Summary
PRCOM20162850
Building Permit - Commercial
Certificate of Occupancy
DRIENIK INVESTMENTS LLC
CHANGE OF TENANT
CHANGE OF USE FROM OFFICE/WAREHOUSE TO WELDING COMPANY **drawing is in plan review file
11/02/2016
11/21/2016
11/29/2016
Locations
Contacts
DRIENIK INVESTMENTS LLC, Address:1009 SE BROWNING ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 11/14/2016 11/07/2016
Joe Dir
Misc
Corrective Action Required
11/07/2016

MARKING HOT AREAS: 3503.6 Signage. Visible hazard identification signs shall be provided where required by Chapter 50. Where the hot work area is accessible to persons other than the operator of the hot work equipment, conspicuous signs shall be posted to warn others before they enter the hot work area. Such signs shall display the following warning: CAUTION HOT WORK IN PROGRESS STAY CLEAR (VERIFIED AT INSPECTION)
Material safety and data sheets
Corrective Action Required
11/07/2016

2012 IFC 407.2- Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. (INFORMATION PURPOSES) THE BUILDING WILL BE POSTED AT EACH ENTRANCE TO THE WELDING AREAS / STORAGE AREAS WITH NFPA 704 PLACARDS WITH THE MSDS HAZARD RATINGS OF THE WELDING GASES. (VERIFIED AT INSPECTION)
Address numbers required
Corrective Action Required
11/07/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 1012 ON THE EXTERIOR OF THE BUILDING IN A CONTRASTING COLOR TO THE BACKGROUND READABLE FROM THE ROADWAY (BROWNING ST) (VERIFIED AT INSPECTION)
Portable fire extinguishers - general
Corrective Action Required
11/07/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. 3504.2.6 Fire extinguisher. A minimum of one portable fire extinguisher complying with Section 906 and with a minimum 2-A:20-B:C rating shall be readily accessible within 30 feet (9144 mm) of the location where hot work is performed. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
11/07/2016

5303.4 Marking. Stationary and portable compressed gas containers, cylinders, tanks and systems shall be marked in accordance with Sections 5303.4.1 through 5303.4.3. 5303.4.1 Stationary compressed gas containers, cylinders and tanks. Stationary compressed gas containers, cylinders and tanks shall be marked with the name of the gas and in accordance with Sections 5003.5 and 5003.6. Markings shall be visible from any direction of approach. 5303.4.2 Portable containers, cylinders and tanks. Portable compressed gas containers, cylinders and tanks shall be marked in accordance with CGA C-7. 5303.4.3 Piping systems. Piping systems shall be marked in accordance with ASME A13.1. Markings used for piping systems shall consist of the content’s name and include a direction-of-flow arrow. Markings shall be provided at each valve; at wall, floor or ceiling penetrations; at each change of direction; and at a minimum of every 20 feet (6096 mm) or fraction thereof throughout the piping run. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
11/07/2016

5303.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints. 2. Securing containers, cylinders and tanks on a cart or other mobile device designed for the movement of compressed gas containers, cylinders or tanks. 3. Nesting of compressed gas containers, cylinders and tanks at container filling or servicing facilities or in seller’s warehouses not accessible to the public. Nesting shall be allowed provided the nested containers, cylinders or tanks, if dislodged, do not obstruct the required means of egress. 4. Securing of compressed gas containers, cylinders and tanks to or within a rack, framework, cabinet or similar assembly designed for such use. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
11/07/2016

5303.6 Valve protection. Compressed gas container, cylinder and tank valves shall be protected from physical damage by means of protective caps, collars or similar devices in accordance with Sections 5303.6.1 and 5303.6.2. (VERIFIED AT INSPECTION)
Zoning Review Approved 11/14/2016 11/02/2016
Joe Frogge
Building Plan Review Approved 11/14/2016 11/02/2016
Joe Frogge
Licensed Contractors Approved 11/14/2016 11/02/2016
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $30.00 $30.00 Paid 11/21/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Codes Commercial Full C of O 11/29/2016 11/29/2016 11/29/2016
Occupancy Inspection - Fire Passed 11/29/2016 11/29/2016
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home

*PLEASE NOTE - You must be logged in with your registered user account to view any documents related to your permit