RED SUMMIT FAIR LLC
REPAIR REPLACE UPGRADE
REPLACING 100 AMP SERVICE FOR THE NEW DICKS PARKING LOT
03/14/2017
03/14/2017
04/11/2017
Locations
Contacts
STACO ELECTRIC CONSTRUCTION COMPANY INC, Address:11030 HICKMAN MILLS DR, Phone:(816) 765-7112  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 03/14/2017 03/14/2017
Development Center
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Repair/Replace/Upgrade $30.00 $30.00 Paid 03/14/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Failed 3/21/2017 3/21/2017 03/21/2017
Misc
Corrective Action Required
03/21/2017
SERVICE CONFIGURATION HAS BEEN CHANGED. TRANSFORMER SHOWN ON APPROVED DRAWING IS NOT IN PLACE.
Misc
Corrective Action Required
03/21/2017
ALUMINUM CONDUCTORS ALLOWED ONLY IF APPROVED BY A/E.
Misc
Corrective Action Required
03/21/2017
GROUNDING NOT PER APPROVED DRAWING. APPARENTLY NO G.E.C. RUN TO WATER LINE OR TO BUILDING STEEL.
Misc
Corrective Action Required
03/21/2017
OLD PANEL RE-USED FOR PERMANENT SERVICE
Electrical Service Inspection Passed 4/11/2017 04/11/2017
Misc
Resolved
04/11/2017
SERVICE CONFIGURATION HAS BEEN CHANGED. TRANSFORMER SHOWN ON APPROVED DRAWING IS NOT IN PLACE.
Misc
Resolved
04/11/2017
ALUMINUM CONDUCTORS ALLOWED ONLY IF APPROVED BY A/E.
Misc
Resolved
04/11/2017
GROUNDING NOT PER APPROVED DRAWING. APPARENTLY NO G.E.C. RUN TO WATER LINE OR TO BUILDING STEEL.
Misc
Resolved
04/11/2017
OLD PANEL RE-USED FOR PERMANENT SERVICE
Final Electrical Inspection - Commercial Passed 4/11/2017 04/11/2017
Documents & Images
Date Uploaded File Type Document Name
03/14/2017 Receipt Receipt for transaction: 2017-000895
03/14/2017 Letter Codes Building Permit
03/15/2017 Scope of Work DOC031517-021
04/07/2017 Engineer Report/Study DOC040717-002
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home