Permit Application Status

PRCOM20163150


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20163150
Building Permit - Commercial
Certificate of Occupancy
RAVID LEE SUMMIT LLC
ALTERATION COMMERCIAL
INTERIOR ALTERATIONS TO EXISTING OFFICE
12/08/2016
01/17/2017
01/28/2017
Locations
Contacts
COX BUILDERS INC, Address:P O BOX 1389, Phone:(704) 906-5737  
MY AMERICAN DREAM LLC, Address:1900 SW OAKLEY AVE, Phone:(785) 554-7077  
MIDWEST ELECTRICAL SERVICE INC, Address:2501 NW 85TH TER, Phone:(816) 726-9251  
R. GARY GLUECK ARCHITECTURE, Address:3797 LOOP RD, Phone:(252) 459-5900  
RAVID LEE SUMMIT LLC, Address:1901 HARRISON ST FL 2ND  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 12/20/2016 01/11/2017
Joe Frogge
LC - General Contractor
Resolved
01/11/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
01/11/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Alarm Plan Review Released for Construction 12/31/2016
Joe Dir
Sprinkler Plan Review Released for Construction 12/31/2016
Joe Dir
Fire Plan Review Approved with Conditions 12/20/2016 12/13/2016
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
12/13/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY MODIFICATIONS TO BE DONE TO THE FIRE ALARM SYSTEM.
Construction documents - Fire protection systems
Corrective Action Required
12/13/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY MODIFICATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM.
Installation acceptance testing
Corrective Action Required
12/13/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING OF ANY MODIFICATIONS TO THE FIRE ALARM SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE TESTING CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
12/13/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ALL REQUIRED SERVICE/MAINTENANCE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE SYSTEMS RISER. (VERIFIED AT INSPECTION)
Portable fire extinguishers - general
Corrective Action Required
12/13/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE ONE 2A-10BC (5POUND) FIRE EXTINGUISHER.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
12/13/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT THE FIRE EXTINGUISHER ON A NORMAL PATH OF TRAVEL CLOSE TO AN EXIT. (VERIFIED AT INSPECTION)
Address numbers required
Corrective Action Required
12/13/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 48 ON THE EXTERIOR OF THE FRONT AND REAR DOORS IN A CONTRASTING COLOR. ADDRESS SHALL BE READABLE FROM THE ROADWAY. (VERIFIED AT INPECTION)
Building Plan Review Approved 12/20/2016 12/12/2016
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $131.96 $131.96 Paid 01/17/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 1/20/2017 1/20/2017 01/20/2017
Above Ceiling Inspection Passed 1/26/2017 1/26/2017 01/26/2017
Occupancy Inspection - Codes Commercial Not Ready 1/27/2017 1/27/2017 01/27/2017
Misc
Corrective Action Required
01/27/2017
FIRE DEPARTMENT APPROVAL REQUIRED
Misc
Corrective Action Required
01/27/2017
AFFIX PERMANENT ADDRESS LABEL TO ELECTRICAL SERVICE EQUIPMENT
Misc
Corrective Action Required
01/27/2017
ELECT RECEPTS AT RR'S INOP
Misc
Corrective Action Required
01/27/2017
ACCESSIBLE RESTROOM SIGNS TO BE MOUNTED ON DOORS
Misc
Corrective Action Required
01/27/2017
BREAKTHROUGH OPENING @ SE CORNER PROPOSED TO BE ADDED TO PERMIT SCOPE. A/E REVISION REQUIRED.
Misc
Corrective Action Required
01/27/2017
OK TO MOVE IN OFFIE FURNITURE. ELECT RECEPTS AT DEMOUNTABLE PARTITIONS SUBJECT TO TEST/APPROVAL WHEN INSTALLED.
Occupancy Inspection - Fire Passed 1/27/2017 01/27/2017
Occupancy Inspection - Codes Commercial Full C of O 1/28/2017 01/28/2017
Misc
Resolved
01/28/2017
FIRE DEPARTMENT APPROVAL REQUIRED
Misc
Resolved
01/28/2017
AFFIX PERMANENT ADDRESS LABEL TO ELECTRICAL SERVICE EQUIPMENT
Misc
Resolved
01/28/2017
ELECT RECEPTS AT RR'S INOP
Misc
Resolved
01/28/2017
ACCESSIBLE RESTROOM SIGNS TO BE MOUNTED ON DOORS
Misc
Resolved
01/28/2017
BREAKTHROUGH OPENING @ SE CORNER PROPOSED TO BE ADDED TO PERMIT SCOPE. A/E REVISION REQUIRED.
Misc
Resolved
01/28/2017
OK TO MOVE IN OFFICE FURNITURE. ELECT RECEPTS AT DEMOUNTABLE PARTITIONS SUBJECT TO TEST/APPROVAL WHEN INSTALLED.
Documents & Images
Date Uploaded File Type Document Name
12/13/2016 Letter Fire Building Plan Review
01/03/2017 email to applicant
01/11/2017 Letter Codes Plan Review Conditions
01/17/2017 Receipt Receipt for transaction: 2017-000142
01/17/2017 Letter Codes Building Permit
01/20/2017 Letter Inspection Summary
01/26/2017 Letter Inspection Summary
01/27/2017 Letter Inspection Summary
01/28/2017 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home