Permit Application Status

PRCOM20170010


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20170010
Building Permit - Commercial
Certificate of Occupancy
GALE COMMUNITIES INC
ALTERATION COMMERCIAL
REMOVE 2 OFFICES FOR OPEN OFFICE SPACE *drawings are in plan review file
01/04/2017
01/05/2017
02/09/2017
Locations
Contacts
MID-AMERICA CONTRACTORS INC, Address:1400 IRON, Phone:(816) 221-4516  
H & S ELECTRIC, Address:4901 ANTIOCH RD, Phone:(913) 206-1486  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 105  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 05/24/2017
Joe Dir
Sprinkler Plan Review Released for Construction 05/24/2017
Joe Dir
Fire Plan Review Approved with Conditions 01/17/2017 01/05/2017
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
01/05/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY MODIFICATIONS TO BE DONE TO THE FIRE ALARM SYSTEM. (INFORMATION PURPOSES)
Construction documents - Fire protection systems
Corrective Action Required
01/05/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY MODIFICATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM. (INFORMATION PURPOSES)
Installation acceptance testing
Corrective Action Required
01/05/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING OF THE MODIFICATIONS DONE TO THE FIRE ALARM SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 8126-969-1300. (INFROMATION PURPOSES)
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
01/05/2017

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ALL REQUIRED SERVICE AND MAINTENANCE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE SYSTEMS RISER. (VERIFIED AT INSPECTION)
Building Plan Review Approved 01/17/2017 01/04/2017
Joe Frogge
Licensed Contractors Approved 01/17/2017 01/04/2017
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $30.00 $30.00 Paid 01/05/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Passed 2/7/2017 2/7/2017 02/07/2017
Above Ceiling Inspection Passed 02/07/2017
Rough Electrical Inspection - Commercial Passed 02/07/2017
Final Electrical Inspection - Commercial Passed 02/07/2017
In-wall Inspection Passed 02/07/2017
Occupancy Inspection - Codes Commercial Full C of O 02/09/2017
Occupancy Inspection - Fire Passed 06/19/2017
Documents & Images
Date Uploaded File Type Document Name
01/05/2017 Letter Fire Building Plan Review
01/05/2017 Letter Codes Plan Review Conditions
01/05/2017 Receipt Receipt for transaction: 2017-000026
01/05/2017 Letter Codes Building Permit
02/07/2017 Letter Inspection Summary
02/09/2017 Letter Codes Final Certificate of Occupancy
02/10/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home