-wire electrical so hood and duct is accessible . install fire alarm and test with FD. schedule final inspection when ready
Alternate Protection Systems Inspection Passed 5/18/2017 05/18/2017
All Rough Inspection - Commercial Passed 05/31/2017
Misc
Resolved
05/31/2017
- re-wire electrical so hood and duct is accessible . install fire alarm and test with FD. schedule final inspection when ready
Final Inspection - Commercial Passed 05/31/2017
Documents & Images
Date Uploaded File Type Document Name
03/30/2017 Letter Fire Building Plan Review
03/31/2017 Letter Codes P/R Corrections Document
04/06/2017 Letter Fire Building Plan Review
04/10/2017 Letter Codes Plan Review Conditions
04/10/2017 Receipt Receipt for transaction: 2017-001325
04/10/2017 Letter Codes Building Permit
05/04/2017 Letter Inspection Summary
05/31/2017 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home